Ventilation for buildings - Air diffusion - Measurements in the occupied zone of airconditioned/ventilated rooms to evaluate thermal and acoustic conditions

This European Standard is applicable to measure some parameters of thermal and acoustic comfort (i.e. temperatures, air velocities…) in a room with an air diffusion system.
This European Standard can be used on site or in a lab for full-scale measurements.
This European Standard applies to ventilation or air conditioning systems designed to maintain the comfort conditions in buildings. It is not applicable in the case of systems for the control of industrial or other special process environments.
NOTE   In the latter case however, it may be referred to if the system technology is similar to that of the above mentioned ventilation and air conditioning systems.

Lüftung von Gebäuden - Luftverteilung - Messungen im Aufenthaltsbereich von klimatisierten/belüfteten Räumen zur Bewertung der thermischen und akustischen Bedingungen

Diese Europäische Norm ist auf die Messung einiger Parameter der thermischen und akustischen Behaglich¬keit (d. h. Temperaturen, Luftgeschwindigkeiten usw.) in einem Raum mit einer Luftverteilungsanlage anwendbar.
Die vorliegende Europäische Norm kann vor Ort oder im Labor zur Durchführung von Messungen im Originalmaßstab angewendet werden.
Diese Europäische Norm gilt für Lüftungs  oder Klimaanlagen, die dafür ausgelegt sind, die Behaglichkeits¬bedingungen in Gebäuden aufrechtzuerhalten. Sie ist nicht anwendbar auf Anlagen zur Regelung der Umgebung industrieller oder sonstiger spezieller Prozesse.
ANMERKUNG   Im letztgenannten Fall kann jedoch auf diese Norm Bezug genommen werden, wenn die Anlagentechnologie ähnlich der Technologie der vorstehend genannten Lüftungs  und Klimaanlagen ist.

Systèmes de ventilation pour les bâtiments - Diffusion d'air - Mesurages dans la zone d'occupation des pièces avec conditionnement d'air ou ventilation afin d'évaluer les conditions thermiques et acoustiques

La présente Norme européenne s’applique au mesurage de certains paramètres de confort thermique et acoustique (c’est à dire températures, vitesses de l’air, …) dans une pièce équipée d’un système de diffusion d’air.
La présente Norme européenne peut être utilisée sur site ou dans un laboratoire pour des mesures grandeur réelle.
La présente Norme européenne s’applique aux systèmes de ventilation ou de conditionnement d’air conçus pour maintenir les conditions de confort dans les bâtiments. Elle ne s’applique pas aux systèmes de contrôle des environnements de traitement industriel ou autre traitement spécial.
NOTE   Dans ce dernier cas cependant, il peut être fait référence à la présente norme si la technologie du système est similaire à celle des systèmes de ventilation et de climatisation mentionnés ci-dessus.

Prezračevanje stavb - Difuzija zraka - Merjenja v lastni coni klimatizirane/prezračevane sobe za vrednotenje toplotnih in akustičnih razmer

Ta evropski standard se uporablja za merjenje nekaterih parametrov toplotnega in akustičnega udobja (tj. temperatur, hitrosti zraka itd.) v sobi s sistemom za difuzijo zraka.
Ta evropski standard se lahko uporablja na kraju samem ali za temeljite meritve v laboratoriju.
Ta evropski standard se uporablja za sisteme za prezračevanje/klimatizacijo, ki so namenjeni vzdrževanju udobnih pogojev v zgradbah. Ne uporablja se za sisteme za nadzor industrijskih ali drugih okolij za posebne postopke.
OPOMBA: Vendar se lahko za tak primer uporabi, če je sistemska tehnologija podobna tehnologiji omenjenih sistemov za prezračevanje in klimatizacijo.

