IEC 60364-4-43:2023
(Main)Low-voltage electrical installations - Part 4-43: Protection for safety - Protection against overcurrent
Low-voltage electrical installations - Part 4-43: Protection for safety - Protection against overcurrent
IEC 60364-4-43:2023 provides requirements for:
- protection of live conductors, PEN conductors, PEM conductors, and PEL conductors against the harmful effects caused by overcurrent;
- coordination of measures for protection against overcurrent.
This fourth edition cancels and replaces the third edition published in 2008. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
a) the standard has been restructured, see Table 1 (Correspondence between IEC 60364‑4‑43:2008 and this document) below;
b) the measure "automatic disconnection of supply" has been designated as the preferred measure for protection against overcurrent;
c) all measures except the measure "automatic disconnection of supply" have been transferred into new normative annexes to indicate that these measures are usable in certain applications and under certain restricted conditions only (see Annex A, Annex B and Annex E);
d) a new clause "Terms and definitions" has been added;
e) new requirements have been added for the protection of the neutral or mid-point conductor (with and without triplen harmonics).
Installations électriques à basse tension - Partie 4-43: Protection pour assurer la sécurité - Protection contre les surintensités
IEC 60364-4-43:2023 fournit les exigences pour:
- la protection des conducteurs actifs, des conducteurs PEN, des conducteurs PEM et des conducteurs PEL contre les effets nuisibles des surintensités;
- la coordination des mesures de protection contre les surintensités.
Cette quatrième édition annule et remplace la troisième édition parue en 2008. Cette édition constitue une révision technique.
Cette édition inclut les modifications techniques majeures suivantes par rapport à l'édition précédente:
a) la norme a été restructurée, voir le Tableau 1 (Correspondance entre l'IEC 60364-4-43:2008 et le présent document) ci-après;
b) la mesure "déconnexion automatique de l'alimentation" a été adoptée comme mesure préférentielle pour la protection contre les surintensités;
c) toutes les mesures, à l'exception de la mesure "déconnexion automatique de l'alimentation", ont été déplacées dans de nouvelles annexes normatives pour indiquer que ces mesures sont réservées à certaines applications dans des conditions restreintes (voir l'Annexe A, l'Annexe B et l'Annexe E);
d) un nouvel article "Termes et définitions" a été ajouté;
e) de nouvelles exigences ont été ajoutées pour la protection du conducteur neutre ou du conducteur de point milieu (avec et sans harmoniques de rang 3 et multiples de 3).
General Information
Relations
Frequently Asked Questions
IEC 60364-4-43:2023 is a standard published by the International Electrotechnical Commission (IEC). Its full title is "Low-voltage electrical installations - Part 4-43: Protection for safety - Protection against overcurrent". This standard covers: IEC 60364-4-43:2023 provides requirements for: - protection of live conductors, PEN conductors, PEM conductors, and PEL conductors against the harmful effects caused by overcurrent; - coordination of measures for protection against overcurrent. This fourth edition cancels and replaces the third edition published in 2008. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) the standard has been restructured, see Table 1 (Correspondence between IEC 60364‑4‑43:2008 and this document) below; b) the measure "automatic disconnection of supply" has been designated as the preferred measure for protection against overcurrent; c) all measures except the measure "automatic disconnection of supply" have been transferred into new normative annexes to indicate that these measures are usable in certain applications and under certain restricted conditions only (see Annex A, Annex B and Annex E); d) a new clause "Terms and definitions" has been added; e) new requirements have been added for the protection of the neutral or mid-point conductor (with and without triplen harmonics).
IEC 60364-4-43:2023 provides requirements for: - protection of live conductors, PEN conductors, PEM conductors, and PEL conductors against the harmful effects caused by overcurrent; - coordination of measures for protection against overcurrent. This fourth edition cancels and replaces the third edition published in 2008. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) the standard has been restructured, see Table 1 (Correspondence between IEC 60364‑4‑43:2008 and this document) below; b) the measure "automatic disconnection of supply" has been designated as the preferred measure for protection against overcurrent; c) all measures except the measure "automatic disconnection of supply" have been transferred into new normative annexes to indicate that these measures are usable in certain applications and under certain restricted conditions only (see Annex A, Annex B and Annex E); d) a new clause "Terms and definitions" has been added; e) new requirements have been added for the protection of the neutral or mid-point conductor (with and without triplen harmonics).
IEC 60364-4-43:2023 is classified under the following ICS (International Classification for Standards) categories: 29.120.50 - Fuses and other overcurrent protection devices; 91.140.50 - Electricity supply systems. The ICS classification helps identify the subject area and facilitates finding related standards.
IEC 60364-4-43:2023 has the following relationships with other standards: It is inter standard links to IEC 60364-4-43:2008/COR1:2008, IEC 60364-4-43:2008. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
You can purchase IEC 60364-4-43:2023 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of IEC standards.
Standards Content (Sample)
IEC 60364-4-43 ®
Edition 4.0 2023-07
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Low-voltage electrical installations –
Part 4-43: Protection for safety – Protection against overcurrent
Installations électriques à basse tension –
Partie 4-43: Protection pour assurer la sécurité – Protection contre les
surintensités
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form
or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from
either IEC or IEC's member National Committee in the country of the requester. If you have any questions about IEC
copyright or have an enquiry about obtaining additional rights to this publication, please contact the address below or
your local IEC member National Committee for further information.
Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite ni
utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie et
les microfilms, sans l'accord écrit de l'IEC ou du Comité national de l'IEC du pays du demandeur. Si vous avez des
questions sur le copyright de l'IEC ou si vous désirez obtenir des droits supplémentaires sur cette publication, utilisez
les coordonnées ci-après ou contactez le Comité national de l'IEC de votre pays de résidence.
