TC 31 - Equipment for explosive atmospheres
- Abstract
To prepare and maintain international standards relating to equipment for use where there is a hazard due to the possible presence of explosive atmospheres of gases, vapours, mists or combustible dusts
- Slovenian
Equipements pour atmosphères explosives
Préparer et maintenir des normes internationales concernant le matériel électrique utilisable dans les atmosphères explosibles sous forme de gaz, vapeurs, brouillards ou poussières combustibles.
IEC 60079-1:2026 contains specific requirements for the construction and testing of Ex Equipment and Ex Components with the Type of Protection flameproof enclosure "d", intended for use in explosive gas atmospheres.
This document supplements and modifies the general requirements of IEC 60079‑0. Where a requirement of this document conflicts with a requirement of IEC 60079‑0, the requirement of this document takes precedence.
This eighth edition constitutes a technical revision. Refer to the Foreword of the document for a complete listing of the technical changes between edition 8.0 and the previous edition of the document.
Users of this document are advised that interpretation sheets clarifying the interpretation of this document can be published. Interpretation sheets are available from the IEC webstore and can be found in the "history" tab of the page for each document.
- Standard119 pagesEnglish languagesale 15% off
- Standard127 pagesFrench languagesale 15% off
This document is published as a dual logo standard and is applicable for the explosion protection requirements for the construction, testing and marking for Group I Ex Equipment that can be an individual item, or be an assembly of multiple items of Ex Equipment and Ex Components forming mining machinery. The standard atmospheric conditions (relating to the explosion characteristics of the atmosphere) under which it can be assumed that Ex Equipment can be operated are: - temperature −20 °C to +60 °C; - pressure 80 kPa (0,8 bar) to 110 kPa (1,1 bar); and - air with normal oxygen content, typically a volume fraction of 21 %. This part of ISO/IEC 80079 applies for Ex Equipment and Ex Components with Explosion Protection Levels (EPLs) Ma and Mb. This document supplements and modifies the general requirements of IEC 60079‑0. Where a requirement of this document conflicts with a requirement of IEC 60079-0, the requirement of this document takes precedence. This document can be used for guidance on underground applications where firedamp or coal dust can be present, but which are not Group I mines, for example tunnels. This second edition cancels and replaces the first edition, published in 2016. This edition constitutes a technical revision. Refer to the Foreword of the document for a complete listing of the technical changes between edition 2.0 and the previous edition of the document.
- Standard40 pagesEnglish languagesale 15% off
- Standard3 pagesEnglish languagesale 15% off
IEC 60079-10-2 is concerned with the identification and classification of areas where explosive dust atmospheres and combustible dust layers are present in order to permit the proper assessment of ignition sources in such areas. In this document, explosive dust atmospheres and combustible dust layers are treated separately. In Clause 4, area classification for explosive dust clouds is described, with dust layers acting as one of the possible sources of release. In Clause 7, other general considerations for dust layers are described. The examples in this document are based on a system of effective housekeeping being implemented in the plant to prevent dust layers from accumulating. Where effective housekeeping is not present, the area classification includes the possible formation of explosive dust clouds from dust layers. The principles of this document can also be followed when combustible fibres or flyings might cause a hazard.
Atmospheric conditions include variations in pressure and temperature above and below reference levels of 101,3 kPa (1 013 mbar) and 20 °C (293 K), provided that the variations have a negligible effect on the explosive properties of the combustible material. For air with normal oxygen content, typically a volume fraction of 21 % is assumed.
It does not apply to:
a) underground mining areas;
b) dusts of explosives that do not require atmospheric oxygen for combustion such as pyrophoric substances, propellants, pyrotechnics, munitions, peroxides, oxidizers, water‑reactive elements or compounds, or other similar materials;
c) catastrophic failures or rare malfunctions which are outside the conditions dealt with in this document;
d) rooms used for medical purposes;
e) domestic premises;
f) where a hazard is due to the presence of flammable gas or vapour, but the principles can be used in the assessment of a hybrid mixture (see also IEC 60079-10-1).
This document does not consider the effects of consequential damage following a fire or an explosion. Please refer to the foreword of the document for a detailed listing of the significant technical changes from the previous edition.
- Standard74 pagesEnglish languagesale 15% off
- Standard75 pagesEnglish and French languagesale 15% off
- Standard75 pagesEnglish and French languagesale 15% off
IEC 60079-0:2026 is available as IEC 60079-0:2026 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.
IEC 60079-0:2026 specifies the general requirements for construction, testing and marking of Ex Equipment and Ex Components intended for use in or associated with explosive atmospheres.
The standard atmospheric conditions (relating to the explosion characteristics of the atmosphere) for Ex Equipment are:
- temperature −20 °C to +60 °C;
- pressure 80 kPa (0,8 bar) to 110 kPa (1,1 bar); and
- air with normal oxygen content, typically a volume fraction of 21 %.
This IEC 60079-0:2026 and other documents supplementing this document specify additional test requirements for Ex Equipment operating outside the standard temperature range, but in some cases, further additional consideration and additional testing is required for Ex Equipment operating outside the standard atmospheric pressure range and standard oxygen content. Such additional testing is particularly relevant with respect to Types of Protection that depend on quenching of a flame such as 'flameproof enclosures "d"' (IEC 60079-1) or limitation of energy, 'intrinsic safety "i"' (IEC 60079-11). This eighth edition cancels and replaces the seventh edition, published in 2017. This edition constitutes a technical revision. Refer to the Foreword of the document for a complete listing of the technical changes between edition 8.0 and the previous edition of the document.
- Standard159 pagesEnglish languagesale 15% off
- Standard331 pagesEnglish languagesale 15% off
- Standard331 pagesEnglish and French languagesale 15% off
- Standard1 pageEnglish and French languagesale 15% off
IEC 60079-29-0:2025 specifies general requirements, test methods and acceptance criteria that apply to flammable, oxygen and toxic gas detection equipment intended to detect gases and vapours and to provide an indication, alarm or other output function for personnel or property protection in industrial and commercial applications.
