Power transformers -- Part 1: General

Applies to three-phase and single-phase transformers including autotransformers. Defines the rating and connection symbols. Gives certain specifications for transformers having a tapped winding. Defines information which shall be marked on the rating plate and the tests to be conducted.

Leistungstransformatoren -- Teil 1: Allgemeines

Transformateurs de puissance -- Partie 1: Généralités

S'applique aux transformateurs triphasés et monophasés y compris aux autotransformateurs. Définit le régime assigné et les symboles de couplage. Donne certaines prescriptions pour les transformateurs avec enroulement à prise. Définit les informations qui doivent figurer sur la plaque signalétique et les essais à effectuer.

Power transformers - Part 1: General (IEC 76-1:1993 modified)

General Information

Status
Withdrawn
Publication Date
30-Sep-1997
Withdrawal Date
01-Nov-2015
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
02-Nov-2015
Due Date
25-Nov-2015
Completion Date
02-Nov-2015

Relations

Buy Standard

Standard
EN 60076-1:1997
English language
55 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Power transformers - Part 1: General (IEC 76-1:1993 modified)Leistungstransformatoren -- Teil 1: AllgemeinesTransformateurs de puissance -- Partie 1: GénéralitésPower transformers -- Part 1: General29.180Transformatorji. DušilkeTransformers. ReactorsICS:Ta slovenski standard je istoveten z:EN 60076-1:1997SIST EN 60076-1:1997en01-oktober-1997SIST EN 60076-1:1997SLOVENSKI
STANDARD



SIST EN 60076-1:1997



SIST EN 60076-1:1997



SIST EN 60076-1:1997



SIST EN 60076-1:1997



SIST EN 60076-1:1997



SIST EN 60076-1:1997



SIST EN 60076-1:1997



NORMEINTERNATIONALEINTERNATIONALSTANDARDCEIIEC76-1Deuxième éditionSecond edition1993-03Transformateurs de puissancePartie 1:GénéralitésPower transformersPart 1:General© CEI 1993 Droits de reproduction réservés — Copyright — all rights reservedAucune partie de cette publication ne peut être reproduite niutilisée sous quelque forme que ce soit et par aucun pro-cédé, électronique ou mécanique, y compris la photocopie etles microfilms, sans l'accord écrit de l'éditeur.No part of this publication may be reproduced or utilized inany form or by any means, electronic or mechanical,including photocopying and microfilm, without permissionin writing from the publisher.Bureau Central de la Commission Electrotechnique Internationale 3, rue de Varembé Genève, SuisseIEC•Commission Electrotechnique Internationale CODE PRIX^/International Electrotechnical Commission PRICE CODE/^Mew,ayHapoaHan 3nettrpoTexmoiecttan HOMHCCHA• Pour prix, voir catalogue en vigueurFor price, see current catalogueSIST EN 60076-1:1997



Publication 60076-1 de la CEIIEC Publication 60076-1(Deuxième édition - 1993)(Second edition - 1993)Transformateurs de puissance —Power transformers —Partie 1: GénéralitésPart 1: GeneralCORRIGENDUM 1Page 76Page 77Article A.1.2:Clause A.1.2:Au point h), dans la première ligne, au lieu deItem h), in the first line, instead of.(voir 2.1 b)).(see 2.1 b)).lireread.(voir 1.2.1 b)).(see 1.2.1 b)).Juin 1997June 1997SIST EN 60076-1:1997



76-1 ©IEC: 1993- 3 -CONTENTSPageFOREWORD 7Clause1Scope and service conditions
111.1Scope
111.2Service conditions 112Normative references 153Definitions 173.1General 173.2 Terminals and neutral point 173.3 Windings
193.4Rating
213.5 Tappings
233.6 Losses and no-load current 273.7 Short-circuit impedance and voltage drop 273.8 Temperature rise 313.9Insulation 313.10 Connections 313.11 Kinds of tests 333.12 Meteorological data with respect to cooling
334 Rating 334.1Rated power 334.2 Loading cycle 354.3 Preferred values of rated power 354.4 Operation at higher than rated voltage and/or at disturbed frequency 355Requirements for transformers having a tapped winding 375.1General - Notation of tapping range 375.2 Tapping voltage - tapping current. Standard categories of tapping voltagevariation. Maximum voltage tapping 375.3 Tapping power. Full-power tappings - reduced-power tappings 435.4Specification of tappings in enquiry and order 455.5Specification of short-circuit impedance 455.6 Load loss and temperature rise
476 Connection and phase displacement symbols for three-phase transformers 49SIST EN 60076-1:1997



