(Test Method)Standard Test Method for Sampling and Testing Grout
Standard Test Method for Sampling and Testing Grout
SIGNIFICANCE AND USE
3.1 Grout used in masonry is a fluid mixture of cementitious materials and aggregate with a high water content for ease of placement.
3.1.1 During construction, grout is placed within or between absorptive masonry units. Excess water must be removed from grout specimens in order to provide compressive strength test results more nearly indicative of the grout strength in the wall. In this test method, molds are made from masonry units having the same absorption and moisture content characteristics as those being used in the construction.
3.2 This test method is used to either help select grout proportions by comparing test values or as a quality control test for uniformity of grout preparation during construction.
3.3 The physical exposure condition and curing of the grout are not exactly reproduced, but this test method does subject the grout specimens to absorption conditions similar to those experienced by grout in the wall.
Note 2: Test results of grout specimens taken from a wall should not be compared to test results obtained with this test method.
SCOPE
1.1 This test method covers procedures for both field and laboratory sampling and compression testing of grout used in masonry construction. Grout for masonry is specified under Specification C476.
Note 1: The testing agency performing this test method should be evaluated in accordance with Practice C1093.
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
General Information
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
´1
Designation: C1019 −18
Standard Test Method for
1
Sampling and Testing Grout
This standard is issued under the fixed designation C1019; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the U.S. Department of Defense.
1
ε NOTE—Subsection 10.5 was editorially corrected in October 2019.
1. Scope C511 Specification for Mixing Rooms, Moist Cabinets,
Moist Rooms, and Water Storage Tanks Used in the
1.1 This test method covers procedures for both field and
Testing of Hydraulic Cements and Concretes
laboratory sampling and compression testing of grout used in
C617 Practice for Capping Cylindrical Concrete Specimens
masonry construction. Grout for masonry is specified under
C1064/C1064M Test Method for Temperature of Freshly
Specification C476.
Mixed Hydraulic-Cement Concrete
NOTE 1—The testing agency performing this test method should be
C1093 Practice for Accreditation of Testing Agencies for
evaluated in accordance with Practice C1093.
Masonry
1.2 The values stated in inch-pound units are to be regarded
C1611/C1611M Test Method for Slump Flow of Self-
as standard. The values given in parentheses are mathematical
Consolidating Concrete
conversions to SI units that are provided for information only
and are not considered standard.
3. Significance and Use
1.3 This standard does not purport to address all of the
3.1 Groutusedinmasonryisafluidmixtureofcementitious
safety concerns, if any, associated with its use. It is the
materials and aggregate with a high water content for ease of
responsibility of the user of this standard to establish appro-
placement.
priate safety, health, and environmental practices and deter-
3.1.1 Duringconstruction,groutisplacedwithinorbetween
mine the applicability of regulatory limitations prior to use.
absorptive masonry units. Excess water must be removed from
1.4 This international standard was developed in accor-
grout specimens in order to provide compressive strength test
dance with internationally recognized principles on standard-
results more nearly indicative of the grout strength in the wall.
ization established in the Decision on Principles for the
In this test method, molds are made from masonry units having
Development of International Standards, Guides and Recom-
the same absorption and moisture content characteristics as
mendations issued by the World Trade Organization Technical
those being used in the construction.
Barriers to Trade (TBT) Committee.
3.2 This test method is used to either help select grout
proportionsbycomparingtestvaluesorasaqualitycontroltest
2. Referenced Documents
for uniformity of grout preparation during construction.
2
2.1 ASTM Standards:
3.3 The physical exposure condition and curing of the grout
C39/C39M Test Method for Compressive Strength of Cylin-
are not exactly reproduced, but this test method does subject
drical Concrete Specimens
the grout specimens to absorption conditions similar to those
C143/C143M Test Method for Slump of Hydraulic-Cement
experienced by grout in the wall.
Concrete
C476 Specification for Grout for Masonry
NOTE 2—Test results of grout specimens taken from a wall should not
be compared to test results obtained with this test method.