This document applies to the following gas detection equipment:
– Gas detection equipment Type "FL" intended for the detection of flammable gases:
• Type FL-Group I, in mines susceptible to firedamp;
• Type FL-Group II, in locations other than mines susceptible to firedamp; and
• Type FL-OP, open path gas detection equipment for flammable gases.
– Gas detection equipment Type "O2" intended for the detection of Oxygen:
• Type O2-DE, detection of oxygen deficiency or oxygen enrichment; and
• Type O2-IN, inertisation as measuring function for explosion protection.
– Gas detection equipment Type "TX" intended for the detection of toxic gases:
• Type TX-SM, detection in areas for safety monitoring applications and typically using alarm signalling;
• Type TX-HM, occupational exposure measurement in the region of occupational exposure limit values; and
• Type TX-OP, open path gas detection equipment for toxic gases.
This document is not applicable to equipment:
– used for medical applications;
– used only in laboratories for analysis or measurement;
– used only for process monitoring or control purposes (such as a gas analyser);
– used in the domestic environment;
– used in environmental air pollution monitoring;
– used for flue gas analysis;
– used for sampling systems external to the gas detection equipment;
– with samplers and concentrators such as sorbents or paper tape having an irreversible indication;
– consisting of a passive optical receiver without a dedicated optical source;
– equipment within the scope of IEC 60335-2-40 and IEC 60335-2-89.
This first edition of IEC 60079-29-0 cancels and replaces the second edition of 60079-29-1 published in 2016 and its Amendment 1:2020, and the first edition of IEC 60079-29-4 published in 2009. In addition, IEC 60079-29-0 Type TX-SM cancels and replaces Type SM of the first edition of IEC 62990-1.
- Standard88 pagesEnglish languagesale 15% off
- Standard93 pagesFrench languagesale 15% off
- Standard181 pagesEnglish and French languagesale 15% off
IEC 60079-28:2025 specifies additional requirements for Ex Equipment, Ex associated equipment or Ex Components containing optical systems emitting optical radiation, which is exposed to explosive atmospheres. These additional requirements are applicable for all equipment groups and all Equipment Protection Levels (EPL).
This document contains requirements for optical radiation in the wavelength range from 380 nm to 10 µm. It covers the following ignition mechanisms:
• Optical radiation is absorbed by surfaces or particles, causing them to heat up, and under certain circumstances this might allow them to attain a temperature which will ignite a surrounding explosive atmosphere.
• In rare special cases, direct laser induced breakdown of the gas at the focus of a strong beam, producing plasma and a shock wave both eventually acting as ignition source. These processes can be supported by a solid material close to the breakdown point.
• Annex A provides guidance when considering ignition mechanisms that influence the hazard of optics in explosive atmospheres.
This document applies to
a) laser equipment; and
b) optical fibre equipment; and
c) any optical system that converts light into convergent beams with focal points within the hazardous area only.
This document does not apply to:
d) laser equipment for EPL Mb, Gb, Gc, Db or Dc applications which complies with Class 1 limits in accordance with IEC 60825-1; or
e) Single or multiple optical fibre cables not part of optical fibre equipment if the cables:
1) comply with the relevant industrial standards for optical fibre cables, along with additional protective means, for example robust cabling, conduit or raceway (for EPL Gb, Db, Mb, Gc or Dc); or
2) comply with the relevant industrial standards for optical fibre cables (for EPL Gc or Dc); or
f) Optical radiation sources as defined in i) to iii) above where the optical radiation is fully contained in an enclosure complying with one of the following Types of Protection suitable for the EPL, or the minimum ingress protection rating specified:
1) flameproof "d" enclosures (IEC 60079-1); or
2) pressurized "p" enclosures (IEC 60079-2); or
3) restricted breathing "nR" enclosure (IEC 60079-15); or
4) dust protection "t" enclosures" (IEC 60079-31); or
5) an enclosure that provides a minimum ingress protection of IP 6X and where no internal absorbers are to be expected and complying with "Tests of enclosures" in IEC 60079-0.
This document does not cover ignition by ultraviolet radiation and by absorption of the radiation in the explosive mixture itself. Explosive absorbers or absorbers that contain their own oxidizer as well as catalytic absorbers are also outside the scope of this document.
This document supplements and modifies the general requirements of IEC 60079-0. Where a requirement of this document conflicts with a requirement of IEC 60079-0, the requirement of this document takes precedence.
This third edition cancels and replaces the second edition published in 2015. This edition constitutes a technical revision
- Standard30 pagesEnglish languagesale 15% off
- Standard32 pagesFrench languagesale 15% off
- Standard62 pagesEnglish and French languagesale 15% off
IEC 60079-18:2025 gives the specific requirements for the construction, testing and marking of electrical Ex Equipment, parts of electrical Ex Equipment and Ex Components with the Type of Protection encapsulation "m" (hereinafter referred to as "m" Equipment) intended for use in explosive gas atmospheres or explosive dust atmospheres. For Levels of Protection "mb" and "mc", this document applies where the rated voltage does not exceed 11 kV ACRMS or DC. For Level of Protection "ma", this document applies where the rated voltage does not exceed 1 kV ACRMS or DC. This document does not take account of any hazard due to an emission of flammable or toxic gas from the dust. This document supplements and modifies the general requirements of IEC 60079-0. Where a requirement of this document conflicts with a requirement of IEC 60079-0, the requirement of this document takes precedence. This fifth edition cancels and replaces the fourth edition published in 2014 and Amendment 1:2017. This edition constitutes a technical revision. This International Standard is to be used in conjunction with IEC 60079-0, Explosive atmospheres - Part 0: Equipment - General requirements. Users of this document are advised that interpretation sheets clarifying the interpretation of this document can be published. Interpretation sheets are available from the IEC webstore and can be found in the "history" tab of the page for each document. Please see the foreword to this document for the list of significant technical changes with respect to the previous edition.