General Information

Status
Published
Public Enquiry End Date
29-May-2011
Publication Date
16-Jan-2012
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
12-Sep-2011
Due Date
17-Nov-2011
Completion Date
17-Jan-2012

Relations

Buy Standard

Standard
EN 15726:2012
English language
21 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day
Draft
k FprEN 15726:2011
English language
21 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Lüftung von Gebäuden - Luftverteilung - Messungen im Aufenthaltsbereich von klimatisierten/belüfteten Räumen zur Bewertung der thermischen und akustischen BedingungenSystèmes de ventilation pour les bâtiments - Diffusion d'air - Mesurages dans la zone d'occupation des pièces avec conditionnement d'air ou ventilation afin d'évaluer les conditions thermiques et acoustiquesVentilation for buildings - Air diffusion - Measurements in the occupied zone of airconditioned/ventilated rooms to evaluate thermal and acoustic conditions91.140.30VLVWHPLVentilation and air-conditioningICS:Ta slovenski standard je istoveten z:EN 15726:2011SIST EN 15726:2012en,fr,de01-februar-2012SIST EN 15726:2012SLOVENSKI
STANDARD



SIST EN 15726:2012



EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 15726
October 2011 ICS 91.140.30 English Version
Ventilation for buildings - Air diffusion - Measurements in the occupied zone of air-conditioned/ventilated rooms to evaluate thermal and acoustic conditions
Systèmes de ventilation pour les bâtiments - Diffusion d'air - Mesurages dans la zone d'occupation des pièces avec conditionnement d'air ou ventilation afin d'évaluer les conditions thermiques et acoustiques
Lüftung von Gebäuden - Luftverteilung - Messungen im Aufenthaltsbereich von klimatisierten/belüfteten Räumen zur Bewertung der thermischen und akustischen Bedingungen This European Standard was approved by CEN on 4 September 2011.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2011 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 15726:2011: ESIST EN 15726:2012



EN 15726:2011 (E) 2 Contents Page Foreword .31Scope .42Normative references .43Terms and definitions .44Test set up and conditions .54.1General .54.2Thermal loads .54.3Furniture .54.4Other conditions .55Methodology .65.1Sampling in a room.65.2Measurements .65.2.1General .65.2.2Airflow rate .65.2.3Velocities in the occupied zone .75.2.4Temperature measurements . 115.2.5Sound pressure level . 116Test report . 13Annex A (normative)
Operational and environmental conditions . 14Annex B (informative)
Typical Flow Pattern . 15Annex C (informative)
Intermittence and draught risk . 16Annex D (informative)
Estimation of Air velocities in the occupied zone for different types of jets. 19Annex E (informative)
Ventilation Efficiency Measurement. 20Bibliography . 21 SIST EN 15726:2012



EN 15726:2011 (E) 3 Foreword This document (EN 15726:2011) has been prepared by Technical Committee CEN/TC 156 “Vetnilation for buildings”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by April 2012, and conflicting national standards shall be withdrawn at the latest by April 2012. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. SIST EN 15726:2012



EN 15726:2011 (E) 4 1 Scope
This European Standard is applicable to measure some parameters of thermal and acoustic comfort (i.e. temperatures, air velocities…) in a room with an air diffusion system.
This European Standard can be used on site or in a lab for full-scale measurements.
This European Standard applies to ventilation or air conditioning systems designed to maintain the comfort conditions in buildings. It is not applicable in the case of systems for the control of industrial or other special process environments.
NOTE In the latter case however, it may be referred to if the system technology is similar to that of the above mentioned ventilation and air conditioning systems. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 12599, Ventilation for buildings — Test procedures and measuring methods for handing over installed ventilation and air conditioning systems EN 13182 Ventilation for buildings — Instrumentation requirements for air velocity measurements in ventilated spaces EN 13779, Ventilation for non-residential buildings — Performance requirements for ventilation and room-conditioning systems prEN 16211, Ventilation for buildings — Measurement of air flows on site — methods EN ISO 5167-1, Measurement of fluid flow by means of pressure differential devices inserted in circular cross-section conduits running full — Part 1: General principles and requirements (ISO 5167-1:2003) EN ISO 7726, Ergonomics of the thermal environment - Instruments for measuring physical quantities (ISO 7726:1998) 3 Terms and definitions
For the purposes of this document, the following terms and definitions apply: 3.1 reference point point where the measurements are taken 3.2 mean velocity time average velocity over the whole measuring period 3.3 spatial average velocity average value of mean velocities taken in several points in the occupied zone SIST EN 15726:2012