1
This test method is under the jurisdiction ofASTM Committee C12 on Mortars 4. Apparatus
and Grouts for Unit Masonry and is the direct responsibility of Subcommittee
4.1 Maximum-Minimum Thermometer.
C12.02 on Research and Methods of Test.
Current edition approved Jan. 1, 2018. Published February 2018. Originally
4.2 Straightedge, a steel straightedge not less than 6 in.
approved in 1984. Last previous edition approved in 2016 as C1019 – 16. DOI:
1
(152.4 mm) long and not less than ⁄16 in. (1.6 mm) in
10.1520/C1019-18E01.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or thickness.
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
4.3 TampingRod,around,straight,steelrodwithadiameter
Standards volume information, refer to the standard’s Document Summary page on
3 1
the ASTM website. of ⁄8 6 ⁄16 in. (10 6 2 mm) and a length of 12 6 4 inches.
*A Summary of Changes section appears at the end of this standard
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1
---------------------- Page: 1 ----------------------
´1
C1019 − 18
(300 6 100 millimetres). The rod shall have the tamping end
or both ends rounded to a hemispherical tip of the same
diameter as the rod.
4.4 Nonabsorbent Blocks and Spacers, nonabsorbent, rigid
square
...
This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
´1
Designation: C1019 − 18 C1019 − 18
Standard Test Method for
1
Sampling and Testing Grout
This standard is issued under the fixed designation C1019; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the U.S. Department of Defense.
1
ε NOTE—Subsection 10.5 was editorially corrected in October 2019.
1. Scope
1.1 This test method covers procedures for both field and laboratory sampling and compression testing of grout used in masonry
construction. Grout for masonry is specified under Specification C476.
NOTE 1—The testing agency performing this test method should be evaluated in accordance with Practice C1093.
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of
regulatory limitations prior to use.
1.4 This international standard was developed in accordance with internationally recognized principles on standardization
established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued
by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
2. Referenced Documents
2
2.1 ASTM Standards:
C39/C39M Test Method for Compressive Strength of Cylindrical Concrete Specimens
C143/C143M Test Method for Slump of Hydraulic-Cement Concrete
C476 Specification for Grout for Masonry
C511 Specification for Mixing Rooms, Moist Cabinets, Moist Rooms, and Water Storage Tanks Used in the Testing of Hydraulic
Cements and Concretes
C617 Practice for Capping Cylindrical Concrete Specimens
C1064/C1064M Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
C1093 Practice for Accreditation of Testing Agencies for Masonry
C1611/C1611M Test Method for Slump Flow of Self-Consolidating Concrete
3. Significance and Use
3.1 Grout used in masonry is a fluid mixture of cementitious materials and aggregate with a high water content for ease of
placement.
3.1.1 During construction, grout is placed within or between absorptive masonry units. Excess water must be removed from
grout specimens in order to provide compressive strength test results more nearly indicative of the grout strength in the wall. In
this test method, molds are made from masonry units having the same absorption and moisture content characteristics as those
being used in the construction.
3.2 This test method is used to either help select grout proportions by comparing test values or as a quality control test for
uniformity of grout preparation during construction.
1
This test method is under the jurisdiction of ASTM Committee C12 on Mortars and Grouts for Unit Masonry and is the direct responsibility of Subcommittee C12.02
on Research and Methods of Test.
Current edition approved Jan. 1, 2018. Published February 2018. Originally approved in 1984. Last previous edition approved in 2016 as C1019 – 16. DOI:
10.1520/C1019-18.10.1520/C1019-18E01.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
*A Summary of Changes section appears at the end of this standard
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1
---------------------- Page: 1 ----------------------
´1
C1019 − 18
3.3 The physical exposure condition and curing of the grout are not exactly reproduced, but this test method does subject the
grout specimens to absorption conditions similar to those experienced by grout in the wall.
NOTE 2—Test results of grout specimens taken from a wall should not be compared to test results obtained with this test method.
4. Apparatus
4.1 Maximum-Minimum Thermometer.
1
4.2 Straightedge, a steel straightedge not less than 6 in. (152.4 mm) long and not less than ⁄16 in. (1.6 mm) in thick
...