Fire safety engineering — Examples of fire safety objectives, functional requirements and safety criteria

ISO/TR 16576:2017 compiles examples of fire safety design objectives, functional requirements and safety criteria from Japan, France and New Zealand.

Ingénierie de la sécurité incendie — Exemples d'objectifs de sécurité incendie, d'exigences fonctionnelles et de critères de sécurité

General Information

Status
Published
Publication Date
29-Jun-2017
Current Stage
9093 - International Standard confirmed
Completion Date
01-Jun-2022
Ref Project

Buy Standard

Technical report
ISO/TR 16576:2017 - Fire safety engineering -- Examples of fire safety objectives, functional requirements and safety criteria
English language
86 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

TECHNICAL ISO/TR
REPORT 16576
First edition
2017-06
Fire safety engineering — Examples
of fire safety objectives, functional
requirements and safety criteria
Ingénierie de la sécurité incendie — Exemples d’objectifs de sécurité
incendie, d’exigences fonctionnelles et de critères de sécurité
Reference number
ISO/TR 16576:2017(E)
©
ISO 2017

---------------------- Page: 1 ----------------------
ISO/TR 16576:2017(E)

COPYRIGHT PROTECTED DOCUMENT
© ISO 2017, Published in Switzerland
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized otherwise in any form
or by any means, electronic or mechanical, including photocopying, or posting on the internet or an intranet, without prior
written permission. Permission can be requested from either ISO at the address below or ISO’s member body in the country of
the requester.
ISO copyright office
Ch. de Blandonnet 8 • CP 401
CH-1214 Vernier, Geneva, Switzerland
Tel. +41 22 749 01 11
Fax +41 22 749 09 47
copyright@iso.org
www.iso.org
ii © ISO 2017 – All rights reserved

---------------------- Page: 2 ----------------------
ISO/TR 16576:2017(E)

Contents Page
Foreword .iv
Introduction .v
1 Scope . 1
2 Normative references . 1
3 Terms and definitions . 1
4 Examples from France, New Zealand and Japan . 2
Annex A (informative) Example of fire safety design objectives and functional requirements
in France . 3
Annex B (informative) Example of fire safety design objectives and functional requirements
in New Zealand .11
Annex C (informative) Example of fire safety design objectives and functional requirements
in Japan .23
Annex D (informative) Examples of performance safety criteria for verification of
compliance with functional requirements for individual buildings in Japan .42
Bibliography .86
© ISO 2017 – All rights reserved iii

---------------------- Page: 3 ----------------------
ISO/TR 16576:2017(E)

Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards
bodies (ISO member bodies). The work of preparing International Standards is normally carried out
through ISO technical committees. Each member body interested in a subject for which a technical
committee has been established has the right to be represented on that committee. International
organizations, governmental and non-governmental, in liaison with ISO, also take part in the work.
ISO collaborates closely with the International Electrotechnical Commission (IEC) on all matters of
electrotechnical standardization.
The procedures used to develop this document and those intended for its further maintenance are
described in the ISO/IEC Directives, Part 1. In particular the different approval criteria needed for the
different types of ISO documents should be noted. This document was drafted in accordance with the
editorial rules of the ISO/IEC Directives, Part 2 (see www .iso .org/ directives).
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. ISO shall not be held responsible for identifying any or all such patent rights. Details of
any patent rights identified during the development of the document will be in the Introduction and/or
on the ISO list of patent declarations received (see www .iso .org/ patents).
Any trade name used in this document is information given for the convenience of users and does not
constitute an endorsement.
For an explanation on the voluntary nature of standards, the meaning of ISO specific terms and
expressions related to conformity assessment, as well as information about ISO’s adherence to the
World Trade Organization (WTO) principles in the Technical Barriers to Trade (TBT) see the following
URL: w w w . i s o .org/ iso/ foreword .html.
This document was prepared by Technical Committee ISO/TC 92, Fire safety, Subcommittee SC 4, Fire
safety engineering.
iv © ISO 2017 – All rights reserved