IEC Secretariat Tel.: +41 22 919 02 11
3, rue de Varembé info@iec.ch
CH-1211 Geneva 20 www.iec.ch
Switzerland
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.
About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigendum or an amendment might have been published.
IEC publications search - webstore.iec.ch/advsearchform IEC Products & Services Portal - products.iec.ch
The advanced search enables to find IEC publications by a Discover our powerful search engine and read freely all the
variety of criteria (reference number, text, technical publications previews. With a subscription you will always have
committee, …). It also gives information on projects, replaced access to up to date content tailored to your needs.
and withdrawn publications.
Electropedia - www.electropedia.org
IEC Just Published - webstore.iec.ch/justpublished
The world's leading online dictionary on electrotechnology,
Stay up to date on all new IEC publications. Just Published
containing more than 22 300 terminological entries in English
details all new publications released. Available online and once
and French, with equivalent terms in 19 additional languages.
a month by email.
Also known as the International Electrotechnical Vocabulary
(IEV) online.
IEC Customer Service Centre - webstore.iec.ch/csc
If you wish to give us your feedback on this publication or need
further assistance, please contact the Customer Service
Centre: sales@iec.ch.
A propos de l'IEC
La Commission Electrotechnique Internationale (IEC) est la première organisation mondiale qui élabore et publie des
Normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.
A propos des publications IEC
Le contenu technique des publications IEC est constamment revu. Veuillez vous assurer que vous possédez l’édition la
plus récente, un corrigendum ou amendement peut avoir été publié.
Recherche de publications IEC - Découvrez notre puissant moteur de recherche et consultez
webstore.iec.ch/advsearchform gratuitement tous les aperçus des publications. Avec un
La recherche avancée permet de trouver des publications IEC abonnement, vous aurez toujours accès à un contenu à jour
en utilisant différents critères (numéro de référence, texte, adapté à vos besoins.
comité d’études, …). Elle donne aussi des informations sur les
projets et les publications remplacées ou retirées. Electropedia - www.electropedia.org
Le premier dictionnaire d'électrotechnologie en ligne au monde,
IEC Just Published - webstore.iec.ch/justpublished
avec plus de 22 300 articles terminologiques en anglais et en
Restez informé sur les nouvelles publications IEC. Just
français, ainsi que les termes équivalents dans 19 langues
Published détaille les nouvelles publications parues.
additionnelles. Egalement appelé Vocabulaire
Disponible en ligne et une fois par mois par email.
Electrotechnique International (IEV) en ligne.
Service Clients - webstore.iec.ch/csc
Si vous désirez nous donner des commentaires sur cette
publication ou si vous avez des questions contactez-nous:
sales@iec.ch.
IEC Products & Services Portal - products.iec.ch
IEC 60364-4-43 ®
Edition 4.0 2023-07
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Low-voltage electrical installations –
Part 4-43: Protection for safety – Protection against overcurrent
Installations électriques à basse tension –
Partie 4-43: Protection pour assurer la sécurité – Protection contre les
surintensités
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 29.120.50; 91.140.50 ISBN 978-2-8322-7031-8
– 2 – IEC 60364-4-43:2023 © IEC 2023
CONTENTS
FOREWORD . 4
430 Protection against overcurrent . 8
430.1 Scope . 8
430.2 Normative references . 8
430.3 Terms and definitions . 8
430.4 General requirements . 10
431 Protection against overcurrent by automatic disconnection of supply . 10
431.1 Protection of line conductors . 10
431.2 Protection of neutral or mid-point conductor . 10
431.2.1 AC circuits without triplen harmonics and DC circuits . 10
431.2.2 Additional requirements for IT systems . 11
431.2.3 AC system with triplen harmonics . 11
431.3 Protection against overcurrent . 12
431.3.1 Protection against both overload current and short-circuit current . 12
431.3.2 Protection against overload current only . 12
431.3.3 Protection against short-circuit current only . 12
431.4 Protection against overload current . 12
431.4.1 General . 12
431.4.2 Coordination between conductors and overload protective devices . 12
431.4.3 Protection against overload current of conductors connected in parallel . 13
431.5 Protection against short-circuit currents . 14
431.5.1 General . 14
431.5.2 Determination of prospective short-circuit currents . 14
431.5.3 Protection against short-circuit current of conductors connected in
parallel . 14
431.5.4 Requirements for protection against short-circuit current . 15
431.6 Coordination of protection against overload current and protection against
short-circuit current . 17
431.6.1 Protection afforded by one device . 17
431.6.2 Protection afforded by separate devices . 17
431.6.3 Coordination for selectivity and combined short-circuit protection . 17
Annex A (normative) Protection against overcurrent by other means . 19
A.1 General . 19
A.2 Protection against overload . 19
A.3 Protection against short-circuits . 19
Annex B (normative) Protection against overcurrent by limitation of the characteristics
of supply . 20
Annex C (informative) Protection of conductors in parallel against overcurrent . 21
C.1 General . 21
C.2 Protection against overload current of conductors connected in parallel . 21
C.3 Protection against short-circuit current of conductors connected in parallel . 24
Annex D (informative) Design current . 27
Annex E (normative) Cases where automatic disconnection of supply for protection
against overcurrent can cause an increased risk . 28
Annex F (informative) List of notes concerning certain countries . 29
Bibliography . 32
Figure 1 – Coordination between conductor and protective device (conditions 1 and 2) . 13
Figure C.1 – Circuit in which an overload protective device is provided for each of the
m conductors in parallel . 23
Figure C.2 – Circuit in which a single overload protective device is provided for the m
conductors in parallel . 24
Figure C.3 – Current flow at the beginning of the short-circuit . 25
Figure C.4 – Current flow after operation of the protective device D3 . 25
Figure C.5 – Illustration of linked protective device . 26
Table 1 – Correspondence between IEC 60364-4-43:2008 and this document . 6
Table 2 – Values of k for conductors . 16
– 4 – IEC 60364-4-43:2023 © IEC 2023
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
LOW-VOLTAGE ELECTRICAL INSTALLATIONS –
Part 4-43: Protection for safety – Protection against overcurrent
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote international
co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and
in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports,
Publicly Available Specifications (PAS) and Guides (hereafter referred to as "IEC Publication(s)"). Their
preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with
may participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for
Standardization (ISO) in accordance with conditions determined by agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence between
any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of patent
rights. IEC shall not be held responsible for identifying any or all such patent rights.
