Amendment 1 - Low-voltage switchgear and controlgear - Part 4-2: Contactors and motor-starters - AC semiconductor motor controllers and starters

The contents of the corrigendum of March 2002 have been included in this copy.

Amendement 1 - Appareillage à basse tension - Partie 4-2: Contacteurs et démarreurs de moteurs - Gradateurs et démarreurs à semiconducteurs de moteurs à courant alternatif

Le contenu du corrigendum de mars 2002 a été pris en considération dans cet exemplaire.

General Information

Status
Published
Publication Date
15-Oct-2001
Current Stage
DELPUB - Deleted Publication
Completion Date
18-May-2011
Ref Project

Relations

Buy Standard

Standard
IEC 60947-4-2:1999/AMD1:2001 - Amendment 1 - Low-voltage switchgear and controlgear - Part 4-2: Contactors and motor-starters - AC semiconductor motor controllers and starters Released:10/16/2001 Isbn:2831860490
English and French language
41 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


NORME CEI
INTERNATIONALE IEC
60947-4-2
INTERNATIONAL
STANDARD
AMENDEMENT 1
AMENDMENT 1
2001-10
Amendement 1
Appareillage à basse tension –
Partie 4-2:
Contacteurs et démarreurs de moteurs –
Gradateurs et démarreurs à semiconducteurs de
moteurs à courant alternatif
Amendment 1
Low-voltage switchgear and controlgear –
Part 4-2:
Contactors and motor-starters –
AC semiconductor motor controllers and starters
 IEC 2001 Droits de reproduction réservés  Copyright - all rights reserved
International Electrotechnical Commission 3, rue de Varembé Geneva, Switzerland
Telefax: +41 22 919 0300 e-mail: inmail@iec.ch IEC web site http://www.iec.ch
CODE PRIX
Commission Electrotechnique Internationale
S
PRICE CODE
International Electrotechnical Commission
Pour prix, voir catalogue en vigueur
For price, see current catalogue

– 2 – 60947-4-2 amend. 1  CEI:2001
AVANT-PROPOS
Le présent amendement a été établi par le sous-comité 17B: Appareillage à basse tension, du
comité d'études 17 de la CEI: Appareillage.
Le texte de cet amendement est issu des documents suivants:
FDIS Rapport de vote
17B/1143/FDIS 17B/1168/RVD
Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à l'approbation de cet amendement.
Le comité a décidé que le contenu de la publication de base et de ses amendements ne sera
pas modifié avant 2003. A cette date, la publication sera
• reconduite;
• supprimée;
• remplacée par une édition révisée, ou
• amendée.
Le contenu du corrigendum de mars 2002 a été pris en considération dans cet exemplaire.
____________
Page 2
SOMMAIRE
Ajouter, à la page 4, le titre des nouvelles annexes et nouveaux tableaux suivants:
Annexe I (normative) Circuit d'essai modifié pour l'essai de court-circuit des gradateurs et
démarreurs à semiconducteurs de moteurs
Annexe J (informative) Diagramme pour définir les essais des gradateurs à semiconducteurs
à dérivation
Tableau 17 – Limites d’échauffement pour les bobines isolées dans l’air et dans l’huile
Tableau 18 – Données pour les cycles d'essai de service intermittent
Page 6
AVANT-PROPOS
Changer, à la page 8, les deux premiers alinéas pour lire:
Les annexes A, B, C, D et I font partie intégrante de cette norme.
Les annexes E, F, G, H et J sont données uniquement à titre d'information.