---------------------- Page: 4 ----------------------
ISO/TR 16576:2017(E)

Introduction
The vast majority of fire safety designs rely on prescriptive specifications written into regional,
national, or local regulations. Currently, various engineering approaches are also allowed by these
regulations, although information needed for an engineering approach is still generally obtained
from conventional test methods. Fire safety engineering (FSE) is a discipline increasingly being used
throughout the world in support of performance-based design, i.e. the reliance on engineering methods
to determine whether a given design meets stated performance objectives. ISO 23932 provides general
principles for a performance-based methodology for engineers to assess the level of fire safety for new
or existing built environments. Fire safety is evaluated through an engineered approach based on the
quantification of the behaviour of fire and people and based on knowledge of the consequences of such
behaviour on life safety, property and the environment.
The difference between prescriptive and performance-based approaches to fire safety design is
highlighted in ISO 23932 by emphasizing the development of quantifiable fire safety design objectives
and related functional requirements as the first step in a performance-based analysis. According
to ISO 23932, the fire safety objectives include, for example, safety of life, conservation of property,
continuity of operations, protection of the environment and preservation of heritage.
In ISO 23932, it is also mentioned that explicit performance criteria should be developed for
each functional requirement. Performance criteria are engineering metrics that are expressed
in deterministic or probabilistic (e.g. measures of fire risk) form to determine if each functional
requirement has been satisfied by the fire safety design.
As a preliminary work prior to producing ISO standardized documents for fire safety objectives,
functional requirements and safety criteria, ISO/TC 92/SC 4 decides to collect the examples of those
from the existing documents that have been developed in different countries in the course of moving
towards performance-based fire safety design. So far, three countries have responded to the solicitation
for such documents, i.e. Japan, France and New Zealand. The development of these documents, as
summarized below, was motivated by the attempts to rationalize the existing fire safety design
practices based on prescriptive building by making use of fire safety engineering methods.
Japan: First developed by the Building Research Institute during the Ministry of Construction’s project
for developing a performance-based fire safety design method, 1981 to 1986, and subsequently
improved by the committee on fire safety design in Architectural Institute of Japan, of which the report
was published in 2000.
France: Developed in the collaborative research project to establish the bases to introduce fire safety
engineering into fire safety design, which was conducted with the sponsorship of French ministry
for construction and home office from 2005 to 2011, involving research institutes, fire brigades,
practitioners, designers and owners.
New Zealand: Developed by a working group made up of external fire experts and staff from the
regulatory agency. The group was set up to research and develop a suitable fire safety design framework,
in the course of amending the New Zealand Building Codes corresponding to the introduction of the
Building Act 2004.
© ISO 2017 – All rights reserved v

---------------------- Page: 5 ----------------------
TECHNICAL REPORT ISO/TR 16576:2017(E)
Fire safety engineering — Examples of fire safety
objectives, functional requirements and safety criteria
1 Scope
This document compiles examples of fire safety design objectives, functional requirements and safety
criteria from Japan, France and New Zealand.
2 Normative references
There are no normative references in this document.
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
— IEC Electropedia: available at http:// www .electropedia .org/
— ISO Online browsing platform: available at http:// www .iso .org/ obp
3.1
functional requirements
statement of the means to achieve specified fire safety objectives, taking into account the features of a
built environment
Note 1 to entry: Mandatory functional requirements are required by building codes or national regulations;
voluntary functional requirements are expressed by other interested/affected parties.
3.2
mandatory objectives
fire safety objectives, such as life safety and protection of the environment, which are required by
building codes or national regulations
3.3
performance criteria
quantitative engineering specifications, which form an agreed basis for assessing the safety of a built
environment design
3.4
safety factor
multiplicative adjustment applied to calculated values to compensate for uncertainty in methods,
calculations, input data and assumptions
3.5
verification
process of determining that a fire safety design complies with the fire safety requirements by examining
the design in the light of safety criteria
3.6
voluntary objectives
fire safety objectives, which are requirements expressed by interested/affected parties, beyond
mandatory objectives
© ISO 2017 – All rights reserved 1

