Ventilation for buildings - Performance testing of components/products for residential ventilation - Part 10: Hygrometric air oulet

To specify laboratory methods for testing all humidity controlled exhaust air terminal devices.  It describes tests intended  to characterise aero and hydro-dynamic performance,  air diffusion and noise characteristics.This European Standard specifies laboratory methods for testing humidity controlled exhaust air terminal devices. This European Standard applies to all controlled devices on indoor humidity, used in mechanical and natural powered residential ventilation systems. For instance, devices of the following types: - humidity controlled devices with a manually adjustable opening;- humidity controlled devices with fixed setting;- humidity controlled devices self-adjusting on pressure difference. This European Standard describes tests intended to characterize: - aero and hygro-dynamic performance;- acoustic characteristics (including noise production of the device;- insertion loss of the device; sound insulation);- time response.

Lüftung von Gebäuden - Leistungsprüfung von Bauteilen/Produkten für die Lüftung von Wohnungen - teil 10: Hygrometrische Abluftdurchlässe

Diese Europäische Norm legt Laborverfahren für die Prüfung von feuchtegeregelten Abluftdurchlässen fest.
Sie gilt für alle durch die Raumluftfeuchte geregelten Abluftdurchlässe, die in maschinellen und natürlichen Lüftungsanlagen von Wohnungen verwendet werden. Dazu gehören zum Beispiel folgende Arten:
   feuchtegeregelte Abluftdurchlässe mit manuell einstellbarer Öffnung;
   feuchtegeregelte Abluftdurchlässe mit festen Einstellungen;
   feuchtegeregelte Abluftdurchlässe, sich selbstständig bei Druckdifferenz  einstellend.
Diese Europäische Norm beschreibt Prüfungen, die der Bestimmung folgender Größen dienen:
                aero - und hygrodynamische Leistungsfähigkeit;
   akustische Merkmale (einschließlich Geräuscherzeugung und Eintrittsverlust des Abluftdurchlasses, Schalldämmung);
Zeitverhalten.

Ventilation des bâtiments - Essais de performance des composants/produits pour la ventilation des logements - Partie 10 : Bouche d'air d'évacuation hygroréglable

Le présent document spécifie des méthodes de laboratoire pour les essais des bouches d’air d’évacuation hygroréglables.
Ce document s’applique a tous les dispositifs commandés par l’humidité intérieure et utilisés dans les systemes de ventilation mécanique et naturelle des logements. Il s’agit, par exemple, des types de dispositifs suivants :
- dispositifs hygroréglables, a ouverture ajustable manuellement ;
- dispositifs hygroréglables a réglages fixes ;
- dispositifs hygroréglables et auto-réglables en fonction de la différence de pression.
Le présent document décrit les essais destinés a caractériser :
- es performances aérauliques et hygro-dynamiques ;
- les caractéristiques acoustiques (y compris le bruit produit par le dispositif ; la perte d’insertion du dispositif ; l’isolement acoustique).

Prezračevanje stavb - Preskušanje lastnosti komponent/proizvodov za prezračevanje stanovanj - 10. del: Kontrola zraka ob izpustu/izhodu

General Information

Status
Published
Publication Date
12-Aug-2008
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
20-May-2008
Due Date
25-Jul-2008
Completion Date
13-Aug-2008

Buy Standard

Standard
EN 13141-10:2008
English language
16 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 13141-10:2008
01-september-2008
3UH]UDþHYDQMHVWDYE3UHVNXãDQMHODVWQRVWLNRPSRQHQWSURL]YRGRY]D
SUH]UDþHYDQMHVWDQRYDQMGHO.RQWUROD]UDNDREL]SXVWXL]KRGX
Ventilation for buildings - Performance testing of components/products for residential
ventilation - Part 10: Hygrometric air oulet
Lüftung von Gebäuden - Leistungsprüfung von Bauteilen/Produkten für die Lüftung von
Wohnungen - teil 10: Hygrometrische Abluftdurchlässe
Ventilation des bâtiments - Essais de performance des composants/produits pour la
ventilation des logements - Partie 10 : Bouche d'air d'évacuation hygroréglable
Ta slovenski standard je istoveten z: EN 13141-10:2008
ICS:
91.140.30 3UH]UDþHYDOQLLQNOLPDWVNL Ventilation and air-
VLVWHPL conditioning
SIST EN 13141-10:2008 en,fr
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 13141-10:2008

---------------------- Page: 2 ----------------------

SIST EN 13141-10:2008
EUROPEAN STANDARD
EN 13141-10
NORME EUROPÉENNE
EUROPÄISCHE NORM
May 2008
ICS 91.140.30

English Version
Ventilation for buildings - Performance testing of
components/products for residential ventilation - Part 10:
Humidity controlled extract air terminal device
Ventilation des bâtiments - Essais de performance des Lüftung von Gebäuden - Leistungsprüfungen von
composants/produits pour la ventilation des logements - Bauteilen/Produkten für die Lüftung von Wohnungen - Teil
Partie 10 : Bouche d'extraction d'air hygroréglable 10: Feuchtegeregelte Abluftdurchlässe
This European Standard was approved by CEN on 11 April 2008.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the CEN Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the
official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36  B-1050 Brussels
© 2008 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 13141-10:2008: E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------