76-1 ©IEC: 1993– 5 –7Rating plates 537.1Information to be given in all cases 537.2Additional information to be given when applicable
558Miscellaneous requirements
578.1Dimensioning of neutral connection
578.2 Oil preservation system
578.3 Load rejection on generator transformers
579 Tolerances 5710 Tests 6310.1 General requirements for routine, type and special tests 6310.2 Measurement of winding resistance
6510.3 Measurement of voltage ratio and check of phase displacement 6710.4 Measurement of short-circuit impedance and load loss 6710.5 Measurement of no-load loss and current
6910.6 Measurement of the harmonics of the no-load current
6910.7 Measurement of zero-sequence impedance(s) onthree-phase transformers 7110.8 Tests on on-load tap-changers
71AnnexesAInformation required with enquiry and order 75BExamples of specifications for transformers with tappings
81CSpecification of short-circuit impedance by boundaries
85DThree-phase transformer connections
87ETemperature correction of load loss
93FBibliography 95SIST EN 60076-1:1997



Six Month's RuleReport on Voting14(CO)7514(CO)7776-1 © IEC: 1993- 7 -INTERNATIONAL ELECTROTECHNICAL COMMISSIONPOWER TRANSFORMERSPart 1: GeneralFOREWORD1)The IEC (International Electrotechnical Commission) is a worldwide organization for standardizationcomprising all national electrotechnical committees (IEC National Committees). The object of the IEC is topromote international cooperation on all questions concerning standardization in the electrical andelectronic fields. To this end and in addition to other activities, the IEC publishes International Standards.Their preparation is entrusted to technical committees; any IEC National Committee interested inthe subject dealt with may participate in this preparatory work. International, governmental andnon-governmental organizations liaising with the IEC also participate in this preparation. The IECcollaborates closely with the International Organization for Standardization (ISO) in accordance withconditions determined by agreement between the two organizations.2)The formal decisions or agreements of the IEC on technical matters, prepared by technical committees onwhich all the National Committees having a special interest therein are represented, express, as nearly aspossible, an international consensus of opinion on the subjects dealt with.3)They have the form of recommendations for international use published in the form of standards, technicalreports or guides and they are accepted by the National Committees in that sense.4)In order to promote international unification, IEC National Committees undertake to apply IEC InternationalStandards transparently to the maximum extent possible in their national and regional standards. Anydivergence between the IEC Standard and the corresponding national or regional standard shall be clearlyindicated in the latter.5)The IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for anyequipment declared to be in conformity with one of its standards.This International Standard has been, prepared by IEC by technical committee 14: Powertransformers.This second edition cancels and replaces the first edition published in 1976 as well as thefirst edition of IEC 76-4 published in 1976.The text of this standard is based on the following documents:Full information on the voting for the approval of this standard can be found in the reporton voting indicated in the above table.IEC 76 consists of the following parts, under the general title: Power transformers.SIST EN 60076-1:1997



76-1 ©IEC: 1993– 9 –Part 1: 1993, General.Part 2: 1993, Temperature rise.Part 3: 1980, Insulation levels and dielectric tests.Part 5: 1976, Ability to withstand short circuit.Annexes A and E form an integral part of this standard.Annexes B, C and D are for information only.SIST EN 60076-1:1997