EN 15726:2011 (E) 5 3.4 spatial maximum velocity maximum value of mean velocities taken in several points in the occupied zone 3.5 test area usually areas designed for human occupancy and defined as a volume of air that is confined by specified horizontal and vertical planes NOTE 1 The vertical planes are usually parallel with the walls of the room. Usually there is also a limit placed on the height of the occupied zone. Thus, the occupied zone in a room is that space in which the occupants are normally located and where the requirements for the indoor environment shall be satisfied. Definitions are given in EN 13779:2007, 7.2.
NOTE 2 Definition of the occupied zone is dependent on the geometry and the use of the room and should be specified case by case. [Occupied area, EN 13779, modified] 3.6 occupied zone (for laboratory purpose) portion of the treated space geometrically limited to be no closer than 0,15 m to all walls and within a height of 1,8 m above the floor 4 Test set up and conditions 4.1 General
Before any test, the air diffusion system shall be checked accordance with EN 12599 so that its performance may be recorded.
If the system performance does not meet the design criteria, correction shall be considered prior to the continuation of the test. If this is not possible this shall be made clear in the report along with the assumptions made. 4.2 Thermal loads The room should be occupied according to its expected use or thermal loads have to be simulated. This should include all internal and external loads (occupants, lights, equipment…). For on site measurements internal and external loads should be reported (actual or simulated).
4.3 Furniture Furniture, curtains, absorbent surfaces, etc. can influence thermal or acoustic characteristics and should therefore be as representative as possible. 4.4 Other conditions Operational conditions of system running (VAV, fan speed, variable geometry…) and environmental conditions do have influence on results and have to be reported according to Annex A. Conditions must be stabilised as much as possible during the test. For instance, supply temperature and reference point temperature should be checked regularly and should not vary during the test by more than +/- 1 K. If this is not possible then the variation shall be recorded. SIST EN 15726:2012



EN 15726:2011 (E) 6 5 Methodology 5.1 Sampling in a room The reference point will be situated in the centre of the test area at a height of 1,1 m. Large areas may be divided into smaller parts, usually recommended to be less than or equal to 20 m2 (EN 12599). In this case, each smaller part shall be treated as a test area There should be enough area to ensure a correct representation of the overall and local air diffusion. It is recommended that the test area takes into account several diffusers jets in order to cover the effect of jet interaction.
5.2 Measurements 5.2.1 General
Different levels of measurements can be used:  Level 1: easy and quick check at the reference point(s).
 Level 2: more detailed check. Level 1 tests have to be performed first. For each level, required measurements are indicated in Table 1. Table 1 — Measurements required
Level 1 Level 2 Airflow rate Smoke test or any other jet visualisation (5.2.2.1) Measurement (5.2.2.2) Velocities
Measurement (5.2.3.2) Temperatures At reference point (5.2.4.2) Measurement (5.2.4.3)
Sound pressure level Overall dB(A) level at the reference point, or any other point where the highest sound level can be expected. (5.2.5.1) Octave band in order to recalculate any criteria (dB(A), dB(C), NR…) asked (5.2.5.2) If required Ventilation Efficiency
see Annex E
5.2.2 Airflow rate 5.2.2.1 Level 1: Jet visualisation Jet shall be visualised either by smoke test or by any other means
The objective of the visualisation is:  to determine the air flow pattern in the occupied zone;
 to detect possible high velocity areas; SIST EN 15726:2012



EN 15726:2011 (E) 7  to detect possible dead zones;
Examples of common flow patterns are given in Annex B. 5.2.2.2 Level 2: Airflow rate measurements Any method described either in prEN 16211, EN 12599 or EN ISO 5167-1 (lab measurements) shall be used for the determination of airflow rates. Both supply and extract airflow rates shall be determined if
...