60947-4-2 Amend. 1  IEC:2001 – 3 –
FOREWORD
This amendment has been prepared by subcommittee 17B: Low-voltage switchgear and
controlgear, of IEC technical committee 17: Switchgear and controlgear.
The text of this amendment is based on the following documents:
FDIS Report on voting
17B/1143/FDIS 17B/1168/RVD
Full information on the voting for the approval of this amendment can be found in the report
on voting indicated in the above table.
The committee has decided that the contents of the base publication and its amendments will
remain unchanged until 2003. At this date, the publication will be
• reconfirmed;
• withdrawn;
• replaced by a revised edition, or
• amended.
The contents of the corrigendum of March 2002 have been included in this copy.
___________
Page 3
CONTENTS
Add, on page 5, the titles of the following new annexes and tables:
Annex I (normative) Modified test circuit for short-circuit testing of semiconductor motor
controllers and starters
Annex J (informative) Flowchart for constructing bypassed semiconductor controllers tests
Table 17 – Temperature rise limits for insulated coils in air and in oil
Table 18 – Intermittent duty test cycle data
Page 7
FOREWORD
Replace, on page 9, the first two paragraphs by the following:
Annexes A, B, C, D and I form an integral part of this standard.
Annexes E, F, G, H and J are for information only.

– 4 – 60947-4-2 amend. 1  CEI:2001
Page 12
1 Domaine d'application et objet
Remplacer le deuxième alinéa existant par ce qui suit:
La présente norme définit les caractéristiques des gradateurs et démarreurs avec ou sans
dispositif de court-circuitage.
Page 14
2 Références normatives
Insérer dans la liste existante le titre de la norme suivante:
CEI 60085:1984, Evaluation et classification thermiques de l'isolation électrique
Ajouter, après «CEI 60947-1:1999, Appareillage à basse tension – Partie 1: Règles
générales», ce qui suit:
Amendement 1 (2000)
Page 16
3 Définitions
Remplacer, à la page 20, le titre existant de la figure 1 par le nouveau titre suivant:
Figure 1 – Appareils à semiconducteurs de commande de moteur
A l’intérieur de la figure 1, dans la première colonne, remplacer:
«Gradateur à semiconducteur de moteur (toute variante)» par «Gradateur à semiconducteurs
de moteur (variantes 1, 2, 3)»
«Démarreur à semiconducteurs de moteur (toute variante)» par «Démarreur à
semiconducteurs de moteur (variantes 1, 2, 3)»

60947-4-2 Amend. 1  IEC:2001 – 5 –
Page 13
1 Scope and object
Replace the existing second paragraph by the following:
This standard characterizes controllers and starters with and without bypass means.
Page 15
2 Normative references
Insert, in the existing list, the title of the following standard:
IEC 60085:1984, Thermal evaluation and classification of electrical insulation
Add, after "IEC 60947-1:1999, Low-voltage switchgear and controlgear – Part 1: General
rules" the following:
Amendment 1 (2000)
Page 17
3 Definitions
Replace, on page 21, the title of the existing figure 1 by the following new title:
Figure 1 – Semiconductor motor control devices
Within figure 1
In the first column, replace:
"Semiconductor motor controller (all forms)" by "Semiconductor motor controller (forms 1, 2, 3)"
"Semiconductor motor starter (all forms)" by "Semiconductor motor starter (forms 1, 2, 3)"