- Standard41 pagesEnglish languagee-Library read for
IEC 60079-45:2025 is intended to enhance the safety of personnel by providing minimum requirements for electrical ignition systems for spark-ignited reciprocating internal combustion engines, parts of which provide Equipment Protection Level (EPL) Gc. This document provides minimum construction and test requirements, in addition to manufacturer installation and maintenance recommendations, for the safe operation of ignition systems and components for spark-ignited reciprocating internal combustion engines providing EPL Gc for equipment Group IIB+H2, IIB or IIA. These requirements apply to systems rated for normal operation with secondary voltages less than or equal to 60 kV. This document applies only to the ignition systems or the individual ignition system components used on reciprocating internal combustion engines that are stationary when in operation and mobile machinery where the internal combustion engine can be potential source of ignition. Applications addressed by the scope of this document include but are not limited to gas compressors, electric power generators, forklift trucks, and pumps. This document does not apply to: a) Engine ignition systems that utilize a breaker point or magneto type ignition systems as these would not be suitable for use in a hazardous area. b) Road vehicles. c) Low voltage parts and electrical installation that are not included in the ignition system, such as various sensors and thermocouples, throttle actuator(s), fuel control valve(s), human machine interface (HMI), respective harness and wiring and all the other items that might belong to the integrated control system besides the ignition system. This document supplements and modifies the general requirements of IEC 60079-0 and the requirements of ISO/IEC 80079-41. Where a requirement of this document conflicts with IEC 60079 0 or ISO/IEC 80079-41, the requirement of this document takes precedence.
- Standard47 pagesEnglish languagee-Library read for
- Standard7 pagesEnglish languagesale 15% off
- Standard8 pagesFrench languagesale 15% off
- Standard15 pagesEnglish and French languagesale 15% off
IEC 60079-25:2020 contains the specific requirements for design, construction and assessment of intrinsically safe systems, Type of Protection “i”, intended for use, as a whole or in part, in locations in which the use of Group I, II or III Ex Equipment is required. This document supplements and modifies the general requirements of IEC 60079-0 and the intrinsic safety standard IEC 60079-11. Where a requirement of this standard conflicts with a requirement of IEC 60079-0 or IEC 60079-11, the requirement of this standard takes precedence. The installation requirements of Group II or Group III systems designed in accordance with this standard are specified in IEC 60079-14. This third edition cancels and replaces the second edition published in 2010 and constitutes a technical revision. The contents of the corrigendum 1 of October 2020 and corrigendum 2 of November 2022 have been included in this copy.
- Standard123 pagesEnglish languagesale 15% off
- Standard117 pagesEnglish and French languagesale 15% off
IEC/IEEE 60079-30-2:2025 is available as IEC/IEEE 60079-30-2:2025 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC/IEEE 60079-30-2:2025 provides guidance for the application of electrical resistance trace heating systems in areas where explosive atmospheres can be present, with the exclusion of those classified as requiring Equipment Protection Level (EPL) Ga or Da (traditional relationship to Zone 0 and Zone 20 respectively). This document also provides guidance for explosive atmospheres incorporating the Division method of area classification that can be applied by some users of this document.
This document provides recommendations for the design, installation, maintenance and repair of trace heating systems including associated control and monitoring equipment. It does not cover devices that operate by induction heating, skin effect heating or direct pipeline heating, nor those intended for stress relieving.
This second edition of IEC/IEEE 60079-30-2 cancels and replaces the first edition of IEC/IEEE 60079-30-2 published in 2015.
This edition includes the following significant technical changes with respect to the previous edition:
a) a general review and updating of the first edition;
b) the addition of Annex I – Other applications of trace heating in explosive atmospheres.
The significance of changes between IEC/IEEE 60079-30-2, Edition 1.0 (2015) and IEC/IEEE 60079-30-2, Edition 2.0 (this document) can be found on the foreword of this document.
- Standard73 pagesEnglish languagesale 15% off
- Standard150 pagesEnglish languagesale 15% off
IEC/IEEE 60079-30-1:2025 is available as IEC/IEEE 60079-30-1:2025 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC/IEEE 60079-30-1:2025 specifies general and testing requirements for electrical resistance trace heaters for application in explosive atmospheres with the exclusion of those for Equipment Protection Levels (EPL) Ga, Da, Ma and Mb equipment. This document covers trace heaters that comprise either factory or field (worksite) assembled units, and which can be series trace heaters, parallel trace heaters, trace heater pads, or trace heater panels that have been assembled and/or terminated in accordance with the manufacturer's instructions.
This document also includes requirements for termination assemblies and control methods used with trace heating systems. The explosive atmospheres referred to in this document are those defined in IEC 60079-10-1 and IEC 60079-10-2.
Annex F and Annex G outline the application of this document for those users applying the Division method of area classification
This second edition of IEC/IEEE 60079-30-1 cancels and replaces the first edition of IEC/IEEE 60079-30-1 published in 2015. This edition constitutes a technical revision.
The significant technical changes with respect to the previous edition can be found n the foreword of this publication.
- Standard77 pagesEnglish languagesale 15% off
- Standard167 pagesEnglish languagesale 15% off
CORRECTED VERSION 2026-05
- Standard2 pagesEnglish languagesale 15% off
CORRECTED VERSION 2026-05
- Standard2 pagesEnglish languagesale 15% off
IEC 60079-45:2025 is intended to enhance the safety of personnel by providing minimum requirements for electrical ignition systems for spark-ignited reciprocating internal combustion engines, parts of which provide Equipment Protection Level (EPL) Gc.
This document provides minimum construction and test requirements, in addition to manufacturer installation and maintenance recommendations, for the safe operation of ignition systems and components for spark-ignited reciprocating internal combustion engines providing EPL Gc for equipment Group IIB+H2, IIB or IIA. These requirements apply to systems rated for normal operation with secondary voltages less than or equal to 60 kV.
This document applies only to the ignition systems or the individual ignition system components used on reciprocating internal combustion engines that are stationary when in operation and mobile machinery where the internal combustion engine can be potential source of ignition. Applications addressed by the scope of this document include but are not limited to gas compressors, electric power generators, forklift trucks, and pumps.
