SCOPE
1.1 This specification covers cored, annular, concentric-lay-stranded conductors made from round soft copper wires, either uncoated or coated with tin, lead, or lead alloy for use as electrical conductors (Explanatory Note 1 and Note 2).
1.2 The constructions prescribed herein are suitable for bare conductors, or for conductors to be covered with weather-resistant (weather-proof) material, or for conductors to be insulated with rubber, varnished cloth, or impregnated paper, except types such as "oil-filled" or "gas-filled" (Explanatory Note 0).
1.3 Cored, annular conductor constructions not included in this specification shall be specifically agreed upon between the manufacturer and the purchaser when placing the order.
1.4 These constructions are not recommended for use as electric furnace leads where great flexibility is required and special conductor designs are indicated in consideration of the particular service requirements.
1.5 The SI values for density are regarded as the standard. For all other properties the inch-pound values are to be regarded as standard and the SI units may be approximate.
General Information
Relations
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: B 226 – 95 (Reapproved 2003)
Standard Specification for
Cored, Annular, Concentric-Lay-Stranded Copper
1
Conductors
This standard is issued under the fixed designation B 226; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
1. Scope ductors Having Bunch-Stranded Members, for Electrical
2
Conductors
1.1 This specification covers cored, annular, concentric-lay-
B 173 Specification for Rope-Lay-Stranded Copper Con-
stranded conductors made from round soft copper wires, either
ductors Having Concentric-Stranded Members, for Elec-
uncoated or coated with tin, lead, or lead alloy for use as
2
trical Conductors
electrical conductors (Explanatory Note 1 and Note 2).
B 174 Specification for Bunch-Stranded Copper Conduc-
1.2 The constructions prescribed herein are suitable for bare
2
tors for Electrical Conductors
conductors, or for conductors to be covered with weather-
B 189 Specification for Lead-Coated and Lead-Alloy-
resistant (weather-proof) material, or for conductors to be
2
Coated Soft Copper Wire for Electrical Purposes
insulated with rubber, varnished cloth, or impregnated paper,
B 263 Test Method for Determination of Cross-Sectional
except types such as “oil-filled” or “gas-filled” (Explanatory
2
Area of Stranded Conductors
Note 3).
B 354 Terminology Relating to Uninsulated Metallic Elec-
1.3 Cored, annular conductor constructions not included in
2
trical Conductors
this specification shall be specifically agreed upon between the
2.2 American National Standard:
manufacturer and the purchaser when placing the order.
3
ANSI C42.35 Definitions of Electrical Terms
1.4 These constructions are not recommended for use as
2.3 NIST:
electric furnace leads where great flexibility is required and
4
NBS Handbook 100—Copper Wire Tables
special conductor designs are indicated in consideration of the
particular service requirements.
3. Ordering Information
1.5 The SI values for density are regarded as the standard.
3.1 Orders for material under this specification shall include
For all other properties the inch-pound values are to be
the following information:
regarded as standard and the SI units may be approximate.
3.1.1 Quantity of each size,
2. Referenced Documents 3.1.2 Conductor size: circular-mil area (Section 7 and Table
1),
The following documents of the issue in effect at the time of
3.1.3 Whether coated or uncoated; if coated, designate type
reference form a part of these methods to the extent referenced
of coating (Section 11),
herein:
3.1.4 Specific kind and treatment of core material (Section
2.1 ASTM Standards:
2 4),
B 3 Specification for Soft or Annealed Copper Wire
3.1.5 Details of special-purpose lays, if required (see 6.1
B 8 Specification for Concentric-Lay-Stranded Copper
2 and 6.2 and Explanatory Note 3),
Conductors, Hard, Medium-Hard, or Soft
3.1.6 Package size (Section 14),
B 33 Specification for Tinned Soft or Annealed Copper
2
3.1.7 Lagging, if required (see 14.2),
Wire for Electrical Purposes
3.1.8 Special package marking, if required (Section 14), and
B 172 Specification for Rope-Lay-Stranded Copper Con-
3.1.9 Place of inspection (Section 13).
1
This specification is under the jurisdiction of ASTM Committee B01 on
3
Electrical Conductors and is the direct responsibility of Subcommittee B01.04 on Available from American National Standards Institute (ANSI), 25 W. 43rd St.,
Conductors of Copper and Copper Alloys. 4th Floor, New York, NY 10036.
4
Current edition approved October 1, 2003. Published October 2003. Originally NBS Handbook 100, available from National Technical Information Service
approved in 1948. Last previous edition approved in 1995 as B 226 – 95. (NTIS), U.S. Department of Commerce, 5285 Port Royal Rd., Springfield, VA
2
Annual Book of ASTM Standards, Vol 02.03. 22161.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1
---------------------- Page: 1 ----------------------
B 226 – 95 (2003)
TABLE 1 Construction of Cored, Annular, Concentric-Lay-Stranded Copper Conductors
Nominal Area of Number of Strands in Layers
Approximate Calculated Area of Maximum
Copper Diameter of
A
Diameter of Copper, Cross Outside Diameter,
Cross Wires, in.
Core, in. Section, cmils in.
1st 2nd 3rd Total
Section, cmils
5 000 000 2.875 0.1620 57 63 69 189 4 960 116 3.897
4 500 000 2.500 0.1620 50 56 62 168 4 408 992 3.517
4 000 000 2.250 0.1620 45 51 57 153 4 015 332 3.262
3 500 000 2.000 0.1620 40 45 52 137 3 595 428 3.007
3 000 000 1.625 0.1620 33 38 45 116 3 044 304 2.627
2 500 000 1.500 0.1440 34 40 46 120 2 488 320 2.394