IEC 60364-4-43 has been prepared by IEC technical committee 64: Electrical installations and
protection against electric shock. It is an International Standard.
This fourth edition cancels and replaces the third edition published in 2008. This edition
constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous
edition:
a) the standard has been restructured, see Table 1 (Correspondence between
IEC 60364‑4‑43:2008 and this document) below;
b) the measure "automatic disconnection of supply" has been designated as the preferred
measure for protection against overcurrent;
c) all measures except the measure "automatic disconnection of supply" have been transferred
into new normative annexes to indicate that these measures are usable in certain
applications and under certain restricted conditions only (see Annex A, Annex B and
Annex E);
d) a new clause "Terms and definitions" has been added;
e) new requirements have been added for the protection of the neutral or mid-point conductor
(with and without triplen harmonics).
The text of this International Standard is based on the following documents:
Draft Report on voting
64/2591/FDIS 64/2618/RVD
Full information on the voting for its approval can be found in the report on voting indicated in
the above table.
The language used for the development of this International Standard is English.
This document was drafted in accordance with ISO/IEC Directives, Part 2, and developed in
accordance with ISO/IEC Directives, Part 1 and ISO/IEC Directives, IEC Supplement, available
at www.iec.ch/members_experts/refdocs. The main document types developed by IEC are
described in greater detail at www.iec.ch/publications.
A list of all parts in the IEC 60364 series, published under the general title Low-voltage electrical
installations, can be found on the IEC website.
The reader's attention is drawn to the fact that Annex F lists all of the "in-some-country" clauses
on differing practices of a less permanent nature relating to the subject of this document.
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under webstore.iec.ch in the data related to the
specific document. At this date, the document will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
– 6 – IEC 60364-4-43:2023 © IEC 2023
Correspondence between IEC 60364-4-43:2008 and this document
Table 1 provides a list of contents of both the previous edition and the current edition of
IEC 60364-4-43, indicating the new structure of the standard.
Table 1 also indicates which clauses of IEC 60364-4-43:2008 have been transferred to
IEC 60364-5-53:2019.
Table 1 – Correspondence between IEC 60364-4-43:2008 and this document
IEC 60364-4-43:2008 IEC 60364-4-43:2023
Low-voltage electrical installations – Low-voltage electrical installations –
Part 4-43: Protection for safety – Protection Part 4-43: Protection for safety – Protection
against overcurrent against overcurrent
43 Protection against overcurrent 430 Protection against overcurrent
430.1 Scope 430.1 Scope
430.2 Normative references 430.2 Normative references
430.3 Terms and definitions
430.3 General requirements 430.4 General requirements
431 Requirements according to the nature of the 431 Protection against overcurrent by automatic
circuits disconnection of supply
431.1 Protection of line conductors 431.1 Protection of line conductors
431.2 Protection of the neutral conductor 431.2 Protection of neutral or mid-point conductor
431.3 Disconnection and reconnection of the neutral Deleted
conductor in multi-phase systems
Covered by product standards and 530.4.2
432 Nature of protective devices 431.3 Protection against overcurrent
Partly covered by Clause 533
432.1 Devices providing protection against both 431.3.1 Protection against both overload current
overload current and short-circuit current and short-circuit current
432.2 Devices ensuring protection against overload 431.3.2 Protection against overload current only
current only
432.3 Devices ensuring protection against 431.3.3 Protection against short-circuit current only
short‑circuit current only
432.4 Characteristics of protective devices Deleted
Covered by Clause 533
433 Protection against overload current 431.4 Protection against overload current
Coordination between conductors and Coordination between conductors and
433.1 431.4.2
overload protective devices overload protective devices
433.2 Position of devices for overload protection Deleted
Covered by 533.4.2
433.3 Omission of devices for protection against Annex A Protection against overcurrent by other
overload means, Clause A.2 Protection against overload
except 433.3.2.1 which was initially transferred to
IEC 60364-5-53:2019, 533.4.2.4 but was then
deleted at CDV stage from IEC 60364-5-53:2019
433.4 Overload protection of conductors in parallel 431.4.3 Protection against overload current of
conductors connected in parallel
434 Protection against short-circuit currents 431.5 Protection against short-circuit currents
434.1 Determination of prospective short-circuit 431.5.2 Determination of prospective short-circuit
currents currents
IEC 60364-4-43:2008 IEC 60364-4-43:2023
Low-voltage electrical installations – Low-voltage electrical installations –
Part 4-43: Protection for safety – Protection Part 4-43: Protection for safety – Protection
against overcurrent against overcurrent
434.2 Position of devices for short-circuit protection Deleted
Covered by 533.4.3
434.3 Omission of devices for protection against Annex A Protection against overcurrent by other
short-circuit means, Clause A.3 Protection against short-circuits
434.4 Short-circuit protection of conductors in 431.5.3 Protection against short-circuit current of
parallel conductors connected in parallel
434.5 Characteristics of short-circuit protective 431.5.4 Requirements for protection against short-
devices circuit current
