Intrepretation sheet 1 - Explosive atmospheres - Part 15: Equipment protection by type of protection "n"

Feuille d'intreprétation 1 - Atmosphères explosives - Partie 15: Protection du matériel par mode de protection "n"

General Information

Status
Published
Publication Date
14-Sep-2016
Current Stage
DELPUB - Deleted Publication
Completion Date
08-Dec-2017
Ref Project

Relations

Buy Standard

Standard
IEC 60079-15:2010/ISH1:2016 - Intrepretation sheet 1 - Explosive atmospheres - Part 15: Equipment protection by type of protection "n" Released:9/15/2016
English and French language
10 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


INTERNATIONAL ELECTROTECHNICAL COMMISSION

____________
IEC 60079-15
Edition 4.0  2010-01
EXPLOSIVE ATMOSPHERES –
Part 15: Equipment protection by type of protection "n"

INTERPRETATION SHEET 1
This interpretation sheet has been prepared by IEC technical committee 31: Equipment for
explosive atmospheres.
The text of this interpretation sheet is based on the following documents:
ISH Report on voting
31/1259/ISH 31/1273/RVD
Full information on the voting for the approval of this interpretation sheet can be found in the
report on voting indicated in the above table.
___________
IEC 60079-15:2010 Edition 4.0, Explosive atmospheres – Part 15: Equipment protection
by type of protection "n"
Question:
Do the requirements given in 8.3 prohibit the use of a terminal box opened to the interior of a
motor rated 1 kV or greater, provided the interior of the machine has an ingress protection of
IP54 or greater?
IEC 60079-15:2010 Edition 4.0
8.3 Terminal boxes
Terminal boxes attached to machines operating at voltages up to 1 kV, may be opened to the
interior of the machine, only when the IP rating of the machine is IP44 or higher. The external
IP protection of the box shall be not less than IP54, as determined in accordance with
IEC 60079-0.
ICS 29.260.20
IEC 60079-15:2010-01/ISH1:2016-09(en-fr)

– 2 – IEC 60079-15:2010/ISH1:2016  IEC 2016

Answer:
No. As long as the interior of the machine has an ingress protection of IP54 or greater,

determined in accordance with IEC 60079-0, there is no limitation to less than 1 kV. If the

interior of the machine has an ingress rating of IP44 or lower, the use of a terminal box open

to the interior of a motor rated 1 kV or greater is not permitted.

NOTE Many manufacturers opt to declare IP44 for the machine for certification purposes, whilst claiming a rating

of IP54 or higher, by assessment, for contractual purposes in order to avoid the difficult testing required for

certification of the IP of larger machines. As such, this additional IP rating need only comply with IEC 60529 or
IEC 60034-5 as applicable, and not with any of the testing detailed in IEC 60079-0.