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Lüftung von Gebäuden - Luftverteilung - Messungen im Aufenthaltsbereich von klimatisierten/belüfteten Räumen zur Bewertung der thermischen und akustischen BedingungenSystèmes de ventilation pour les bâtiments - Diffusion d'air - Mesurages dans la zone d'occupation des pièces avec conditionnement d'air ou ventilation afin d'évaluer les conditions thermiques et acoustiquesVentilation for buildings - Air diffusion - Measurements in the occupied zone of airconditioned/ventilated rooms to evaluate thermal and acoustic conditions91.140.30VLVWHPLVentilation and air-conditioningICS:Ta slovenski standard je istoveten z:FprEN 15726kSIST FprEN 15726:2011en,fr,de01-maj-2011kSIST FprEN 15726:2011SLOVENSKI
STANDARD



kSIST FprEN 15726:2011



EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
FINAL DRAFT
FprEN 15726
March 2011 ICS 91.140.30 English Version
Ventilation for buildings - Air diffusion - Measurements in the occupied zone of airconditioned/ventilated rooms to evaluate thermal and acoustic conditions
Systèmes de ventilation pour les bâtiments - Diffusion d'air - Mesurages dans la zone d'occupation des pièces avec conditionnement d'air ou ventilation afin d'évaluer les conditions thermiques et acoustiques
Lüftung von Gebäuden - Luftverteilung - Messungen im Aufenthaltsbereich von klimatisierten/belüfteten Räumen zur Bewertung der thermischen und akustischen Bedingungen This draft European Standard is submitted to CEN members for unique acceptance procedure. It has been drawn up by the Technical Committee CEN/TC 156.
If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to provide supporting documentation.
Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and shall not be referred to as a European Standard.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2011 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. FprEN 15726:2011: EkSIST FprEN 15726:2011



FprEN 15726:2011 (E) 2 Contents Page Foreword .31Scope .42Normative references .43Terms and definitions .44Test set up and conditions .54.1General .54.2Thermal loads .54.3Furniture .54.4Other conditions .55Methodology .55.1Sampling in a room.55.2Measurements .65.2.1General .65.2.2Airflow rate .65.2.3Velocities in the occupied zone .75.2.4Temperature measurements . 115.2.5Sound pressure level . 126Test report . 13Annex A (normative)
Operational and environmental conditions . 14Annex B (informative)
Typical Flow Pattern . 15Annex C (informative)
Intermittence and draught risk . 16Annex D (informative)
Estimation of Air velocities in the occupied zone for different types of jets. 19Annex E (informative)
Ventilation Efficiency Measurement. 20Bibliography . 21 kSIST FprEN 15726:2011



FprEN 15726:2011 (E) 3 Foreword This document (FprEN 15726:2011) has been prepared by Technical Committee CEN/TC 156 “Vetnilation for buildings”, the secretariat of which is held by BSI. This document is currently submitted to the Unique Acceptance Procedure. kSIST FprEN 15726:2011



FprEN 15726:2011 (E) 4 1 Scope
This European Standard is applicable to measure some parameters of thermal and acoustic comfort (i.e. temperatures, air velocities…) in a room with an air diffusion system.
This European Standard can be used on site or in a lab for full-scale measurements.
This European Standard applies to ventilation or air conditioning systems designed to maintain the comfort conditions in buildings. It is not applicable in the case of systems for the control of industrial or other special process environments.
NOTE In the latter case however, it may be referred to if the system technology is similar to that of the above mentioned ventilation and air conditioning systems. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 12599, Ventilation for buildings — Test procedures and measuring methods for handing over installed ventilation and air conditioning systems EN 13182 Ventilation for buildings — Instrumentation requirements for air velocity measurements in ventilated spaces EN 13779, Ventilation for non-residential buildings — Performance requirements for ventilation and room-conditioning systems prEN 16211, Ventilation for buildings — Measurement of air flows on site — methods EN ISO 5167-1, Measurement of fluid flow by means of pressure differential devices inserted in circular cross-section conduits running full — Part 1: General principles and requirements (ISO 5167-1:2003) ISO 7726, Ergonomics of the thermal environment — Instruments for measuring physical quantities
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply: 3.1 reference point point where the measurements are taken 3.2 mean velocity at a point, mean velocity is the time average velocity over the measuring period 3.3 spatial Average (or residual) velocity average value of mean velocities taken in several points in the occupied zone 3.4 spatial Maximum velocity maximum value of mean velocities taken in several points in the occupied zone kSIST FprEN 15726:2011