This document does not apply to:
a) Engine ignition systems that utilize a breaker point or magneto type ignition systems as these would not be suitable for use in a hazardous area.
b) Road vehicles.
c) Low voltage parts and electrical installation that are not included in the ignition system, such as various sensors and thermocouples, throttle actuator(s), fuel control valve(s), human machine interface (HMI), respective harness and wiring and all the other items that might belong to the integrated control system besides the ignition system.
This document supplements and modifies the general requirements of IEC 60079-0 and the requirements of ISO/IEC 80079-41. Where a requirement of this document conflicts with IEC 60079 0 or ISO/IEC 80079-41, the requirement of this document takes precedence.
- Standard43 pagesEnglish languagesale 15% off
- Standard46 pagesFrench languagesale 15% off
- Standard89 pagesEnglish and French languagesale 15% off
IEC 60079-19:2025 applies to service facilities and covers only those factors related to overhaul, repair or reclamation of Ex Equipment specifically designed for hazardous areas, where the hazard is caused by explosive atmospheres. Ex Equipment can be overhauled, repaired or reclaimed to mitigate deficiencies identified during operation, inspection and maintenance.
It does not include:
• advice on cable and wiring systems which can require a renewal when the equipment is re-installed;
• Repair or overhaul of Type of Protection “m”;
• Repair or overhaul of Ex Components;
• Requirements for manufacturers who overhaul and repair equipment which they have manufactured
This fifth edition cancels and replaces the fourth edition published in 2019. This edition constitutes a technical revision.
Users of this document are advised that interpretation sheets clarifying the interpretation of this document can be published. Interpretation sheets are available from the IEC webstore and can be found in the “history” tab of the page for each document.
The significance of changes between IEC 60079-19, Edition 5 (2025) and IEC 60079-19, Edition 4 (2019) are as listed in the foreword of this standard.
- Standard87 pagesEnglish languagesale 15% off
- Standard94 pagesFrench languagesale 15% off
- Standard181 pagesEnglish and French languagesale 15% off
IEC 60079-18:2025 gives the specific requirements for the construction, testing and marking of electrical Ex Equipment, parts of electrical Ex Equipment and Ex Components with the Type of Protection encapsulation "m" (hereinafter referred to as "m" Equipment) intended for use in explosive gas atmospheres or explosive dust atmospheres. For Levels of Protection "mb" and "mc", this document applies where the rated voltage does not exceed 11 kV ACRMS or DC. For Level of Protection "ma", this document applies where the rated voltage does not exceed 1 kV ACRMS or DC. This document does not take account of any hazard due to an emission of flammable or toxic gas from the dust. This document supplements and modifies the general requirements of IEC 60079-0. Where a requirement of this document conflicts with a requirement of IEC 60079-0, the requirement of this document takes precedence. This fifth edition cancels and replaces the fourth edition published in 2014 and Amendment 1:2017. This edition constitutes a technical revision. This International Standard is to be used in conjunction with IEC 60079-0, Explosive atmospheres - Part 0: Equipment - General requirements. Users of this document are advised that interpretation sheets clarifying the interpretation of this document can be published. Interpretation sheets are available from the IEC webstore and can be found in the "history" tab of the page for each document. Please see the foreword to this document for the list of significant technical changes with respect to the previous edition.
- Standard113 pagesEnglish languagesale 15% off
- Standard74 pagesEnglish and French languagesale 15% off
No scope available
- Amendment5 pagesEnglish languagee-Library read for
This part of IEC 60079 specifies the construction and testing of intrinsically safe apparatus intended for use in an explosive atmosphere, and for associated apparatus which is intended for connection to intrinsically safe circuits which enter such atmospheres. This Type of Protection is applicable to electrical equipment in which the electrical circuits themselves are incapable of causing ignition of a surrounding explosive atmosphere. This includes electrical equipment which contains circuits that are intrinsically safe only under certain conditions, for example under battery supply with mains supply removed. This standard is also applicable to electrical equipment or parts of electrical equipment located outside the explosive atmosphere or protected by another Type of Protection listed in IEC 60079-0, where the intrinsic safety of the electrical circuits in the explosive atmosphere may depend upon the design and construction of such electrical equipment or parts of such electrical equipment. The electrical circuits exposed to the explosive atmosphere are assessed for use in such an atmosphere by applying this standard. This standard applies to sensors connected to intrinsically safe circuits but does not apply to the protection of catalytic elements for Group IIC or Group IIB + H2. The requirements for intrinsically safe systems are provided in IEC 60079-25. This standard supplements and modifies the general requirements of IEC 60079-0, except as indicated in Table 1. Where a requirement of this standard conflicts with a requirement of IEC 60079-0, the requirement of this standard takes precedence. Unless otherwise stated, the requirements in this standard are applicable to both intrinsically safe apparatus and associated apparatus, and the generic term "apparatus" is used throughout the standard. As this standard applies only to electrical equipment, the term "equipment" used in the standard always means “electrical equipment”. This standard applies to apparatus for use under the atmospheric conditions of IEC 60079-0 with additional requirements for for use at lower atmospheric pressures in the range from 60 kPa (0,6 bar), up to 110 kPa (1,1 bar). [...]
- Standard222 pagesEnglish languagee-Library read for
IEC 60079:2024 contains the specific requirements for the design of electrical systems, selection, installation and the required initial inspection of electrical installations of Ex Equipment in, or associated with, explosive atmospheres including requirements for documentation and personnel competency. These requirements are in addition to the requirements for installations in non-hazardous areas. This document applies to all electrical Ex Equipment including fixed, transportable, portable and personal, and installations, permanent or temporary. This document does not apply to: • electrical installations in mines susceptible to firedamp; • inherently explosive situations and dust from explosives or pyrophoric substances (for example explosives manufacturing and processing); • rooms used for medical purposes; • electrical installations in areas where the hazard is due to flammable mist; and • installation of non-electrical Ex Equipment (unless being part of an equipment assembly according IEC TS 60079-46). No account is taken in this document of the toxic hazards that are associated with flammable gases, liquids and dusts in concentrations that are usually very much less than the lower flammable limit. In locations where personnel could be exposed to potentially toxic concentrations of flammable material, appropriate precautions are necessary. Such precautions are outside the scope of this document. This sixth edition cancels and replaces the fifth edition published in 2013. This edition constitutes a technical revision. Edition 6 is a major restructure and introduces a number of technical changes from the previous edition (2013), see Table 1 of the foreword for detailed information.