76-1 © IEC: 1993-11 -POWER TRANSFORMERSPart 1: General1 Scope and service conditions1.1 ScopeThis part of International Standard IEC 76 applies to three-phase and single-phase powertransformers (including auto-transformers) with the exception of certain categories of smalland special transformers such as:-single-phase transformers with rated power less than 1 kVA and three-phasetransformers less than 5 kVA;-instrument transformers;-transformers for static convertors;-traction transformers mounted on rolling stock;-starting transformers;- testing transformers;-welding transformers.When IEC standards do not exist for such categories of transformers, this part of IEC 76may still be applicable either as a whole or in part.For those categories of power transformers and reactors which have their own IECstandards, this part is applicable only to the extent in which it is specifically called up bycross-reference in the other standard.*At several places in this part it is specified or recommended that an `agreement' shall bereached concerning alternative or additional technical solutions or procedures. Suchagreement is to be made between the manufacturer and the purchaser. The mattersshould preferably be raised at an early stage and the agreements included in the contractspecification.1.2 Service conditions1.2.1 Normal service conditionsThis part of IEC 76 gives detailed requirements for transformers for use under thefollowing conditions:a) AltitudeA height above sea-level not exceeding 1 000 m (3 300 ft).Such standards exist for dry-type transformers (IEC 726), for reactors in general (IEC 289), for tractiontransformers and reactors (IEC 310), and are under preparation for static convertor transformers.SIST EN 60076-1:1997



76-1 © IEC: 1993- 13 -b) Temperature of ambient air and cooling mediumA temperature of ambient air not below -25 °C and not above +40 °C. For water-cooledtransformers, a temperature of cooling water at the inlet not exceeding +25 °C.Further limitations, with regard to cooling are given for:-oil-immersed transformers in IEC 76-2;-dry-type transformers in IEC 726.c)Wave shape of supply voltageA supply voltage of which the wave shape is approximately sinusoidal.NOTE - This requirement is normally not critical in public supply systems but may have to be consideredin installations with considerable convertor loading. In such cases there is a conventional rule that thedeformation shall neither exceed 5 % total harmonic content nor 1 % even harmonic content. Also note theimportance of current harmonics for load loss and temperature rise.d)Symmetry of three-phase supply voltageFor three-phase transformers, a set of three-phase supply voltages which areapproximately symmetrical.e)Installation environmentAn environment with a pollution rate (see IEC 137 and IEC 815) that does not requirespecial consideration regarding the external insulation of transformer bushings or of thetransformer itself.An environment not exposed to seismic disturbance which would otherwise requirespecial consideration in the design. (This is assumed to be the case when the groundacceleration level ag is below 2 m/s2.)*1.2.2 Provision for unusual service conditionsAny unusual service conditions which may lead to special consideration in the design of atransformer shall be stated in the enquiry and the order. These may be factors such ashigh altitude, extreme high or low temperature, tropical humidity, seismic activity, severecontamination, unusual voltage or load current wave shapes and intermittent loading. Theymay also concern conditions for shipment, storage and installation, such as weight orspace limitations (see annex A).Supplementary rules for rating and testing are given in other publications for:-Temperature rise and cooling in high ambient temperature or at high altitude:IEC 76-2 for oil-immersed transformers, and IEC 726 for dry-type transformers.-External insulation at high altitude: IEC 76-3 and IEC 76-3-1 for oil-immersedtransformers, and IEC 726 for dry-type transformers.See IEC 68-3-3.SIST EN 60076-1:1997



76-1 © I EC: 1993- 15 -2 Normative referencesThe following normative documents contain provisions which, through reference in thistext, constitute provisions of this part of IEC 76. At the time of publication, the editionsindicated were valid. All normative documents are subject to revision, and parties toagreements based on this part of IEC 76 are encouraged to investigate the possibility ofapplying the most recent edition of the normative documents indicated below. Members ofIEC and ISO maintain registers of currently valid International Standards.IEC 50(421): 1990, International Electrotechnical Vocabulary - Chapter 421: Powertransformers and reactorsIEC 68-3-3: 1991, Environmental testing - Part 3: Guidance. Seismic test methods forequipmentsIEC 76-2: 1993, Power transformers - Part 2: Temperature riseIEC 76-3: 1980, Power transformers - Part 3: Insulation levels and dielectric tests!EC 76-3-1: 1987, Power transformers - Part 3: Insulation levels and dielectric tests.External clearances in airIEC 76-5: 1976, Power transformers - Part 5: Ability to withstand short circuitIEC 137: 1984, Bushings for alternating voltages above 1 000 VIEC 354: 1991, Loading guide for oil-immersed power transformersIEC 529: 1989, Degrees of protection provided by enclosures (IP Code)IEC 551: 1987, Determination of transformer and reactor sound levelsIEC 606: 1978, Application guide for power transformersIEC 726: 1982, Dry-type power transformersIEC 815: 1986, Guide for the selection of insulators in respect of polluted conditionsIEC 905: 1987, Loading guide for dry-type power transformersISO 3: 1973, Preferred numbers - Series of preferred numbersISO 9001: 1987, Quality systems - Model for quality assurance in design/development,production, installation and servicingSIST EN 60076-1:1997