---------------------- Page: 6 ----------------------
ISO/TR 16576:2017(E)

4 Examples from France, New Zealand and Japan
Annexes A to D contain examples of fire safety objectives, functional requirements and safety criteria
from France, New Zealand and Japan.
2 © ISO 2017 – All rights reserved

---------------------- Page: 7 ----------------------
ISO/TR 16576:2017(E)

Annex A
(informative)

Example of fire safety design objectives and functional
requirements in France
A.1 Introduction
Fire safety design in France for life safety and property protection is mainly prescriptive and managed
by regulation. Even if there are already partial openings to fire safety engineering, since only some
years ago it has become increasingly obvious that more involvement in fire safety engineering need to
be made in French fire safety regulations.
In mid-2005, a collaborative research project was set up, with the sponsorship of French ministry for
construction and home office, involving different partners including research institutes, fire brigades,
practitioners, designers and owners. The research project, which ended by mid-2011, was divided into
18 main items, clustered in three main parts:
— Development of general principles for FSE assessment:
— FSE methodology;
— objectives and performance criteria;
— fire risk assessment;
— design fire and behavioural scenarios;
— verification of the methodology by examples;
— validation by reconstructions of fire incidents.
— State-of-the-art and research projects regarding:
— statistical analysis of fuel load density;
— characterization of burning items;
— fire development and spread;
— structural behaviour calculations;
— fire containment;
— behaviour at elevated temperature of regular glazing;
— fire protection;
— human behaviour.
— Communication and dissemination:
— teaching of FSE in universities or high schools for engineers;
— information and awareness of actors involved in FSE;
— publication of outcomes;
© ISO 2017 – All rights reserved 3

---------------------- Page: 8 ----------------------
ISO/TR 16576:2017(E)

— proposals for regulation improvements.
A translation of the general principles developed within the scope of this collaborative research is given
in this document. The performance-based structure consists of the three following levels:
— fire safety objectives;
— functional requirements;
— performance criteria.
Fire safety objectives which are explicitly or implicitly mentioned in French regulations (for public
buildings, tall buildings, work places, warehouses, industrial plants, etc.) were identified. Functional
requirements were selected mainly by brain storming among the members who joined this research
project.
A few examples of vulnerability criteria have been given, involving life safety objectives and
requirements, and focusing on what should be “adequate tenability conditions”. Performance criteria
proposed were derived from some national or international research works or standards.
A.2 General
A.2.1 Purpose
This document provides examples of fire safety objectives, functional requirements and performance
criteria for interested parties involved in a performance-based approach to assess the level of fire
safety of a built environment. The development of quantifiable fire safety objectives is the first step in a
performance-based analysis. This is an alternative to prescribed regulatory requirements, giving more
freedom in the design of built environments, a better cost/benefit within sustainability development,
while retaining equal or higher level of safety performance compared with the prescribed approach.
A.2.2 Scope
The examples developed in this document can apply when performing the fire safety engineering
process for a whole built environment or part of it, and for new or existing buildings. They can be used
when the performance-based approach is considered as an alternative to a prescriptive acceptable
solution (in this case, performance criteria are not defined but relative to the performance reached
by the acceptable solution when considering the selected fire safety objectives and functional
requirements).
These objectives can be used as either mandatory or voluntary fire design objectives, depending on the
regulatory requirements which need to be fulfilled.
It is necessary to have an agreement on any assumptions taken for objectives, functional requirements
and performance criteria (when they are not explicitly given in the regulation) from authorities having
jurisdiction, prior to performing the assessment work as such.
A.2.3 Terms and definitions
A.2.3.1
compartment
enclosed space, which may be subdivided, separated from adjoining spaces by fire barriers
A.2.3.2
media impact
qualitative value of exposure through a given medium
4 © ISO 2017 – All rights reserved