- Standard149 pagesEnglish languagee-Library read for
IEC 60079:2024 contains the specific requirements for the design of electrical systems, selection, installation and the required initial inspection of electrical installations of Ex Equipment in, or associated with, explosive atmospheres including requirements for documentation and personnel competency.
These requirements are in addition to the requirements for installations in non-hazardous areas.
This document applies to all electrical Ex Equipment including fixed, transportable, portable and personal, and installations, permanent or temporary.
This document does not apply to:
• electrical installations in mines susceptible to firedamp;
• inherently explosive situations and dust from explosives or pyrophoric substances (for example explosives manufacturing and processing);
• rooms used for medical purposes;
• electrical installations in areas where the hazard is due to flammable mist; and
• installation of non-electrical Ex Equipment (unless being part of an equipment assembly according IEC TS 60079-46).
No account is taken in this document of the toxic hazards that are associated with flammable gases, liquids and dusts in concentrations that are usually very much less than the lower flammable limit. In locations where personnel could be exposed to potentially toxic concentrations of flammable material, appropriate precautions are necessary. Such precautions are outside the scope of this document.
This sixth edition cancels and replaces the fifth edition published in 2013. This edition constitutes a technical revision. Edition 6 is a major restructure and introduces a number of technical changes from the previous edition (2013), see Table 1 of the foreword for detailed information.
- Standard300 pagesEnglish and French languagesale 15% off
CORRECTED VERSION 2026-05
- Standard2 pagesEnglish languagesale 15% off
- Standard2 pagesEnglish languagesale 15% off
CORRECTED VERSION 2026-05
- Standard2 pagesEnglish languagesale 15% off
CORRECTED VERSION 2026-05
- Standard2 pagesEnglish languagesale 15% off
ISO/IEC 80079-49:2024 specifies the requirements for flame arresters that prevent flame transmission when explosive gas-air or vapour-air mixtures are present. It establishes uniform principles for the classification, basic construction and information for use, including the marking of flame arresters, and specifies test methods to verify the safety requirements and determine safe limits of use.
This document is applicable to pressures ranging from 80 kPa to 160 kPa and temperatures ranging from -20 °C to +200 °C.
This document does not apply to the following:
- external safety-related measurement and control equipment that might be required to keep the operational conditions within the established safe limits;
- flame arresters used for explosive mixtures of vapours and gases, which tend to self-decompose (for example, acetylene) or which are chemically unstable;
- flame arresters used for carbon disulfide, due to its special properties;
- flame arresters whose intended use is for mixtures other than gas-air or vapour-air mixtures (for example, higher oxygen-nitrogen ratio, chlorine as oxidant);
- flame arrester test procedures for reciprocating internal combustion engines;
- fast acting valves, extinguishing systems and other explosion isolating systems;
- Flame arresters used in gas detectors (those being covered for example, by IEC 60079‑29‑1 and IEC 62990‑1).
This edition cancels and replaces ISO 16852:2016, which has been technically revised. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to ISO 16852:2016:
a) adaptation of the relevant IEC TC 31 requirements on standards;
b) modification of the upper limit of the temperature range from 150 °C to 200 °C under the condition that T0 shall be not larger than 80 % of the auto ignition temperature of the gas-air-mixture;
c) change of the term "explosion group" to "equipment group" due to editorial requirements in IEC/TC 31;
d) clarification of the conditions and requirements for flame arresters whose intended operating conditions are outside the atmospheric conditions in 7.3.4 and 7.3.5;
e) clarification of the requirements on the information for use in Clause 12 f) concerning the burn time;
f) addition of a permission to the construction requirements both in 7.1 and 14.1 to substitute visual inspection by performing a flow test;
g) addition of a flow chart for the evaluation of test results as Annex D
- Standard69 pagesEnglish languagesale 15% off
- Standard139 pagesEnglish and French languagesale 15% off
This part of the IEC 60079 series applies to users and covers only those factors directly related to the inspection and maintenance of electrical installations specifically designed for hazardous areas, where the hazard may be caused by explosive gas or explosive dust atmospheres. It does not include: - other fundamental installation and inspection requirements for electrical installations; - the verification of electrical equipment; - protection or ventilation of rooms; - gas detection systems; - the repair and overhaul of explosion protected equipment (see IEC 60079-19). While this standard does not include inspection of safety devices such as used in ventilated rooms (see 60079-13), this standard does include the requirements for inspection and maintenance of individual items of equipment that will be part of such systems, for example motors or sensors. This standard supplements the requirements for inspection and testing in non-hazardous areas in IEC 60364-6. NOTE 1 Standards applied at the date of installation might not have been IEC standards. This standard is intended to be applied where there can be a risk due to the presence of explosive gas or dust mixtures with air or combustible dust layers under normal atmospheric conditions. It does not apply to: - underground mining areas, - dusts of explosives, - pyrophoric substances.
- Standard49 pagesEnglish languagee-Library read for
IEC 60079-17:2023 applies to users and covers only those factors directly related to the inspection and maintenance of electrical installations specifically designed for hazardous areas, where the hazard is caused by explosive atmospheres.
It does not include:
- other fundamental installation and inspection requirements for electrical installations;
- the verification of electrical equipment;
- protection or ventilation of rooms;
- gas detection systems;
- the repair, overhaul and reclamation of explosion protected equipment (see IEC 60079-19).
While this document does not include inspection of safety devices such as used in ventilated rooms (see IEC 60079-13), it does include the requirements for inspection and maintenance of individual items of equipment that will be part of such systems, for example motors or sensors. This document supplements the requirements for inspection and testing in non-hazardous areas in IEC 60364-6. This document is intended to be applied where there is a risk due to the potential presence of explosive gas or dust mixtures with air or combustible dust layers under normal atmospheric conditions. It does not apply to:
- underground mining areas,
- dusts of explosives,
- pyrophoric substances.