76-1 © IEC: 1993- 17 -3 DefinitionsFor the purpose of this part of IEC 76, the following definitions shall apply. Other termsuse the meanings ascribed to them in the International Electrotechnical Vocabulary (IEV).3.1 General3.1.1 power transformer: A static piece of apparatus with two or more windings which,by electromagnetic induction, transforms a system of alternating voltage and current intoanother system of voltage and current usually of different values and at the samefrequency for the purpose of transmitting electrical power. [IEV 421-01-01, modified]3.1.2 auto-transformer*: A transformer in which at least two windings have a commonpart. [IEV 421-01-11]3.1.3 booster transformer: A transformer of which one winding is intended to beconnected in series with a circuit in order to alter its voltage and/or shift its phase. Theother winding is an energizing winding. [IEV 42-01-12, modified]3.1.4 oil-immersed type transformer: A transformer of which the magnetic circuit andwindings are immersed in oil. [IEV 421-01-14]NOTE - For the purpose of this part any insulating liquid, mineral oil or other product, is regarded as oil.3.1.5 dry-type transformer: A transformer of which the magnetic circuit and windingsare not immersed in an insulating liquid. [IEV 421-01-16]3.1.6 oil preservation system: The system in an oil-immersed transformer by which thethermal expansion of the oil is accommodated. Contact between the oil and external airmay sometimes be diminished or prevented.3.2 Terminals and neutral point3.2.1 terminal: A conducting element intended for connecting a winding to externalconductors.3.2.2 line terminal: A terminal intended for connection to a line conductor of a network.[IEV 421-02-01]3.2.3 neutral terminal:a)For three-phase transformers and three-phase banks of single-phase transformers:The terminal or terminals connected to the common point (the neutral point) of astar-connected or zigzag connected winding.b)For single-phase transformers:The terminal intended for connection to a neutral point of a network. [IEV 421-02-02,modified]* Where there is a need to express that a transformer is not auto-connected, use is made of terms such asseparate winding transformer, or double-wound transformer (see IEV 421-01-13).SIST EN 60076-1:1997



76-1 ©IEC: 1993- 19 -3.2.4 neutral point: The point of a symmetrical system of voltages which is normally atzero potential.3.2.5 corresponding terminals: Terminals of different windings of a transformer,marked with the same letter or corresponding symbol. [IEV 421-02-03]3.3 Windings3.3.1 winding: The assembly of turns forming an electrical circuit associated with one ofthe voltages assigned to the transformer.NOTE - For a three-phase transformer, the 'winding' is the combination of the phase windings (see 3.3.3).[IEV 421-03-01, modified]3.3.2 tapped winding: A winding in which the effective number of turns can be changedin steps.3.3.3 phase winding: The assembly of turns forming one phase of a three-phasewinding.NOTE - The term 'phase winding' should not be used for identifying the assembly of all coils on a specificleg. [IEV 421-03-02, modified]3.3.4 high-voltage winding*: The winding having the highest rated voltage. [IEV 421-03-03]3.3.5 low-voltage winding*: The winding having the lowest rated voltage. [IEV 421-03-04]NOTE - For a booster transformer, the winding having the lower rated voltage may be that having thehigher insulation level.3.3.6 intermediate-voltage winding*: A winding of a multi-winding transformer having arated voltage intermediate between the highest and lowest winding rated voltages.[IEV 421-03-05]3.3.7 auxiliary winding: A winding intended only for a small load compared with therated power of the transformer. [IEV 421-03-08]3.3.8 stabilizing winding: A supplementary delta-connected winding provided in astar-star-connected or star-zigzag-connected transformer to decrease its zero-sequenceimpedance, see 3.7.3. [IEV 421-03-09, modified]NOTE - A winding is referred to as a stabilizing winding only if it is not intended for three-phaseconnection to an external circuit.* The winding which receives active power from the supply source in service is referred to as a 'primarywinding', and that which delivers active power to a load as a 'secondary winding'. These terms have nosignificance as to which of the windings has the higher rated voltage and should not be used except in thecontext of direction of active power flow (see IEV 421-03-06 and 07). A further winding in the transformer,usually with lower value of rated power than the secondary winding, is then often referred to as 'tertiarywinding', see also definition 3.3.8.SIST EN 60076-1:1997