---------------------- Page: 9 ----------------------
ISO/TR 16576:2017(E)

A.2.3.3
safe refuge
temporary location that is free from immediate danger from effects of fire
A.2.3.4
strategic function
capacity or resource of an entity or an organization that maintains its ability to achieve future
outcomes and determines its long-term performance
A.2.3.5
sudden change
transition within a few seconds
A.2.3.6
untenable condition
condition such that people are unable to take effective action to accomplish their own escape to a place
of safe refuge
A.2.4 Symbols and abbreviated terms
Shown below are the abbreviated terms that are used in this document.
FNR functional requirement
FSE fire safety engineering
OBJ objective
A.3 Fire safety objectives
The fire safety objectives which need to be addressed in design of a building can be related to the safety
of life, property, environment, continuity of operations, or cultural heritage. The different categories of
objectives are summarized below.
OBJ 1: Health and life safety
Life safety is often the most important objective of fire safety design. It first involves occupants of the
building and may extend to firefighters who are expected to assist in evacuation or prevent extensive
uncontrolled spread of fire, and finally to third parties. Thus, three sub-objectives are defined.
OBJ 1-1: Health and life safety of occupants
OBJ 1-2: Health and life safety of firefighters
OBJ 1-3: Health and life safety of third parties
OBJ 2: Environment protection
Avoiding long-term consequences of the environmental impact of fires is becoming a more apparent
goal. The objectives of environmental protection in case of fire may be divided into two main groups as
follows:
OBJ 2-1: Ground and water
OBJ 2-2: Atmosphere
© ISO 2017 – All rights reserved 5

---------------------- Page: 10 ----------------------
ISO/TR 16576:2017(E)

OBJ 3: Property protection
Protection of property from fire damage aims generally at limiting any damage to the contents of the
building, to the building itself, or to the vicinity of the building.
In the modern world, the cost of business interruption is also of interest because it may be much higher
than the cost of direct damage to the contents and the building itself. In the same way, preservation of
the strategic functions may be essential, especially when involving, for example, transportation, power,
and other infrastructures necessary to the functioning of a community.
Besides, some buildings with architectural, historical or cultural importance may have values which
cannot be measured on a monetary scale. Their protection against the damage caused by fire is
considered to be one of the basic moral duties of the society.
Finally, in many fields of industry, a good public image is essential to success in business. A fire loss may
damage public image and lead to detrimental long-term consequences.
As a result, the property protection objectives may be divided into the following sub-objectives:
OBJ 3-1: Moveable properties and real estate within the premises
OBJ 3-2: Moveable properties and real estate of third parties
OBJ 3-3: Continuity of operations
OBJ 3-4: Strategic matters
OBJ 3-5: Preservation of heritage
OBJ 3-6: Media impact
A.4 Functional requirements
Functional requirements are necessary to take into account specific conditions related to the built
environment to enable the link between fire safety objectives and performance criteria.
OBJ 1-1: Health and life safety of occupants
FNR 1-1-1: No sudden change in the tenability conditions before every occupant left the room of origin
In the room of fire origin, the different factors influencing fire development and spread of fire effluents
shall be such that sudden changes in the exposure conditions, which can catch the occupants before
they have become aware of the hazard and have left the room, should be prevented. The underlying
idea is to delay the occurrence of a flashover in this room, for example, by distancing the different
combustible materials present in the room, or by using safety systems such as automatic detection or
sprinkler system.
FNR 1-1-2: Adequate tenability conditions in the egress route up to any occupant left
The occupants must be able to totally evacuate the building without being subject to untenable
conditions.
FNR 1-1-3: Adequate tenability conditions in space within the building, outside the room of origin,
where people are waiting for rescue
The occupants must be able to remain in a safe refuge, waiting to get rescued, without being subject to
untenable conditions.
6 © ISO 2017 – All rights reserved

---------------------- Page: 11 ----------------------
ISO/TR 16576:2017(E)