– 6 – 60947-4-2 amend. 1  CEI:2001
Ajouter, après la ligne «Gradateur de moteur hybride HxB**», les nouvelles lignes suivantes:
Contact mécanique en
parallèle
Gradateur à dérivation L
T
Gradateur à semiconducteurs
(Variantes 1,2, 3)
Contact mécanique en
parallèle
Gradateur hybride de moteur
Gradateur hybride de
L T
moteur à dérivation
Contact
Gradateur à
mécanique
semiconducteurs
en série
(Variantes HxA, HxB) (voir 8.2.4.2.3)
Ajouter, à la page 28, après la définition 3.1.23, la nouvelle définition suivante:
3.1.24
gradateur à dérivation
matériel dans lequel les contacts principaux d’un appareil mécanique de connexion sont
connectés en parallèle avec les bornes du circuit principal d’un appareil de connexion à
semiconducteurs, et dont les dispositifs de commande des deux appareils de connexion sont
coordonnés
Page 42
5.3.5.3.1 Caractéristiques de démarrage des moteurs à cage d'écureuil et des moteurs
de compresseurs hermétiques de réfrigération
Remplacer le point b) existant par ce qui suit:
b) Un seul sens de rotation avec aptitude au contrôle de phase permettant de commander
l'accélération jusqu'à la vitesse normale. Les gradateurs et les démarreurs ont des
caractéristiques assignées pour un service intermittent seulement (AC-53b, AC-58b); par
exemple, après le démarrage, le moteur peut être relié à un circuit qui court-circuite les
semiconducteurs de puissance.
60947-4-2 Amend. 1  IEC:2001 – 7 –
Add, after the row "Hybrid motor controller HxB**", the following new rows:
Parallel mechanical
contact
Bypassed controller
L
T
Semiconductor controller
(Forms 1,2, 3)
Parallel mechanical
contact
Hybrid motor controller
Bypassed hybrid motor
L T
controller
Series Semiconductor
mechanical
controller
contact
(Forms HxA, HxB) (see 8.2.4.2.3)
Page 29
Add, after definition 3.1.23, the following new definition:
3.1.24
bypassed controller
equipment wherein the main circuit contacts of a mechanical switching device are connected
in parallel with the main circuit terminals of a semiconductor switching device, and wherein
the operating means of the two switching devices are co-ordinated
Page 43
5.3.5.3.1 Starting characteristics of squirrel cage and hermetic refrigeration motors
Replace the existing item b) by the following:
b) One direction of rotation with the inclusion of phase-control capability to provide controlled
acceleration to normal speed. Controllers and starters are rated for intermittent duty only
(AC-53b, AC-58b); for example after starting, the motor may be connected into a circuit
that bypasses the power semiconductors.

– 8 – 60947-4-2 amend. 1  CEI:2001
Page 46
Tableau 2 – Catégories d'emploi
Remplacer le tableau existant par le nouveau tableau suivant:
Catégorie Applications caractéristiques
d'emploi
AC-52a Commande statorique de moteurs à bagues: service de 8 h avec des courants de démarrage,
d'accélération et de vitesse normale
AC-52b Commande statorique de moteurs à bagues: service intermittent
AC-53a Commande de moteurs à cage d'écureuil: service de 8 h avec des courants de démarrage,
d'accélération et de vitesse normale
AC-53b Commande de moteurs à cage d'écureuil: service intermittent
AC-58a Commande de compresseurs hermétiques de réfrigération avec réarmement automatique des
déclencheurs de surcharge: service de 8 h avec des courants de démarrage, d'accélération et de
vitesse normale
AC-58b Commande de compresseurs hermétiques de réfrigération avec réarmement automatique des
déclencheurs de surcharge: service intermittent
NOTE 1 Le dispositif de court-circuitage du gradateur à semiconducteurs peut faire partie intégrante du
gradateur/démarreur ou être installé séparément.
NOTE 2 Un moteur de compresseur hermétique de réfrigération est un appareil combiné comprenant un
compresseur et un moteur, tous deux enfermés dans le même boîtier sans arbre ou joint d'arbre extérieur, le
moteur fonctionnant dans le réfrigérant.
Page 54
8.1.3 Distances d'isolement et lignes de fuite
Remplacer le texte existant par ce qui suit:
Le paragraphe 7.1.3 de la CEI 60947-1 est applicable avec la prescription complémentaire
suivante. Les lignes de fuite minimales spécifiées s'appliquent seulement aux dimensions
extérieures au semiconducteur.
Page 58
Ajouter, après 8.2.1.5.2, les nouveaux paragraphes 8.2.1.6 à 8.2.1.9 suivants:
8.2.1.6 Composants des gradateurs à dérivation ayant subi des essais de type
8.2.1.6.1 Des appareils de connexion qui satisfont aux prescriptions de leur propre norme de
produit doivent être considérés comme des appareils ayant partiellement subi des essais de
type et sont soumis aux prescriptions complémentaires suivantes:
a) les échauffements des appareils mécaniques de connexion doivent satisfaire à 8.2.2;
b) les pouvoirs de fermeture et de coupure des appareils mécaniques de connexion doivent
satisfaire à 8.2.4.2;
c) les dispositifs de connexion à semiconducteurs doivent satisfaire à 8.2.4.1 pour la
catégorie d’emploi AC-53b.
60947-4-2 Amend. 1  IEC:2001 – 9 –
Page 47
Table 2 – Utilization categories
Replace the existing table by the following new table:
Utilization Typical application
category
AC-52a Control of slip ring motor stators: 8 h duty with on-load currents for start, acceleration, run
AC-52b Control of slip ring motor stators: intermittent duty
AC-53a Control of squirrel cage motors: 8 h duty with on-load currents for start, acceleration, run
AC-53b Control of squirrel cage motors: intermittent duty
AC-58a Control of hermetic refrigerant compressor motors with automatic resetting of overload releases:
8 h duty with on-load currents for start, acceleration, run
AC-58b Control of hermetic refrigerant compressor motors with automatic resetting of overload releases:
intermittent duty
NOTE 1 The means of bypassing the semiconductor controller may be integral with the controller/starter or
installed separately.
NOTE 2 A hermetic refrigerant compressor motor is a combination consisting of a compressor and motor, both
of which are enclosed in the same housing, with no external shaft or shaft seals, the motor operating in the
refrigerant.
Page 55
8.1.3 Clearances and creepage distances
Replace the existing text by the following new text:
Subclause 7.1.3 of IEC 60947-1 applies with the following additional requirement. Specified
minimum creepage distances only apply to those dimensions that are external to the
semiconductor.
Page 59
Add, after 8.2.1.5.2, the following new subclauses 8.2.1.6 to 8.2.1.9:
8.2.1.6 Type tested components in bypassed controllers
8.2.1.6.1 Switching devices which meet the requirements of their own relevant product
standard shall be considered as partially type tested devices subject to the following
additional requirements:
a) the temperature rises of mechanical switching devices shall comply with 8.2.2;
b) the making and breaking capacity of mechanical switching devices shall comply with
8.2.4.2;
c) semiconductor switching devices shall comply with 8.2.4.1 for utilization category AC-53b.