76-1 © IEC: 1993- 21 -3.3.9 common winding: The common part of the windings of an auto-transformer.[IEV 421-03-10]3.3.10 series winding: The part of the winding of an auto-transformer or the winding ofa booster transformer which is intended to be connected in series with a circuit.[IEV 421-03-11]3.3.11 energizing winding: The winding of a booster transformer which is intended tosupply power to the series winding. [IEV 421-03-12]3.4 Rating3.4.1 rating: Those numerical values assigned to the quantities which define theoperation of the transformer in the conditions specified in this part of IEC 76 and on whichthe manufacturer's guarantees and the tests are based.3.4.2 rated quantities: Quantities (voltage, current, etc.), the numerical values of whichdefine the rating.NOTES1 For transformers having tappings, rated quantities are related to the principal tapping (see 3.5.2),unless otherwise specified. Corresponding quantities with analogous meaning, related to other specifictappings, are called tapping quantities (see 3.5.10).2Voltages and currents are always expressed by their r.m.s. values, unless otherwise specified.3.4.3 rated voltage of a winding (Ur): The voltage assigned to be applied, or developedat no-load, between the terminals of an untapped winding, or of a tapped windingconnected on the principal tapping (see 3.5.2). For a three-phase winding it is the voltagebetween line terminals. [IEV 421-04-01, modified]NOTES1The rated voltages of all windings appear simultaneously at no-load when the voltage applied to one ofthem has its rated value.2For single-phase transformers intended to be connected in star to form a three-phase bank, the ratedvoltage is indicated as phase-to-phase voltage, divided by 'T for exemple Ur = 400/'3 kV.3 For the series winding of a three-phase booster transformer which is designed as an open winding (see3.10.5) the rated voltage is indicated as if the winding were connected in star, for example Ur = 23/5 kV.3.4.4 rated voltage ratio: The ratio of the rated voltage of a winding to the rated voltageof another winding associated with a lower or equal rated voltage. [IEV 421-04-02]3.4.5 rated frequency (fr): The frequency at which the transformer is designed tooperate. [IEV 421-04-03, modified]SIST EN 60076-1:1997