This sixth edition cancels and replaces the fifth edition published in 2013. This edition constitutes a technical revision.
- Standard144 pagesEnglish languagesale 15% off
- Standard95 pagesEnglish and French languagesale 15% off
IEC TS 60079-44:2023, which is a Technical Specification, is to provide guidance to establish recommended minimum criteria to determine roles, establish expectations of the necessary skills and evidence of competence to assess and manage the competence of personnel conducting work in or associated with hazardous areas. The purpose of this document is to provide guidance to establish:
• recommended minimum criteria to determine roles,
• expectations of the necessary skills, and
• evidence of competence
in order to assess and manage the competence of personnel who are conducting work in or associated with hazardous areas.
This document provides examples and recommendations of minimum levels of competence for typical roles associated with hazardous areas by addressing the knowledge, skills, or abilities that is expected of personnel. Additionally, examples of the evidence of competence expected for each role are provided.
The aim of tThis document is to assist in defining, assessing, and managing unique requirements for the competence of individuals working in or associated with installations where an explosive atmosphere could be present. Such a programme could be specific to a facility or used in conjunction with other regulatory requirements where they exist. The competencies for conducting work in a hazardous area are in addition to any competencies which may apply for the general type of work being undertaken (for example, professional credentials, electrical, non-electrical, operations, design).
This document applies to both electrical and non-electrical applications.
This document identifies the minimum level of knowledge and skills required to work in hazardous areas and the specific competence required for work associated with equipment for explosive atmospheres (commonly termed ‘Ex Equipment’) and the standards to which competence is to be assessed and attributed.
The purpose of this document is to provide guidance to establish:
• recommended minimum criteria to determine roles,
• expectations of the necessary skills, and
• evidence of competence
The principal application of this specification document is for personnel dealing with explosion-protected and associated equipment for use in explosive atmospheres, including the following work functions:
• Classification of areas;
• Producing, processing or servicing functions in a hazardous area and not directly involved in installing, maintaining or repairing explosion-protected equipment and systems;
• Designing, commissioning and maintaining explosion-protection strategies and equipment;
• Selecting, installing, testing and maintaining explosion-protected equipment and systems in hazardous areas;
• Inspecting hazardous area equipment, systems and installations;
• Overhauling, repairing and modifying explosion-protected equipment;
• Management of the Ex aspects of the facility.
- Technical specification29 pagesEnglish languagesale 15% off
IEC 60079-48:2023, which is a Technical Specification, provides guidance for an owner or operator for the use of portable or personal electronic equipment to be used in hazardous areas requiring Equipment Protection Level (EPL) Gb, Gc, Db, or Dc that are not otherwise commercially available with a certificate.
This document does not apply to:
• equipment that is electrically connected to fixed equipment or fixed wiring during use in the hazardous area, for example a lead light connected to the premises wiring system by a plug and socket,
• portable or personal equipment with a certificate for use in a hazardous area,
• transportable equipment,
• portable or personal equipment used in Group I applications,
• battery powered tools, such as drills and saws,
• portable or personal equipment used in areas requiring EPL Ga or Da equipment, or,
• medical devices.
This document does not address other considerations involving the use of portable or personal electronic equipment for other aspects of safety, for example, creation of a distraction from important work tasks, radio frequency interference with measurement and control equipment, or medical issues.
This document supplements the guidance in IEC 60079-14 regarding the use of personal or portable equipment without a certificate for use in hazardous areas.
- Technical specification15 pagesEnglish languagesale 15% off
- Standard3 pagesEnglish and French languagesale 15% off
CORRECTED VERSION 2026-05
- Standard3 pagesEnglish languagesale 15% off
- Standard7 pagesEnglish and French languagesale 15% off
- Standard2 pagesEnglish languagesale 15% off
- Standard2 pagesEnglish languagesale 15% off
CORRECTED VERSION 2026-07
IEC 60079-11:2023 specifies the construction and testing of intrinsically safe apparatus intended for use in explosive atmospheres, and for associated apparatus which is intended for connection to intrinsically safe circuits which enter such atmospheres.
This Type of Protection is applicable to electrical equipment in which the electrical circuits themselves are incapable of causing ignition of a surrounding explosive atmosphere. This includes electrical equipment which contains circuits that are intrinsically safe only under certain conditions, for example under battery supply with mains supply removed.
This document is also applicable to electrical equipment or parts of electrical equipment located outside the explosive atmosphere or protected by another Type of Protection listed in IEC 60079-0, where the intrinsic safety of the electrical circuits in the explosive atmosphere may depend upon the design and construction of such electrical equipment or parts of such electrical equipment. The electrical circuits exposed to the explosive atmosphere are assessed for use in such atmospheres by applying this document.
The contents of the corrigenda 1 (2023-06) and 2 (2026-05) and the interpretation sheets 1 (2024-05), 2 (2024-05), 3 (2024-08), 4 (2025-09), 5 (2025-09) and 6 (2026-07) have been included in this copy.
- Standard209 pagesEnglish languagesale 15% off
- Standard433 pagesEnglish and French languagesale 15% off
- Standard4 pagesEnglish and French languagesale 15% off
IEC 60079-19:2019 gives instructions, principally of a technical nature, on the repair, overhaul, reclamation and modification of equipment designed for use in explosive atmospheres; it is not applicable to maintenance, other than when repair and overhaul cannot be disassociated from maintenance, neither does it give advice on cable entry systems which may require a renewal when the equipment is re-installed. This fourth edition cancels and replaces the third edition published in 2010 together with Amendment 1:2015. This edition constitutes a technical revision. The significance of the changes between IEC 60079-19, Edition 3 (2010), including Amendment 1 (2015), and IEC 60079-19, Edition 4 (2019) are defined in the foreword and cover minor and editorial changes, extension, and major technical changes.