– 10 – 60947-4-2 amend. 1  CEI:2001
8.2.1.6.2 Dans le but d’établir les prescriptions des gradateurs à dérivation, les appareils de
connexion qui satisfont à toutes les prescriptions de 8.2.1.6.1 doivent, avant d’être installés,
être identifiés comme des composants ayant subis des essais de type pouvant être utilisés
sans restriction dans un gradateur à dérivation (voir annexe J).
8.2.1.7 Composants dépendants dans les gradateurs à dérivation
Dans le but d’établir les prescriptions pour les gradateurs à dérivation, les appareils de
connexion qui ne satisfont pas à toutes les prescriptions de 8.2.1.6.1 doivent, avant d’être
installés, être identifiés comme des composants dépendants et ne pouvant être utilisés dans
un gradateur à dérivation que sous certaines restrictions (voir annexe J).
8.2.1.8 Utilisation sans restriction des appareils de connexion dans des gradateurs à
dérivation
Lorsqu’à la fois l’appareil mécanique de connexion et l’appareil de connexion à
semiconducteurs sont identifiés comme des appareils ayant subis des essais de type, ils
doivent être mis en œuvre et connectés pour répondre aux valeurs assignées, au service
assigné et à l’utilisation prévue par le constructeur. Il ne doit pas y avoir d’autres restrictions.
8.2.1.9 Utilisation limitée des appareils de connexion dans les gradateurs à dérivation
Lorsque soit l’un soit les deux appareils de connexion sont identifiés comme des composants
dépendants, les appareils de connexion doivent satisfaire à ce qui suit:
a) les appareils de connexion doivent être combinés, avoir leurs caractéristiques assignées
et être essayés comme pour un ensemble;
b) les appareils de connexion doivent être interverrouillés par n’importe quelle combinaison
de moyens électrique, électronique et mécanique, de telle manière que les contacts
mécaniques de connexion ne doivent pas être sollicités pour établir ou couper des
cou
...

Questions, Comments and Discussion