435 Coordination of overload and short-circuit 431.6 Coordination of protection against overload
protection current and protection against short-circuit
current
435.1 Protection afforded by one device 431.6.1 Protection afforded by one device
435.2 Protection afforded by separate devices 431.6.2 Protection afforded by separate devices
Coordination for selectivity and combined
431.6.3
short-circuit protection
Annex A (normative) Protection against overcurrent by
other means
436 Limitation of overcurrent by characteristics of Annex B (normative) Protection against overcurrent by
supply limitation of the characteristics of supply
Annex A (informative) Protection of conductors in Annex C (informative) Protection of conductors in
parallel against overcurrent. parallel against overcurrent
Annex B (informative) Conditions 1 and 2 of 433.1 Deleted
Covered by Figure 1 in 431.4.2
Annex C (informative) Position or omission of devices Moved to IEC 60364-5-53:2019, Annex A
for overload protection (Position of devices for overload protection)
Annex D (informative) Position or omission of devices Moved to IEC 60364-5-53:2019, Annex B
for short-circuit protection (Position of devices for short-circuit
protection)
Annex D (informative) Design current
Annex E (normative) Cases where automatic
disconnection of supply for protection against
overcurrent can cause an increased risk
Annex E (informative) List of notes concerning certain Annex F (informative) List of notes concerning certain
countries countries
– 8 – IEC 60364-4-43:2023 © IEC 2023
LOW-VOLTAGE ELECTRICAL INSTALLATIONS –
Part 4-43: Protection for safety – Protection against overcurrent
430 Protection against overcurrent
430.1 Scope
This part of IEC 60364 provides requirements for:
– protection of live conductors, PEN conductors, PEM conductors, and PEL conductors
against the harmful effects caused by overcurrent;
– coordination of measures for protection against overcurrent.
NOTE 1 The requirements of this document do not take account of external influences.
NOTE 2 Protection of conductors according to this document does not necessarily protect the equipment
connected to the conductors.
NOTE 3 Flexible cables connecting equipment by plugs and socket-outlet to fixed installations are not part of
the scope of this document and for this reason are not necessarily protected against the harmful effects caused
by overcurrent.
430.2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies.
For undated references, the latest edition of the referenced document (including any
amendments) applies.
IEC 60364-5-52:2009, Low-voltage electrical installations – Part 5-52: Selection and erection
of electrical equipment – Wiring systems
430.3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminology databases for use in standardization at the following
addresses:
• IEC Electropedia: available at https://www.electropedia.org/
• ISO Online browsing platform: available at https://www.iso.org/obp
430.3.1
overcurrent
electric current the value of which exceeds a specified limiting value
Note 1 to entry: For conductors, the specified limiting value is equal to the current-carrying capacity.
Note 2 to entry: An overcurrent is an overload current or a short-circuit current.
[SOURCE: IEC 60050-151:2001, 151-15-28, modified – The Notes to entry have been added.]
430.3.2
overload current
overcurrent occurring in an electric circuit, which is not caused by a
short-circuit or an earth fault
[SOURCE: IEC 60050-826:2022, 826-11-15]
430.3.3
short-circuit current
electric current in a given short-circuit
[SOURCE: IEC 60050-195:2021, 195-05-18]
430.3.4
short-circuit
accidental or intentional conductive path between two or more conductive parts forcing the
electric potential differences between these conductive parts to be equal to or close to zero
[SOURCE: IEC 60050-151:2001, 151-12-04]
430.3.5
overload
operating conditions in an electrically undamaged circuit, which cause an overcurrent
[SOURCE: IEC 60050-441:1984, 441-11-08]
430.3.6
design current
electric current intended to be carried by an electric circuit in normal
operation
[SOURCE: IEC 60050-826:2022, 826-11-10]
430.3.7
rated conditional short-circuit current
I
cc
value of prospective short-circuit current, declared by the busbar trunking or powertrack system
manufacturer, that can be withstood for the disconnection time of the overcurrent protective
device under specified conditions
[SOURCE: IEC 61439-1:2020, 3.8.10.4, modified – The definition has been adapted to busbar
trunking or powertrack system.]
430.3.8
combined short-circuit protection
coordination of two overcurrent protective devices in series, capable of breaking short-circuit
currents higher than the breaking capacity of one of the devices alone
430.3.9
diversity
prospective simultaneous demand of a group of electrical loads.
[SOURCE: IEC 60364-1:—, 1.3.1]
– 10 – IEC 60364-4-43:2023 © IEC 2023
430.4 General requirements
Electric circuits shall be protected so as to eliminate the harmful effects caused by
overcurrent in live conductors, PEN conductors, PEM conductors, and PEL conductors.
This protection shall be achieved by the use of a protective device to disconnect any
overcurrent in the circuit conductors in accordance with Clause 431.
However, in certain cases, where automatic disconnection of the supply can be inappropriate,
protection may be achieved by other means as given in Annex A or by limitation of overcurrent
by the characteristics of supply as given in Annex B. In those cases where automatic
disconnection of supply can cause a danger or an increased risk, Annex E applies.
NOTE 1 Disconnection does not mean isolation in this document.
NOTE 2 Harmful effects include: thermal or mechanical effects detrimental to insulation, joints, terminations or
material surrounding the conductors.