FNR 1-1-4: Adequate tenability conditions for the whole duration of the fire, in space within the building
where people have found refuge
The occupants must be able to remain in a safe refuge for the whole duration of the fire without being
subjected to untenable conditions. This is the same as the previous functional requirement, except that
the possibility to get rescued is not considered. It could lead, for example, to a fire resistance rating for
the walls of the refuge more important that in the previous case.
OBJ 1-2: Health and life safety of firefighters
FNR 1-2-1: Adequate tenability conditions during the necessary time for the reconnaissance of the
fire area
This mainly concerns the access paths for firefighting vehicles and the egress routes to search for the
origin of the fire or to identify specific risks such as storage of gas cylinders.
FNR 1-2-2: Adequate tenability conditions during the necessary time for evacuating people
The firefighters must be able to evacuate people without being subjected to untenable conditions.
FNR 1-2-3: No sudden change in the tenability conditions when fighting the fire
Sufficient time must be available for the firefighters to get out from the room, the floor or the building
before conditions have become untenable. They should not be trapped by an extremely rapid fire progress
or other flashover-related phenomena that may happen in a room with combustible partition walls.
OBJ 1-3: Health and life safety of third parties
FNR 1-3-1: Adequate tenability conditions within a neighbouring built environment during the whole
duration of the fire
The health and life safety of third parties must be ensured during the whole duration of the fire without
forcing them to leave the premises.
FNR 1-3-2: Adequate tenability conditions in the surrounding spaces, during the necessary time, as a
function of the mobility conditions of the third parties (including traffic roads)
Third parties in surrounding spaces must be able to move away from the fire zone without being
subjected to the effects of the fire. Surrounding spaces include sidewalks, public or private areas, and
roads for which visibility conditions may be essential.
OBJ 2-1: Ground and water protection
FNR 2-1-1: Reduction of hazardous solid or liquid fire residues
When fighting and extinguishing the fire, there are often serious releases of hazardous solid or liquid
fire residues to the ground or to the waste water system, which may consequently damage the ground
water or nearby lakes or rivers. Necessary measures such as containment basins must be in place to
limit or contain these combustion residues.
FNR 2-1-2: Control of hazardous fire effluent released
Necessary measures must be in place to contain the hazardous, polluting or toxic products released
during the fire. Highly hazardous products could be, for example, placed in specifically designated
areas with a particular protection and sectioned off from other areas.
OBJ 2-2: Atmosphere protection
FNR 2-2-1: Fire effluent containment
Necessary measures must be in place to contain the smoke and combustion products released during
the fire, in order to limit emissions into the atmosphere.
© ISO 2017 – All rights reserved 7

---------------------- Page: 12 ----------------------
ISO/TR 16576:2017(E)

FNR 2-2-2: Control of hazardous fire effluent released and dispersed into the atmosphere
Necessary measures must be in place to limit the hazardous, polluting or toxic products released during
the fire and dispersed into the atmosphere.
OBJ 3-1: Moveable properties and real estate within the premises
FNR 3-1-1: Preservation of a specific component within the room of origin
A specific content of the building can be considered of great interest, like a safety-deposit box or a work
of art, and specific protection (automatic detection, sprinkler system, etc.) should be used to prevent
any degradation.
FNR 3-1-2: Fire restricted to the room of origin
Necessary measures must be in place to avoid the spread of fire outside the room of origin.
FNR 3-1-3: Damages restricted to the room of origin
Even if the fire is restricted to the room of fire origin, the effects of the fire may cause damages to
adjacent rooms. It may be necessary to avoid damages outside the room of origin.
FNR 3-1-4: Damages restricted to the compartment of origin/to the floor of origin
It is the same approach as the previous requirement, except that damages are accepted to all the rooms
of the compartment or floor of origin.
OBJ 3-2: Moveable properties and real estate of third parties
FNR 3-2-1: No spread of fire to neighbouring constructions
Necessary measures must be taken to avoid the spread of fire to neighbouring constructions. For
example, to avoid the spread of fire between adjacent multi-storey buildings, a classical approach is to
limit the use of combustible materials in facades.
FNR 3-2-2: No damages to neighbouring constructions
Necessary measures must be in place to avoid damages to neighbouring constructions. It could be by
imposing distance between buildings.
OBJ 3-3: Continuity of operations
FNR 3-3-1: Preservation of a given activity
In a company, an organization, or an association, an activity of critical importance might be subjected
to specific provisions in case of fire.
FNR 3-3-2: Protection of the production capability
Necessary measures must be in place to maintain the production capability intact in case of fire.
FNR 3-3-3: Preservation of a specific device (and its supplying fittings)
Within a building, a specific device can be deemed to be essential for the good functioning of the building.
Necessary measures must be in place to protect the device and its supplying fittings in case of fire.
OBJ 3-4: Strategic matters
FNR 3-4-1: Preservation of the strategic functions
Necessary measures must be in place to ensure the continuity of the strategic functions in case of fire.
8 © ISO 2017 – All rights reserved

