ASTM C1534-07e1
(Specification)Standard Specification for Flexible Polymeric Foam Sheet Insulation Used as a Thermal and Sound Absorbing Liner for Duct Systems
Standard Specification for Flexible Polymeric Foam Sheet Insulation Used as a Thermal and Sound Absorbing Liner for Duct Systems
ABSTRACT
This specification covers the composition, dimensions, and physical properties of flexible unfaced foam sheet, used to insulate interior surfaces of HVAC ducts, plenums and equipment used for the distribution of conditioned air. The flexible polymeric insulations of this specification are classified into Types I and II. Type I is a closed flexible foam. Type II is an open cell flexible foam. Following test methods shall be performed: apparent thermal conductivity; surface burning characteristics; hot service performance; water vapor sorption; water absorption; dimensional stability; odor emission; fungi resistance; erosion resistance; and sound absorption coefficient.
SCOPE
1.1 This specification covers the composition, dimensions, and physical properties of flexible unfaced foam sheet, used to insulate interior surfaces of HVAC ducts, plenums and equipment used for the distribution of conditioned air with a temperature of up to 250°F (121°C).
1.2 HVAC ducts, plenums and equipment systems typically operate between a temperature range of 50°F to 150°F (10°C to 65°C) and are designed to meet building code requirements of maximum temperatures of 250°F (121°C).
1.3 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory requirements prior to use.
General Information
Relations
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
´1
Designation: C1534 – 07
Standard Specification for
Flexible Polymeric Foam Sheet Insulation Used as a
1
Thermal and Sound Absorbing Liner for Duct Systems
This standard is issued under the fixed designation C1534; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1
´ NOTE—Section 1.3 was editorially revised in April 2010.
1. Scope C423 Test Method for Sound Absorption and Sound Ab-
sorption Coefficients by the Reverberation Room Method
1.1 This specification covers the composition, dimensions,
C518 Test Method for Steady-State Thermal Transmission
and physical properties of flexible unfaced foam sheet, used to
Properties by Means of the Heat Flow Meter Apparatus
insulate interior surfaces of HVAC ducts, plenums and equip-
C634 Terminology Relating to Building and Environmental
ment used for the distribution of conditioned air with a
Acoustics
temperature of up to 250°F (121°C).
C665 Specification for Mineral-Fiber Blanket Thermal In-
1.2 HVAC ducts, plenums and equipment systems typically
sulation for Light Frame Construction and Manufactured
operatebetweenatemperaturerangeof50°Fto150°F(10°Cto
Housing
65°C) and are designed to meet building code requirements of
C1045 PracticeforCalculatingThermalTransmissionProp-
maximum temperatures of 250°F (121°C).
erties Under Steady-State Conditions
1.3 The values stated in inch-pound units are to be regarded
C1071 Specification for Fibrous Glass Duct Lining Insula-
as standard. The values given in parentheses are mathematical
tion (Thermal and Sound Absorbing Material)
conversions to SI units that are provided for information only
C1104/C1104M Test Method for Determining the Water
and are not considered standard.
Vapor Sorption of Unfaced Mineral Fiber Insulation
1.4 This standard does not purport to address all of the
C1114 Test Method for Steady-State Thermal Transmission
safety concerns, if any, associated with its use. It is the
Properties by Means of the Thin-Heater Apparatus
responsibility of the user of this standard to establish appro-
C1304 Test Method for Assessing the Odor Emission of
priate safety and health practices and determine the applica-
Thermal Insulation Materials
bility of regulatory requirements prior to use.
C1338 Test Method for Determining Fungi Resistance of
2. Referenced Documents Insulation Materials and Facings
2
E84 Test Method for Surface Burning Characteristics of
2.1 ASTM Standards:
Building Materials
C168 Terminology Relating to Thermal Insulation
E176 Terminology of Fire Standards
C177 Test Method for Steady-State Heat Flux Measure-
E795 Practices for MountingTest Specimens During Sound
ments and Thermal Transmission Properties by Means of
Absorption Tests
the Guarded-Hot-Plate Apparatus
E2231 Practice for Specimen Preparation and Mounting of
C209 Test Methods for Cellulosic Fiber Insulating Board
Pipe and Duct Insulation Materials to Assess Surface
C390 Practice for Sampling and Acceptance of Thermal
Burning Characteristics
Insulation Lots
G21 Practice for Determining Resistance of Synthetic Poly-
C411 Test Method for Hot-Surface Performance of High-
meric Materials to Fungi
Temperature Thermal Insulation
2.2 Other Standards:
CAN/ULC-S102–03 Standard Method of Test for Surface
1
This specification is under the jurisdiction of ASTM Committee C16 on
Burning Characteristics of Building Materials andAssem-
Thermal Insulation and is the direct responsibility of Subcommittee C16.22 on
blies
Organic and Nonhomogeneous Inorganic Thermal Insulations.
Current edition approved Sept. 1, 2007. Published September 2007. Originally
3. Terminology
approved in 2002. Last previous edition approved in 2004 as C1534–04. DOI:
10.1520/C1534-07E01.
3.1 The definitions of terms used in this specification shall
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
beinaccordancewithTerminologiesC168,C634,andE176.In
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
case of any conflicts, Terminology C168 shall be the authority.
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1
---------------------- Page: 1 ----------------------
´1
C1534 – 07
3.2 Definitions of Terms Specific to This Standard: temperature in accordance with 12.1.The thermal conductivity
3.2.1 closed cell foam—a foam comprised of predominately for the average of any four randomly selected samples, shall
individual non interconnecting cells. not be more than 0.30 Btu-in./h-sq ft°F
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.