76-1 ©IEC: 1993– 23 –3.4.6 rated power (Sr): A conventional value of apparent power assigned to a windingwhich, together with the rated voltage of the winding, determines its rated current.NOTES1Both windings of a two-winding transformer have the same rated power which by definition is the ratedpower of the whole transformer.2 For a multi-winding transformer, half the arithmetic sum of the rated power values of all windings(separate windings, not auto-connected) gives a rough estimate of its physical size as compared with atwo-winding transformer.3.4.7 rated current (id: The current flowing through a line terminal of a winding which isderived from rated power Sr and rated voltage Ur for the winding. [IEV 421-04-05,modified]NOTES1For a three-phase winding the rated current Ir is given by:SrIr -‘/-3— A
x Ur2For single-phase transformer windings intended to be connected in delta to form a three-phase bankthe rated current is indicated as line current divided by '13 for example:I500
Ar _^3.5 Tappings3.5.1 tapping: In a transformer having a tapped winding, a specific connection of thatwinding, representing a definite effective number of turns in the tapped winding and,consequently, a definite turns ratio between this winding and any other winding with fixednumber of turns.NOTE - One of the tappings is the principal tapping, and other tappings are described in relation to theprincipal tapping by their respective tapping factors. See definitions of these terms below.3.5.2 principal tapping: The tapping to which the rated quantities are related.[IEV 421-05-02]3.5.3 tapping factor (corresponding to a given tapping):The ratio:UdUr(tapping factor) or100UdUr(tapping factor expressed as a percentage).whereUr is the rated voltage of the winding (see 3.4.3);Ud is the voltage which would be developed at no-load at the terminals of the winding, at the tappingconcerned, by applying rated voltage to an untapped winding.NOTE - This definition is not appropriate in relation to a series winding of a booster transformer(see 3.1.3), and in that case the percentage notation would be referred to the voltage of the energizingwinding or of the winding of an associated system transformer. [IEV 421-05-03, modified]SIST EN 60076-1:1997



76-1 ©IEC: 1993- 25 -3.5.4 plus tapping: A tapping whose tapping factor is higher than 1. [IEV 421-05-04]3.5.5 minus tapping: A tapping whose tapping factor is lower than 1. [IEV 421-05-05]3.5.6 tapping step: The difference between the tapping factors, expressed as apercentage, of two adjacent tappings. [IEV 421-05-06]3.5.7 tapping range: The variation range of the tapping factor, expressed as apercentage, compared with the value `100'.NOTE - If this factor ranges from 100 + a to 100 – b, the tapping range is said to be: +a %, –b % or ±a %,if a = b. [IEV 421-05-07]3.5.8 tapping voltage ratio (of a pair of windings): The ratio which is equal to therated voltage ratio:-multiplied by the tapping factor of the tapped winding if this is the high-voltagewinding;-divided by the tapping factor of the tapped winding if this is the low-voltage winding.[IEV 421-05-08]NOTE - While the rated voltage ratio is, by definition, at least equal to 1, the tapping voltage ratio can belower than 1 for certain tappings when the rated voltage ratio is close to 1.3.5.9 tapping duty: The numerical values assigned to the quantities, analogous to ratedquantities, which refer to tappings other than the principal tapping (see clause 5,and IEC 606). [IEV 421-05-09, modified]3.5.10 tapping quantities: Those quantities the numerical values of which define thetapping duty of a particular tapping (other than the principal tapping).NOTE - Tapping quantities exist for any winding in the transformer, not only for the tapped winding,(see 5.2 and 5.3).The tapping quantities are:-tapping voltage (analogous to rated voltage, 3.4.3);-tapping power (analogous to rated power, 3.4.6);-tapping current (analogous to rated current, 3.4.7). [IEV 421-05-10, modified]3.5.11 full-power tapping: A tapping whose tapping power is equal to the rated power.[IEV 421-05-14]3.5.12 reduced-power tapping: A tapping whose tapping power is lower than the ratedpower. [IEV 421-05-15]3.5.13 on-load tap-changer: A device for changing the tapping connections of awinding, suitable for operation while the transformer is energized or on load. [IEV 421-11-01]SIST EN 60076-1:1997