---------------------- Page: 13 ----------------------
ISO/TR 16576:2017(E)

FNR 3-4-2: Protection of any devices involved in strategic functions
Necessary measures must be in place to protect from the effects of the fire any devices involved in
strategic functions.
OBJ 3-5: Preservation of heritage
FNR 3-5: Protection from attack to any object or construction which could not be replaced
Necessary measures must be in place to protect from the effects of the fire any objects or buildings
with architectural, historical or cultural importance. Any alterations which are unavoidable should
be reversible, allowing the objects or building affected to be returned to its original condition.
Consequently, in some cases, fire detection would be more appropriate than fire suppression.
OBJ 3-6: Media impact
FNR 3-6: Preservation of the image from any media action
This is a global rather than an individual protection, and necessary measures must be in place to
minimize the visible consequences that may damage public image and lead to detrimental long-term
consequences.
A.5 Performance criteria
A few examples of criteria are proposed in this clause, focusing on what should be “adequate tenability
conditions”. These criteria, based on both discrete values (which are sometimes associated with a
discrete time period) and dose methods (which consider time-dependent exposures and thresholds),
are not exhaustive.
OBJ 1-1 and 1-3: Health and life safety of occupants and third parties
FNR 1-1-2, 1-1-3, 1-1-4, 1-3-1 and 1-3-2
[1][2]
Criteria 1: Maximum gas temperature of 60 °C
2 2
Criteria 2: Maximum incident heat flux of 2 kW/m (for an exposure time >10 s) or 2,5 kW/m (for an
[2]
exposure time <10 s)
4/3 −8/3 [3]
Criteria 3: Maximum radiative dose of 300 kW m s (for an exposure time <2 min)
[4]
Criteria 4: Maximum fractional effective dose (FED) of 0,3
[4]
Criteria 5: Minimum visibility of 10 m (as calculated in ISO 13571)
OBJ 1-2: Health and life safety of firefighters
FNR 1-2-1 and 1-2-2
2[5]
Criteria 6: Maximum incident heat flux of 5 kW/m
A.6 Bibliography
[1] Purser, D.A. Toxic product yields and hazard assessment for fully enclosed design fires. Polymer
International. 2000, 49, pp. 1323–1255
[2] Purser, D.A. Assessment of hazards to occupants from smoke, toxic gases, and heat. In: The
SFPE Handbook of Fire Protection Engineering – 4th Ed. NFPA, 2008
[3] Ministry of Environment. “Guide technique relatif aux valeurs de références de seuils d’effets
des phénomènes accidentels des installations classées” (October 2004)
© ISO 2017 – All rights reserved 9

---------------------- Page: 14 ----------------------
ISO/TR 16576:2017(E)

[4] ISO 13571, Life-threatening components of fire — Guidelines for the estimation of time to
compromised tenability in fires
[5] Braun E., Cobb D., Cobble V
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.