FprEN 15726:2011 (E) 5 3.5 test area equal to the occupied zone according to EN 13779 4 Test set up and conditions 4.1 General
Before any test, the air diffusion system shall be checked accordance with EN 12599 so that its performance may be recorded.
If the system performance does not meet the design criteria correction shall be considered prior to the continuation of the test. If this is not possible this shall be made clear in the report along with the assumptions made. 4.2 Thermal loads The room should be occupied according to its expected use or thermal loads have to be simulated. This should include all internal and external loads (occupants, lights, equipment…). For on site measurements internal and external loads should be reported (actual or simulated).
4.3 Furniture Furniture, curtains, absorbent surfaces, etc. can influence thermal or acoustic characteristics and should therefore be as representative as possible. 4.4 Other conditions Operational conditions of system running (VAV, fan speed, variable geometry…) and environmental conditions do have influence on results and have to be reported according to Annex A. Conditions must be stabilised as much as possible during the test. For instance, supply temperature and reference point temperature should be checked regularly and should not vary during the test by more than +/- 1 K.
If this is not possible then the variation shall be recorded. 5 Methodology 5.1 Sampling in a room The reference point will be situated in the centre of the test area at a height of 1.1 m. Large areas may be divided in smaller parts, usually recommended to be less than or equal to 20 m2 (EN 12599). In this case, each smaller part shall be treated as a test area There should be enough area to ensure a correct representation of the overall and local air diffusion. It is recommended that the test area takes into account several diffusers jets in order to cover the effect of jet interaction.
kSIST FprEN 15726:2011



FprEN 15726:2011 (E) 6 5.2 Measurements 5.2.1 General
Different levels of measurements can be used:  Level 1: easy and quick check at the reference point(s).
 Level 2: more detailed check. Level 1 tests have to be performed first. For each level, required measurements are indicated in Table 1. Table 1 — Measurements required
Level 1 Level 2 Airflow rate Smoke test or any other jet visualisation (5.2.2.1) Measurement (5.2.2.2) Velocities
Measurement (5.2.3.2) Temperatures At reference point (5.2.4.2) Measurement (5.2.4.3)
Sound pressure level Overall dBA level at the reference point, or any other point where the highest sound level can be expected. (5.2.5.1) Octave band in order to recalculate any criteria (dB(A), dB(C), NR…) asked (5.2.5.2) If required Ventilation Efficiency
see Annex E
5.2.2 Airflow rate 5.2.2.1 Level 1: Jet visualisation Jet shall be visualised either by smoke test or by any other means
The objective of the visualisation is:  to determine the air flow pattern in the occupied zone;
 to detect possible high velocity areas;  to detect possible dead zones;
Examples of common flow patterns are given in Annex B. 5.2.2.2 Level 2: Airflow rate measurements Any method described either in prEN 16211, EN 12599 or EN ISO 5167-1 (lab measurements) shall be used for the determination of airflow rates. Both supply and extract airflow rates shall be determined if applicable. Results have to be compared to designed values and, if not appropriate, ventilation system shall be adjusted before continuing measurements. kSIST FprEN 15726:2011



FprEN 15726:2011 (E) 7 5.2.3 Velocities in the occupied zone 5.2.3.1 Level 1
No measurements are required. Flow visualisation as in 5.2.2. 5.2.3.2 Level 2: measurements The measurements of low velocities within treated spaces shall be made wi
...