SIST EN 13141-10:2008
EN 13141-10:2008 (E)
Contents Page
Foreword. 3
1 Scope. 5
2 Normative references . 5
3 Terms and definitions. 5
4 Symbols and abbreviations . 5
5 Performance testing of aerodynamic and hygro-dynamic characteristics. 6
5.1 Aero and hygro-dynamic performances.6
5.1.1 Principle . 6
5.1.2 Test installation, conditions and uncertainty of measurement. 6
5.1.3 Test procedure . 8
5.1.4 Analysis of results . 14
5.1.5 Test report . 14
5.2 Other tests . 14
5.2.1 Time response test . 14
5.2.2 Performance testing of acoustic characteristics. 15
Bibliography . 16

2

---------------------- Page: 4 ----------------------

SIST EN 13141-10:2008
EN 13141-10:2008 (E)
Foreword
This document (EN 13141-10:2008) has been prepared by Technical Committee CEN/TC 156
“Ventilation for buildings”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by November 2008, and conflicting national standards
shall be withdrawn at the latest by November 2008.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such
patent rights.
This document is one of a series of standards on residential ventilation. The performance
characteristics of the components/products for residential ventilation are given in EN 13142.
The position of this document in the field of the mechanical building services is shown in Figure 1.
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria,
Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland,
Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania,
Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom.
3

---------------------- Page: 5 ----------------------

SIST EN 13141-10:2008
EN 13141-10:2008 (E)

Figure 1 — Position of EN 13141-10 in the field of the mechanical building services
4

---------------------- Page: 6 ----------------------

SIST EN 13141-10:2008
EN 13141-10:2008 (E)

1 Scope
This European Standard specifies laboratory methods for testing humidity controlled exhaust air
terminal devices.
This European Standard applies to all controlled devices on indoor humidity, used in mechanical and
natural powered residential ventilation systems. For instance, devices of the following types:
 humidity controlled devices with a manually adjustable opening;
 humidity controlled devices with fixed setting;
 humidity controlled devices self-adjusting on pressure difference.
This European Standard describes tests intended to characterize:
 aero and hygro-dynamic performance;
 acoustic characteristics (including noise production of the device; insertion loss of the device;
sound insulation);
 time response.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 12792:2003, Ventilation for buildings — Symbols, terminology and graphical symbols
EN 13141-2:2004, Ventilation for buildings — Performance testing of components/products for
residential ventilation - Part 2: Exhaust and supply air terminal devices
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 12792:2003, EN 13141-
2:2004 and the following apply.
3.1
hysteresis
value defined as the difference of relative humidity, read on the response curve for the same flow,
in % RH
4 Symbols and abbreviations
For the purposes of this document, the symbols and units given in EN 12792:2003 and the symbols
and units given in Table 1 apply.

5

---------------------- Page: 7 ----------------------

SIST EN 13141-10:2008
EN 13141-10:2008 (E)
Table 1 — Symbols and units
Term Symbol Unit
humidity
ϕ
-1
minimum airflow  q l. s
v min
-1
maximum airflow  q l. s
v max
relative humidity ϕ % RH
p
maximum relative humidity for minimum airflow  ϕ % RH
p min
minimum relative humidity for maximum airflow % RH
ϕ
p max

5 Performance testing of aerodynamic and hygro-dynamic characteristics
5.1 Aero and hygro-dynamic performances
5.1.1 Principle
This test consists of measuring several volume flow rates induced through a device by humidity
conditions, under an applied static pressure difference, to define the flow rate/humidity characteristic
curve.
In the case of manually adjustable devices, a test according to EN 13141-2 shall be carried out at
specific opening conditions specified by the manufacturer.
Some exhaust air terminal devices are designed to work under both natural and mechanical
ventilation systems. In this case the manufacturer may have to specify two operational ranges, and
the device shall be tested for each of them.
5.1.2 Test installation, conditions and uncertainty of measurement
5.1.2.1 Test installation and conditions
The test facility shall include one room controlled both in humidity and temperature, representing
indoor conditions. The airflow test rig may be either in this room or outside but in this case, it shall be
verified that all test conditions are still valid, i.e leakages shall be included to achieve the overall
uncertainty of measurement that is required.
The test installation shall comply with those of EN 13141-2:2004, 4.1.2.1 for indoor rooms.
The test facilities shall have a range from – 300 Pa to 0 Pa.
Special care to limit air velocities around the inlet in the test box shall be taken: air velocities shall be
-1
measured at locations specified in Figure 2. The measures shall not exceed 0,10 m.s at these points
without airflow through the exhaust vent.
6

---------------------- Page: 8 ----------------------

SIST EN 13141-10:2008
EN 13141-10:2008 (E)
d

Key
• Locations of the measurement points
d = 0,04 m
l = 0,20 m
Figure 2 — Locations of measurement points
To avoid difficulties in the control of the humidity and temperature controlled room, the volume should
be big enough.
The air permeability of the test equipment shall be measured with the test specimen sealed, over the
same range of pressure differences used during the performance testing of the specimen.
The air permeability of the test equipment shall be reported and shall generate a leakage lower than
-1
0,1 l. s at 100 Pa.
NOTE For low airflow measurements, it can be necessary to introduce some intentional leakage.
In this case, the leakage airflow shall be measured and used in the test report for correction of values
and for uncertainty calculations.
5.1.2.2 Uncertainty of measurement
The pressure shall
...