76-1 © IEC: 1993- 27 -3.6 Losses and no-toad currentNOTE - The values are related to the principal tapping, unless another tapping is specifically stated.3.6.1 no-load loss: The active power absorbed when rated voltage (tapping voltage) atrated frequency is applied to the terminals of one of the windings, the other winding orwindings being open-circuited. [IEV 421-06-01, modified]3.6.2 no-load current: The r.m.s. value of the current flowing through a line terminal of awinding when rated voltage (tapping voltage) is applied at rated frequency, the otherwinding or windings being open-circuited.NOTES1For a three-phase transformer, the value is the arithmetic mean of the values of current in the threephases.2 The no-load current of a winding is often expressed as a percentage of the rated current of thatwinding. For a multi-winding transformer this percentage is referred to the winding with the highest ratedpower. [IEV 421-06-02, modified]3.6.3 load loss: The absorbed active power at rated frequency and referencetemperature (see 10.1), associated with a pair of windings when rated current (tappingcurrent) is flowing through the line terminals of one of the windings, and the terminals ofthe other winding are short-circuited. Further windings, if existing, are open-circuited.NOTES1 For a two-winding transformer there is only one winding combination and one value of load loss. For amulti-winding transformer there are several values of load loss corresponding to the different two-windingcombinations (see clause 6 of IEC 606). A combined load loss figure for the complete transformer isreferred to a specified winding load combination. In general, it is usually not accessible for directmeasurement in testing.2 When the windings of the pair have different rated power values the load loss is referred to ratedcurrent in the winding with the lower rated power and the reference power should be mentioned.3.6.4 total losses: The sum of the no-load loss and the load loss.NOTE - The power consumption of the auxiliary plant is not included in the total losses and is statedseparately. [IEV 421-06-05, modified]3.7 Short-circuit impedance and voltage drop3.7.1 short-circuit impedance of a pair of windings: The equivalent series impedanceZ= R + jX, in ohms, at rated frequency and reference temperature, across the terminals ofone winding of a pair, when the terminals of the other winding are short-circuited andfurther windings, if existing, are open-circuited. For a three-phase transformer theimpedance is expressed as phase impedance (equivalent star connection).SIST EN 60076-1:1997



76-1 © IEC: 1993- 29 -In a transformer having a tapped winding, the short-circuit impedance is referred to aparticular tapping. Unless otherwise specified the principal tapping applies.NOTE - This quantity may be expressed in relative, dimensionless form, as a fraction z of the referenceimpedance Zref, of the same winding of the pair. In percentage notation:Zz = 100 ZrefwhereU2Zref=Sr(Formula valid for both three-phase and single-phase transformers).U is the voltage (rated voltage or tapping voltage) of the winding to which Zand Zref belong.Sr is the reference value of rated power.The relative value is also equal to the ratio between the applied voltage during a short-circuit measurementwhich causes the relevant rated current (or tapping current) to flow, and rated voltage (or tapping voltage).This applied voltage is referred to as the short-circuit voltage [IEV 421-07-01) of the pair of windings. It isnormally expressed as a percentage. [IEV 421-07-02, modified]3.7.2 voltage drop or rise for a specified load condition: The arithmetic differencebetween the no-load voltage of a winding and the voltage developed at the terminals ofthe same winding at a specified load and power factor, the voltage supplied to (one of) theother winding(s) being equal to:- its rated value if the transformer is connected on the principal tapping (the no-loadvoltage of the former winding is then equal to its rated value);- the tapping voltage if the transformer is connected on another tapping.This difference is generally expressed as a percentage of the no-load voltage of theformer winding.NOTE - For multi-winding transformers, the voltage drop or rise depends not only on the load and powerfactor of the winding itself, but also on the load and power factor of the other windings (see IEC 606).[IEV 421-07-03]3.7.3 zero-sequence impedance (of a three-phase winding): The impedance,expressed in ohms per phase at rated frequency, between the line terminals of athree-phase star-connected or zigzag-connected winding, connected together, and itsneutral terminal. [IEV 421-07-04, modified]NOTES1 The zero-sequence impedance may have several values because it depends on how the terminals ofthe other winding or windings are connected and loaded.2 The zero-sequence impedance may be dependent on the value of the current and the temperature,particularly in transformers without any delta-connected winding.3 The zero-sequence impedance may also be expressed as a relative value in the same way as the(positive sequence) short-circuit impedance (see 3.7.1).SIST EN 60076-1:1997



76-1 © IEC: 1993– 31 –3.8 Temperature riseThe difference between the temperature of the part under consideration and thetemperature of the external cooling medium. [IEV 421-08-01, modified]3.9 InsulationFor definitions relating to insulation see IEC 76-3.3.10 Connections3.10.1 star connection (Y-connection): The winding connection so arranged that eachof the phase windings of a three-phase transformer, or of each of the win
...