NOTE 3 Conductors protected against overload in accordance with 431.4 are considered to be protected also
against faults likely to cause short-circuit currents of a magnitude similar to overload currents.
431 Protection against overcurrent by automatic disconnection of supply
431.1 Protection of line conductors
431.1.1 Detection of overcurrent shall be provided for all line conductors, except
where 431.1.2 applies. It shall cause the disconnection of the conductor in which the
overcurrent is detected but not necessarily the disconnection of the other live conductors.
If disconnection of a single phase can cause danger, for example in the case of a
three-phase motor, appropriate precautions shall be taken.
431.1.2 Detection of overcurrent is not required for a PEL conductor in DC circuits.
431.2 Protection of neutral or mid-point conductor
431.2.1 AC circuits without triplen harmonics and DC circuits
NOTE 1 AC circuits with triplen harmonics THD < 5 % are considered to be AC circuits without triplen harmonics.
i3n
Where the cross-sectional area (CSA) of the neutral or mid-point conductor is at least equivalent
to that of the line conductors, and the current in the neutral or mid-point conductor is
expected not to exceed the value in the line conductors, it is not necessary to provide overload
current detection for the neutral or mid-point conductor or a disconnecting device for that
conductor, except for IT systems where 431.2.2 applies.
Where the CSA of the neutral or mid-point conductor is at least equivalent to that of the line
conductors, and the current of the neutral or mid-point conductor is expected to exceed the
value of the line conductors, it is necessary to provide overload current detection for the neutral
or the mid-point conductor appropriate to the cross-sectional area of that conductor; this
detection shall cause the disconnection of the line conductors, but not necessarily of the neutral
or the mid-point conductor.
Where the CSA of the neutral or mid-point conductor is less than that of the line conductors,
a detection of overload current in the neutral or mid-point conductor shall be provided, causing
disconnection of the line conductors, but not necessarily of the neutral or mid-point conductor.
In the case where the conductors are of the same material the detection of the current in the
neutral conductor should follow the following equation:
S
N
I ≤ I ×
NZ
(1)
S
L
where
I is the detection setting current for the neutral conductor or the mid-point conductor;
N
I is the current-carrying capacity of the line conductors in the circuit;
Z
S is the CSA of the neutral conductor or the mid-point conductor;
N
S is the CSA of the line conductor.
L
NOTE 2 The formula is based on the assumption that the power loss in the neutral conductor will not be
greater than the power loss in the line conductor when loaded with a current corresponding to the current-carrying
capacity for the cable as given in IEC 60364-5-52.
The neutral or mid-point conductor shall be protected against short-circuit currents. This
protection may be achieved by the overcurrent protective devices in the line conductors. In
that case it is not necessary to provide short-circuit current detection for the neutral or mid-
point conductor or a disconnecting device for that conductor. Except for disconnection, the
requirements for a neutral conductor apply to a PEN conductor in AC systems, and the
requirements for a mid-point conductor apply to a PEM conductor in DC systems.
431.2.2 Additional requirements for IT systems
Where the neutral conductor is distributed, one of the following measures shall be provided:
– overcurrent detection for the neutral conductor of every circuit, causing disconnection of
all live conductors of the corresponding circuit;
– the neutral conductor is effectively protected against overcurrent by a protective device
placed on the supply side;
– the circuit is protected by a residual current operated protective device with a rated
residual operating current not exceeding 0,2 times the current-carrying capacity of the
corresponding neutral conductor. This device shall disconnect all the live conductors of
the corresponding circuit. The device shall have sufficient breaking capacity for all
poles.
Where a circuit in an IT DC system includes a mid-point conductor, overcurrent detection
shall be provided for the mid-point conductor, causing the disconnection of all the live
conductors of the corresponding circuit, including the mid-point conductor.
431.2.3 AC system with triplen harmonics
Where a neutral conductor carries triplen harmonics, the following applies:
a) where the harmonic content of the line currents is such that the current in the neutral
conductor is expected to cause the conductor temperature to exceed the maximum allowed
conductor temperature of the cable, the neutral conductor shall be provided with means for
overload detection causing disconnection of the line conductors but not necessarily the
neutral conductor, or
b) the CSA of the conductors shall be selected by using a reduction factor for the current-
carrying capacity as provided in IEC 60364-5-52.
NOTE In case of b), the protection of the neutral conductor is ensured by the protection of the line conductors
according to 431.4.1.
– 12 – IEC 60364-4-43:2023 © IEC 2023
431.3 Protection against overcurrent
431.3.1 Protection against both overload current and short-circuit current
Except where the circuit is protected according to 431.3.2 or 431.3.3, protection against both
overload and short-circuit current shall be provided.
431.3.2 Protection against overload current only
Where protection against overcurrent by automatic disconnection of the supply is provided only
in case of overload, protection against short-circuit current shall be achieved by other means
as specified in Clause A.3 or Annex B.
Devices for protection against overload current shall comply with the requirements of 431.4.
431.3.3 Protection against short-circuit current only
Where protection against overcurrent by automatic disconnection of the supply is provided only
in case of short-circuit, protection against overload current shall be achieved by other means
as specified in Clause A.2 or Annex B.
Devices for protection against short-circuit current shall comply with the requirements of 431.5.
431.4
Protection against overload current
431.4.1 General
Conductors shall be protected by an overcurrent protective device that disconnects overload
currents in the conductors before such currents cause detrimental effects on the conductors or
their insulation.