- Standard85 pagesEnglish languagee-Library read for
IEC 60079-25:2020 contains the specific requirements for design, construction and assessment of intrinsically safe systems, Type of Protection “i”, intended for use, as a whole or in part, in locations in which the use of Group I, II or III Ex Equipment is required. This document supplements and modifies the general requirements of IEC 60079-0 and the intrinsic safety standard IEC 60079-11. Where a requirement of this standard conflicts with a requirement of IEC 60079-0 or IEC 60079-11, the requirement of this standard takes precedence. The installation requirements of Group II or Group III systems designed in accordance with this standard are specified in IEC 60079-14. This third edition cancels and replaces the second edition published in 2010 and constitutes a technical revision.
- Standard64 pagesEnglish languagee-Library read for
IEC 60079-31:2022 is available as IEC 60079-31:2022 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 60079-31:2022 is applicable to equipment protected by enclosure and surface temperature limitation for use in explosive dust atmospheres. It specifies requirements for design, construction and testing of Ex Equipment and Ex Components. This document supplements and modifies the general requirements of IEC 60079-0. Where a requirement of this document conflicts with a requirement of IEC 60079-0, the requirement of this document takes precedence. This document does not apply to dusts of explosives, which do not require atmospheric oxygen for combustion, or to pyrophoric substances. This document does not apply to Ex Equipment or Ex Components intended for use in underground parts of mines as well as those parts of surface installations of such mines endangered by firedamp and/or combustible dust. This document does not take account of any risk due to an emission of flammable or toxic gas from the dust. This third edition cancels and replaces the second edition published in 2013. This edition constitutes a technical revision. Main significant changes from the previous edition are: 1) Document has been restructured from edition 2 2) Fault current rating of interrupting contacts in clauses 4.3.1 and 4.4.1, major change type C1 3) Cells and batteries in clauses 4.3.5.1 and 4.4.5.1, major change type C2 4) Overload or malfunction condition for the determination of temperature class for "tb" converter fed rotating electric machines, major change type C3 5) Additional requirements for entry devices with dust ignition protection by enclosure "t", major change type C4 Information about the background of ‘Major Technical Changes’ C1 – Ex Equipment having Level of Protection "ta" shall be rated for connection to a circuit with a prospective short circuit current of not greater than 1.5 kA. For Ex Equipment having Level of Protection "tb" or "tc" which is intended for mains connection and intended to interrupt fault current above 10kA, the equipment shall have a rated maximum short circuit withstand current, be tested according to 6.1.1.1, and be marked according to Clause 7. C2 – For Ex Equipment having Level of Protection "ta" which contains a cell or battery, only a sealed cell or battery shall be used. For Ex Equipment having Level of Protection "tb" and "tc" where there are sparking contacts or hot surfaces, and which contains a cell or battery, only a sealed cell or battery shall be used. C3 – Table 2 now includes malfunction conditions for temperature class determination of Level of Protection "tb" converter-fed electric machines. C4 – Annex A added for entry devices with Type of Protection "t" including cable transit devices.
- Standard25 pagesEnglish languagee-Library read for
- Standard3 pagesEnglish languagesale 15% off
- Standard5 pagesEnglish and French languagesale 15% off
IEC 60079-5:2015 contains specific requirements for the construction, testing and marking of electrical equipment, parts of electrical equipment and Ex components in the type of protection powder filling "q", intended for use in explosive gas atmospheres. This standard supplements and modifies the general requirements of IEC 60079-0. Where a requirement of this standard conflicts with a requirement of IEC 60079-0, the requirement of this standard takes precedence. This standard applies to electrical equipment, parts of electrical equipment and Ex components with:
- a rated supply current less than or equal to 16 A;
- a rated supply voltage less than or equal to 1 000 V;
- a rated power consumption less than or equal to 1 000 W. This fourth edition cancels and replaces the third edition, published in 2007, and constitutes a technical revision. Refer to the Foreword of the document for a complete listing of the technical changes between edition 4.0 and previous edition of the document. Keywords: electrical equipment and Ex components in the type of protection powder filling "q"
- Standard42 pagesEnglish languagesale 15% off
- Standard68 pagesEnglish languagesale 15% off
- Standard41 pagesEnglish and French languagesale 15% off
- Standard83 pagesEnglish and French languagesale 15% off
NEW!IEC 60079-15:2017 is available as IEC 60079-15:2017 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 60079-15:2017 specifies requirements for the construction, testing and marking for Group II electrical equipment with type of protection “n” which includes; sealed devices “nC”, hermetically sealed devices “nC”, non-incendive components “nC” and restricted breathing enclosures “nR” intended for use in explosive gas atmospheres. This part of IEC 60079 applies to electrical equipment where the rated input voltage does not exceed 15 kV r.m.s. AC or DC including where the internal working voltages of the Ex product exceeds 15 kV, for example starters for HID luminaires. This part of IEC 60079 supplements and modifies the general requirements of IEC 60079-0, except as indicated in Table 1 (Clause 1). Where a requirement of this part of IEC 60079 conflicts with a requirement of IEC 60079-0, the requirement of this part of IEC 60079 takes precedence. This fifth edition cancels and replaces the fourth edition, published in 2010, and constitutes a technical revision. Refer to the Forward of the document for a complete listing of the technical changes between edition 5.0 and the previous edition of the document. Keywords: Group II electrical equipment with type of protection “n”
- Standard36 pagesEnglish languagee-Library read for
- Standard2 pagesEnglish languagesale 15% off
- Standard2 pagesEnglish languagesale 15% off
IEC 60079-31:2022 is applicable to equipment protected by enclosure and surface temperature limitation for use in explosive dust atmospheres. It specifies requirements for design, construction and testing of Ex Equipment and Ex Components. This document supplements and modifies the general requirements of IEC 60079-0. Where a requirement of this document conflicts with a requirement of IEC 60079-0, the requirement of this document takes precedence. This document does not apply to dusts of explosives, which do not require atmospheric oxygen for combustion, or to pyrophoric substances. This document does not apply to Ex Equipment or Ex Components intended for use in underground parts of mines as well as those parts of surface installations of such mines endangered by firedamp and/or combustible dust. This document does not take account of any risk due to an emission of flammable or toxic gas from the dust. This third edition cancels and replaces the second edition published in 2013. This edition constitutes a technical revision. Main significant changes from the previous edition are:
1) Document has been restructured from edition 2
2) Fault current rating of interrupting contacts in clauses 4.3.1 and 4.4.1, major change type C1
3) Cells and batteries in clauses 4.3.5.1 and 4.4.5.1, major change type C2
4) Overload or malfunction condition for the determination of temperature class for "tb" converter fed rotating electric machines, major change type C3
5) Additional requirements for entry devices with dust ignition protection by enclosure "t", major change type C4
Information about the background of ‘Major Technical Changes’
C1 – Ex Equipment having Level of Protection "ta" shall be rated for connection to a circuit with a prospective short circuit current of not greater than 1.5 kA. For Ex Equipment having Level of Protection "tb" or "tc" which is intended for mains connection and intended to interrupt fault current above 10kA, the equipment shall have a rated maximum short circuit withstand current, be tested according to 6.1.1.1, and be marked according to Clause 7.
