Standard Test Methods for Physical Assault on Ventilation Grilles for Detention and Correctional Facilities

SIGNIFICANCE AND USE
A major concern for administration officials is security of barriers used in detention/correctional facilities. These test methods are designed to identify the security levels for ventilation grilles mounted within these barriers.
The purpose of these tests is to approximate levels of abuse to which grilles will potentially be subjected in the field, and to provide assurance of protection to the public, facility administrative personnel, and inmates.
SCOPE
1.1 These test methods cover requirements for simulated service tests and testing equipment for determining the performance characteristics of ventilation grilles used in secure areas, including detention and correctional facilities. The testing equipment provides for the setup and testing of specimen grilles and mounting systems. It is recognized that, in order to meet the intent of these test methods, ventilation grilles must be compatible with the level of performance require by Test Methods F2322.
1.2 It is the intent of these test methods to ensure that security ventilation grilles meet minimum performance levels to control the passage of unauthorized materials into secure areas, to confine inmates, to resist vandalism, and to delay or frustrate escape, or both. It is also the responsibility of the user of these test methods to insure that the grille selected is appropriate, based on relevant regulatory, health, and safety concerns and requirements. Such concerns include, but are not limited to, injury and suicide avoidance. These test methods do not quantify such concerns.
1.3 Take care to provide access to return and exhaust ducts for cleaning as required by NFPA 90A. If access cannot be provided though an interstitial space behind walls or ceiling, the use of filter grilles needs to be considered as an option. When filter grilles are provided, filters shall have a minimum UL-900 class 2 rating, and a filter replacement program needs to be in place at the facility.
1.4 Airflow performance shall be catalogued in accordance with ASHRAE 70–91. Manufacturer’s catalog data must include grade level achieved.
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
31-May-2012
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM F2542-05(2012) - Standard Test Methods for Physical Assault on Ventilation Grilles for Detention and Correctional Facilities
English language
5 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: F2542 − 05 (Reapproved 2012)
Standard Test Methods for
Physical Assault on Ventilation Grilles for Detention and
1
Correctional Facilities
This standard is issued under the fixed designation F2542; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 1.6 This standard does not purport to address all of the
safety concerns, if any, associated with its use. It is the
1.1 These test methods cover requirements for simulated
responsibility of the user of this standard to establish appro-
service tests and testing equipment for determining the perfor-
priate safety and health practices and determine the applica-
mancecharacteristicsofventilationgrillesusedinsecureareas,
bility of regulatory limitations prior to use.
including detention and correctional facilities. The testing
equipment provides for the setup and testing of specimen
2. Referenced Documents
grilles and mounting systems. It is recognized that, in order to
2
meet the intent of these test methods, ventilation grilles must 2.1 ASTM Standards:
F2322Test Methods for Physical Assault on Vertical Fixed
be compatible with the level of performance require by Test
Methods F2322. Barriers for Detention and Correctional Facilities
3
2.2 NFPA Standard:
1.2 It is the intent of these test methods to ensure that
NFPA90AStandard for the Installation ofAir Conditioning
security ventilation grilles meet minimum performance levels
and Ventilating Systems
to control the passage of unauthorized materials into secure
4
areas, to confine inmates, to resist vandalism, and to delay or
2.3 UL Standard:
frustrateescape,orboth.Itisalsotheresponsibilityoftheuser
UL-900Standard for Air Filter Units
of these test methods to insure that the grille selected is
5
2.4 ASHRAE Standard:
appropriate, based on relevant regulatory, health, and safety
ASHRAE 70–91Method of Testing for Rating the Perfor-
concerns and requirements. Such concerns include, but are not
mance of Air Outlets and Inlets
limitedto,injuryandsuicideavoidance.Thesetestmethodsdo
not quantify such concerns.
3. Terminology
1.3 Take care to provide access to return and exhaust ducts
3.1 Definitions:
for cleaning as required by NFPA 90A. If access cannot be
3.1.1 bars—method of reinforcement or prevention of
provided though an interstitial space behind walls or ceiling,
egress installed in the sleeve. Bars may be of a material, size,
the use of filter grilles needs to be considered as an option.
shape, and spacing as selected by the manufacturer to provide
When filter grilles are provided, filters shall have a minimum
the desired test results and meet applicable federal, state, and
UL-900 class 2 rating, and a filter replacement program needs
local jail and prison standards.
to be in place at the facility.
3.1.2 diffuser—ceiling-mounted device designed to provide
1.4 Airflow performance shall be catalogued in accordance
deflection of air flow.
with ASHRAE 70–91. Manufacturer’s catalog data must in-
3.1.3 filter grille—grille incorporating a replaceable filter in
clude grade level achieved.
the grille sleeve or body.
1.5 The values stated in inch-pound units are to be regarded
as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
and are not considered standard.
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website.
3
Available from National Fire Protection Association (NFPA), 1 Batterymarch
1
These test methods are under the jurisdiction of ASTM Committee F33 on Park, Quincy, MA 02269-9101.
4
Detention and Correctional Facilities and are the direct responsibility of Subcom- Available from Underwriters Laboratories (UL), Corporate Progress, 333
mittee F33.04 on Detention Hardware. Pfingsten Rd., Northbrook, IL 60062.
5
Current edition approved June 1, 2012. Published August 2012. Originally Available from American Society of Heating, Refrigerating, and Air-
approved in 2005. Last previous edition approved in 2005 as F2542–05. DOI: Conditioning Engineers, Inc. (ASHRAE), 1791 Tullie Circle, NE, Atlanta, GA
10.1520/F2542-05R12. 30329.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
F2542 − 05 (2012)
3.1.4 forcible egress—opening created in the specimen 6.1.1 Grilles must be available in 4 in. (101 mm) incre-
which allows a 5 in. × 8 i
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.