431.4.2 Coordination between conductors and overload protective devices
Protection against overload currents is provided if the following two conditions are satisfied:
I ≤ I ≤ I
Bn Z
(2)
I,≤×1 45 I
2Z (3)
where:
I is the design current for that circuit (see Annex D);
B
I is the continuous current-carrying capacity of the conductor system;
Z
I is the rated current of the protective device;
n
NOTE 1 For adjustable protective devices, the rated current I is the current setting selected.
n
I is the current ensuring effective operation in the conventional time of the protective device.
For conductor systems comprising insulated conductors or cables, the current-carrying capacity
shall be determined in accordance with IEC 60364-5-52:2009, Clause 523. For conductor
systems not covered by IEC 60364-5-52:2009, Clause 523, such as busbar trunking systems
and power track systems, information on current-carrying capacities shall be obtained from the
manufacturer.
The current I ensuring effective operation of the protective device shall be obtained from the
manufacturer.
It is possible that the requirement given by Formula (3) will not ensure protection in certain
cases, for example where sustained overcurrents less than I occur. In such cases,
consideration should be given to the selection of a wiring system with a higher current-carrying
capacity.
NOTE 2 The current ensuring effective operation in the conventional time of protective devices is also symbolized
I or I according to some product standards. Both I and I are multiples of I .
t f t f n
NOTE 3 Refer to Annex D for information on I .
B
Figure 1 illustrates the different currents considered.
Figure 1 – Coordination between conductor and protective device (conditions 1 and 2)
431.4.3 Protection against overload current of conductors connected in parallel
431.4.3.1 General
Where a single protective device protects several conductors in parallel, there shall be no
branch circuits or devices for isolation or switching in the parallel conductors.
This Subclause 431.4.3 does not preclude the use of ring final circuits with or without spur
connections.
NOTE 1 A ring final circuit is a final circuit where both ends of the circuit are connected to a single point of supply.
NOTE 2 Annex C, Clause C.2 provides further information on protection against overload current of conductors
connected in parallel.
431.4.3.2 Equal current sharing between parallel conductors
Where a single device protects conductors in parallel sharing currents equally, and having the
same current-carrying capacities, the value of I to be used in 431.4.2 is the sum of the current-
Z
carrying capacity of each conductor.
It is deemed that current sharing is equal if the requirements of IEC 60364-5-52:2009, 523.7 a)
are satisfied.
– 14 – IEC 60364-4-43:2023 © IEC 2023
431.4.3.3 Unequal current sharing between parallel conductors
Where currents in the parallel conductors per phase are unequal, protection against overload
in accordance with 431.4.3 shall be provided individually for each conductor.
It is deemed that current sharing is unequal if the requirements of IEC 60364-5-52:2009, 523.7
a) are not complied with.
NOTE Guidance on the protection against overload currents of the conductors in parallel is given in Annex C,
Clause C.2.
431.5 Protection against short-circuit currents
431.5.1 General
Conductors of a circuit shall be protected against the effect of short-circuit currents by one or
more overcurrent protective devices, for all supply configurations relevant for that circuit.
NOTE 1 The requirements for the position of the protective device are provided in IEC 60364-5-53:2019, 533.4.3.
2 2
NOTE 2 The reduction of the short-circuit withstands capacity (k S ) of the conductor anywhere along a circuit has
an impact on the selection and erection of short-circuit protective devices.
NOTE 3 Subclause 431.5 only considers the case of short-circuit between conductors belonging to the same circuit.
431.5.2 Determination of prospective short-circuit currents
For all configurations of the power sources, the maximum and the minimum prospective short-
circuit currents at every relevant point of the installation shall be determined.
The data needed for the determination of the prospective short-circuit currents at the relevant
point of the installation should be obtained by calculation, relevant measurements or by enquiry.
NOTE 1 For installations connected to a distribution network, the data on prospective short-circuit currents provided
by the distribution network at the point of connection can be obtained by enquiry to the distribution system operator.
NOTE 2 For installations with internal power sources, the data on prospective short-circuit currents provided by the
power sources can be obtained by enquiry to the respective power source manufacturers.
NOTE 3 IEC 60909-0 provides examples of calculation methods for short-circuit currents in AC 3-phase systems.
431.5.3 Protection against short-circuit current of conductors connected in parallel
Conductors in parallel shall be protected against the effects of short-circuit currents regardless
of whether they are protected by a single protective device or by one or more protective devices
for each conductor.
The protection shall be ensured for the most onerous location of the short-circuit, and that short-
circuit can be fed from both ends of a parallel connected conductor.
If protection by a single overcurrent protective device is not effective, then one or more of the
following measures shall be taken:
a) the wiring system shall be protected against short-circuit by other means according to
Clause A.3;
b) for two conductors in parallel, a short-circuit protective device shall be provided at the supply
side of each parallel conductor;
c) for more than two conductors in parallel, protection against short-circuit shall be provided
for each conductor.
Guidance for b) and c) is given in Annex C, Clause C.3.
431.5.4 Requirements for protection against short-circuit current
431.5.4.1 General
The short-circuit protective device, alone or in combination with an overcurrent protective
device on the supply side in accordance with 431.6.3.2, shall be capable of breaking the
maximum prospective short-circuit current in the circuit.
431.5.4.2 Protection against short-circuit current for cables and insulated
conductors
For cables and insulated conductors, all current caused by a short-circuit occurring at any point
of the circuit shall be interrupted in a time not exceeding that which brings the insulation of the
conductors to the permitted limit temperature.
For short-circuit durations < 0,1 s the let-through energy of the protective device shall be equal
2 2
to or less than the energy (k S ) that can be withstood by the cable or by the insulated
conductor.