C2 – For Ex Equipment having Level of Protection "ta" which contains a cell or battery, only a sealed cell or battery shall be used. For Ex Equipment having Level of Protection "tb" and "tc" where there are sparking contacts or hot surfaces, and which contains a cell or battery, only a sealed cell or battery shall be used.
C3 – Table 2 now includes malfunction conditions for temperature class determination of Level of Protection "tb" converter-fed electric machines.
C4 – Annex A added for entry devices with Type of Protection "t" including cable transit devices.
The contents of the corrigendum of October 2023 have been included in this copy.
- Standard61 pagesEnglish languagesale 15% off
- Standard39 pagesEnglish and French languagesale 15% off
IEC 60079-26:2021 specifies requirements for construction, testing and marking for Ex Equipment that contains parts of the equipment with different Equipment Protection Levels (EPLs) and a separation element. This equipment is mounted across a boundary where different EPLs are required, for example between different gas hazardous areas, dust hazardous areas or gas hazardous areas adjacent to dust hazardous areas. Separation elements are considered for both electrical and non-electrical equipment. If mechanical energy can be transformed into a potential ignition source, additionally an ignition hazard assessment in accordance with ISO 80079-36 is performed and appropriate measures are undertaken. This document also specifies requirements for the combination of two Types of Protection, each with EPL Gb, to achieve EPL Ga. This document supplements and modifies the general requirements of IEC 60079-0. Where a requirement of this document conflicts with a requirement of IEC 60079-0, the requirement of this document takes precedence. This fourth edition cancels and replaces the third edition and constitutes a technical revision. Please see the IEC 60079-26:2020 foreword for a description of the main changes with respect to the previous edition.
- Standard26 pagesEnglish languagee-Library read for
This part of IEC 60079, which is a technical specification, specifies requirements for the construction, marking, and documenting of apparatus, systems and installations for use with the 2-Wire Intrinsically Safe Ethernet concept (2-WISE). The physical layer specification for 2-wire Ethernet 10BASE-T1L is defined in IEEE 802.3cg 2-WISE is the 2-Wire Intrinsically Safe Ethernet concept for advance physical layer (APL), designed to simplify the examination process for components and cable Entity Parameters within APL segments. This is achieved by defining universal Entity Parameter limits for APL ports, according to location and type of hazardous atmosphere, and listing a concise set of rules for the segment setup. The requirements for construction and installation of 2-WISE apparatus and systems are included in IEC 60079-11, IEC 60079-14, and IEC 60079-25, except as modified by this technical specification. Parts of a 2-WISE apparatus may be protected by any Type of Protection listed in IEC 60079-0 appropriate to the EPL for the intended use. In these circumstances, the requirements of this technical specification apply only to intrinsically safe circuits of the apparatus.
- Technical specification17 pagesEnglish languagee-Library read for
NEW!IEC 60079-0:2017 is available as IEC 60079-0:2017 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 60079-0:2017 specifies the general requirements for construction, testing and marking of Ex Equipment and Ex Components intended for use in explosive atmospheres. The standard atmospheric conditions (relating to the explosion characteristics of the atmosphere) under which it may be assumed that Ex Equipment can be operated are: -temperature –20 °C to +60 °C; -pressure 80 kPa (0,8 bar) to 110 kPa (1,1 bar); and -air with normal oxygen content, typically 21 % v/v. This part of IEC 60079 and other standards supplementing this standard specify additional test requirements for Ex Equipment operating outside the standard temperature range, but further additional consideration and additional testing may be required for Ex Equipment operating outside the standard atmospheric pressure range and standard oxygen content. Such additional testing may be particularly relevant with respect to Types of Protection that depend on quenching of a flame such as ‘flameproof enclosures “d”’ (IEC 60079-1) or limitation of energy, ‘intrinsic safety “i”’ (IEC 60079-11). This seventh edition cancels and replaces the sixth edition, published in 2011. This edition constitutes a technical revision. Refer to the Forward of the document for a complete listing of the technical changes between edition 7.0 and the previous edition of the document. Keywords: Ex Equipment and Ex Components intended for use in explosive atmospheres
- Standard148 pagesEnglish languagee-Library read for
Frequently Asked Questions
TC 31 is a Technical Committee within the International Electrotechnical Commission (IEC). It is named "Equipment for explosive atmospheres" and is responsible for: To prepare and maintain international standards relating to equipment for use where there is a hazard due to the possible presence of explosive atmospheres of gases, vapours, mists or combustible dusts This committee has published 437 standards.
TC 31 develops IEC standards in the area of Information technology. The scope of work includes: To prepare and maintain international standards relating to equipment for use where there is a hazard due to the possible presence of explosive atmospheres of gases, vapours, mists or combustible dusts Currently, there are 437 published standards from this technical committee.
The International Electrotechnical Commission (IEC) is the world's leading organization for the preparation and publication of international standards for electrical, electronic, and related technologies. Founded in 1906, the IEC provides a global platform for companies, industries, and governments to meet, discuss, and develop the international standards they require.
A Technical Committee (TC) in IEC is a group of experts responsible for developing international standards in a specific technical area. TCs are composed of national member body delegates and work through consensus to create standards that meet global industry needs. Each TC may have subcommittees (SCs) and working groups (WGs) for specialized topics.