For short-circuit durations ≤ 5 s, the time t, in which a given short-circuit current will raise the
temperature of the insulation of the conductors from the highest permissible value in normal
duty to the limit value, may be calculated by using Formula (4):
kS×
t= (4)
I
where
t is the time expressed in s;
S is the CSA, expressed in mm ;
I is the effective short-circuit current, expressed in A, expressed as an RMS value;
½ −2
k is a factor, expressed in A s mm , taking into account the resistivity, temperature
coefficient and volumetric heat capacity of the conductor material, and the appropriate initial
and final temperatures. For common conductor insulation, the values of k for conductors are
shown in Table 2.
– 16 – IEC 60364-4-43:2023 © IEC 2023
Table 2 – Values of k for conductors
Property or Type of conductor insulation
condition
PVC PVC EPR Rubber 60 °C Mineral
Thermoplastic Thermoplastic XLPE Thermosetting PVC Bare
70 °C 90 °C Thermosetting sheathed unsheathed
Conductor cross-
≤ 300 > 300 ≤ 300 > 300
sectional area mm
Initial
70 90 90 60 70 105
temperature °C
Short-circuit
maximum
160 140 160 140 250 200 160 250
temperature
limit °C
Conductor material:
a
k value for Copper
115 103 100 86 143 141 115
135 to 115
k value for
76 68 66 57 94 93 - -
Aluminum
k value for Tin-
soldered joints in 115 - - - - - - -
copper conductors
NOTE 1 Other values of k are under consideration for:
– small conductors (particularly for cross-sectional areas less than 10 mm );
– other types of joints in conductors;
– bare conductors.
NOTE 2 The nominal current of the short-circuit protective device can be greater than the current-carrying capacity
of the cable.
NOTE 3 The above factors are based on IEC 60724.
NOTE 4 See IEC 60364-5-54:2011, Annex A for the calculation me
...
La norme IEC 60364-4-43:2023, qui traite des installations électriques basse tension, se concentre particulièrement sur la protection pour la sécurité, en se focalisant sur la protection contre les surintensités. Son étendue couvre des exigences précises concernant la protection des conducteurs vivants, des conducteurs PEN, des conducteurs PEM et des conducteurs PEL contre les effets nocifs causés par des surintensités. De plus, la norme aborde la coordination des mesures de protection contre les surintensités. Cette quatrième édition est une révision technique qui remplace la troisième édition de 2008. Parmi les changements techniques significatifs introduits, on note une restructuration de la norme, qui facilite la compréhension et l'application des exigences. La mesure d'« interruption automatique de l'alimentation » est maintenant désignée comme la mesure privilégiée pour la protection contre les surintensités, soulignant ainsi son importance pour garantir la sécurité des installations électriques. En parallèle, les autres mesures de protection ont été transférées dans des annexes normatives nouvelles, indiquant qu'elles ne sont plus considérées comme des solutions standard, mais peuvent être utilisées dans des applications spécifiques et sous certaines conditions restrictives, ce qui accrédite la flexibilité de la norme tout en maintenant des normes de sécurité élevées. L'ajout d'une clause sur les « Termes et définitions » enrichit le document en clarifiant le vocabulaire utilisé, ce qui favorise une meilleure compréhension des enjeux techniques. De plus, les nouvelles exigences pour la protection du conducteur neutre ou de mi-point, y compris en présence d'harmoniques triplen, montrent une actualisation des enjeux liés à la qualité de l'énergie et à la sécurité des installations électriques. Dans l'ensemble, la norme IEC 60364-4-43:2023 est particulièrement pertinente non seulement pour garantir la sécurité des installations électriques contre les surintensités, mais également pour s'adapter aux évolutions technologiques et aux besoins spécifiques des utilisateurs. Les révisions apportées maximisent la sécurité tout en offrant des recommandations pratiques.
IEC 60364-4-43:2023は、低電圧電気設備に関する重要な標準であり、特に過電流からの保護に焦点を当てています。この標準の範囲は、ライブ導体、PEN導体、PEM導体、そしてPEL導体が過電流によって引き起こされる有害な影響から保護されるための要件を提供しています。また、過電流からの保護のための対策の調整に関する指針も含まれています。 この第四版は、2008年に発行された第三版を廃止し置き換えるものであり、技術的な改訂が行われています。重要な技術変更として、標準が再構築され、過電流からの保護に関して「供給の自動切断」が推奨措置として位置づけられています。これにより、より効果的で安全な電力供給が実現されます。 また、過電流からの保護に関連するその他の対策は、新しい規範附属書に移行され、特定の応用および制限された条件下でのみ使用可能であることが示されています。これにより、標準の適用範囲が明確になり、エンジニアや技術者が具体的な状況に応じた適切な対策を選択できるようになります。 新たに追加された「用語と定義」に関する条項は、標準の内容をより明確に理解するために役立つ情報を与えます。さらに、中性導体や中点導体に対する新たな保護要件が導入されており、トリプルハーモニックがある場合とない場合の両方についての考慮がなされています。 全体として、IEC 60364-4-43:2023は、過電流からの保護に関する包括的かつ現代的な指針を提供しており、低電圧電気設備に携わる専門家にとって非常に有用な標準となっています。
The IEC 60364-4-43:2023 standard comprehensively addresses the protection for safety in low-voltage electrical installations, specifically focusing on protection against overcurrent. This document is pivotal for ensuring the safe operation of live conductors, PEN conductors, PEM conductors, and PEL conductors by outlining essential requirements to mitigate the harmful effects that can arise from overcurrent incidents. One of the notable strengths of IEC 60364-4-43:2023 is its emphasis on the coordination of measures for protection against overcurrent. By restructuring the standard as indicated in Table 1, the document enhances clarity and user comprehension, enabling practitioners to navigate effectively through the requirements and their implementations. The designation of "automatic disconnection of supply" as the preferred measure for protection against overcurrent is a significant advancement in this edition. This clear prioritization helps guide users toward the most effective and widely applicable protection method. Moreover, the relocation of alternative measures into new normative annexes serves to clearly delineate conditions under which these approaches may be implemented. This structured approach not only streamlines the standard but also enhances safety by ensuring that additional measures are applied correctly and responsibly. The introduction of a new clause for "Terms and definitions" is another valuable addition, providing essential clarity and ensuring that all stakeholders have a shared understanding of key terms, which is crucial for effective implementation and compliance. Furthermore, the new requirements concerning the protection of the neutral or mid-point conductor-particularly with sensitivity to triplen harmonics-demonstrate a progressive approach to modern electrical safety, addressing emerging complexities in electrical installations as technology evolves. Overall, IEC 60364-4-43:2023 stands as a relevant and robust standard that not only improves safety in low-voltage electrical installations but also reflects advancements in technology and industry practices. Its comprehensive scope and updated technical specifications ensure that it remains an essential resource for professionals aiming to implement effective protection against overcurrent in their systems.
Die Norm IEC 60364-4-43:2023 behandelt den Schutz von Niederspannungsstrominstallationen und fokussiert sich auf den Schutz gegen Überstrom. Der Anwendungsbereich dieser Norm umfasst spezifische Anforderungen zum Schutz von stromführenden Leitern, PEN-Leitern, PEM-Leitern und PEL-Leitern vor den schädlichen Auswirkungen des Überstroms sowie die Koordinierung der Maßnahmen zum Schutz gegen Überstrom. Eine der herausragenden Stärken dieser Norm ist die umfassende technische Überarbeitung im Vergleich zur vorherigen Auflage von 2008. Insbesondere wurde die Struktur der Norm neu organisiert, was die Benutzerfreundlichkeit und das Verständnis verbessert. Der Verweis auf neue normative Anhänge zeigt deutlich, dass bestimmte Maßnahmen nun nur unter spezifischen Bedingungen angewendet werden sollten, was zu einer erhöhten Sicherheit und Verantwortlichkeit bei der Umsetzung beiträgt. Ein weiterer bedeutender Fortschritt ist die Bevorzugung der Maßnahme „automatische Trennung der Energieversorgung“ als primäre Schutzmaßnahme gegen Überstrom. Diese Aktualisierung stellt sicher, dass die Sicherheitsstandards auf dem neuesten Stand der Technik bleiben und praktikable Lösungen für die oft komplexe Problematik des Überstromschutzes bieten. Zusätzlich werden neue Anforderungen zum Schutz des Neutral- oder Mittelleiters eingeführt, die sowohl bei triplen Harmonischen als auch ohne diese relevant sind. Dies erweitert den Anwendungsbereich und die Effektivität der Norm in modernen elektrischen Installationen, in denen solche Aspekte zunehmend an Bedeutung gewinnen. Insgesamt ist die IEC 60364-4-43:2023 eine bedeutende Norm für alle, die im Bereich der Niederspannungsinstallation tätig sind, da sie nicht nur den aktuellen Stand der Technik widerspiegelt, sondern auch eine klare Richtung für zukünftige Entwicklungen gibt. Der Fokus auf Schutzmaßnahmen gegen Überstrom und die eingeführten Änderungen machen diese Norm zu einem unverzichtbaren Leitfaden für die Sicherheit in elektrischen Installationen.
IEC 60364-4-43:2023는 저전압 전기 설비에 대한 중요한 표준으로, 과전류로 인한 유해한 영향을 방지하기 위한 요구 사항을 제공합니다. 이 표준의 범위는 라이브 도체, PEN 도체, PEM 도체 및 PEL 도체를 보호하는 데 중점을 두고 있으며, 과전류로부터의 보호를 위한 제어 방안을 조정하는 방법에 대해서도 다루고 있습니다. 이 표준의 강점 중 하나는 과전류로부터의 보호를 위한 '자동 공급 차단' 조치를 선호하는 것으로 명확히 규정한 점입니다. 이는 안전성을 극대화하는 데 기여하며 전기 설비의 신뢰성을 높이는 중요한 변경 사항입니다. 또한, 이 표준은 지난 2008년에 발표된 제3판을 대체하는 제4판으로, 기술적 개정이 이루어졌습니다. 과거의 조치를 새로운 규범 부록으로 분리하여 특정 응용 분야와 제한된 조건에서만 사용될 수 있도록 명시한 점도 주목할 만한 변화입니다. 또한, '용어 및 정의'라는 새로운 절이 추가됨으로써 표준의 유용성이 더욱 강화되었습니다. 이를 통해 사용자는 과전류 보호에 대한 명확한 이해를 바탕으로 전기 설비를 설치하고 관리할 수 있습니다. 중성 도체 또는 중점 도체를 보호하기 위한 새로운 요구 사항이 추가되었으며, 이는 특히 트리플 조화파가 있는 경우와 없는 경우 모두에 적용됩니다. IEC 60364-4-43:2023는 안전과 관련된 전기 설비의 설계 및 운영에 필수적인 지침을 제공하며, 전기 산업 전반에 걸쳐 적용할 수 있는 중요한 표준입니다. 이 문서는 특히 전기 엔지니어와 설비 관리자에게 큰 도움이 될 것이며, 더욱 안전한 전기 설비 환경을 조성하는 데 기여할 것입니다.








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...