High-voltage switchgear and controlgear - Part 203: Gas-insulated metal-enclosed switchgear for rated voltages above 52 kV (IEC 62271-203:2011)

IEC 62271-203:2011 specifies requirements for gas-insulated metal-enclosed switchgear in which the insulation is obtained, at least partly, by an insulating gas other than air at atmospheric pressure, for alternating current of rated voltages above 52 kV, for indoor and outdoor installation, and for service frequencies up to and including 60 Hz. This second edition of IEC 62271-203 cancels and replaces the first edition of IEC 62271-203, published in 2003, and constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:   - adopting the structure and the content to IEC 62271-1,   - harmonisation with IEEE C37.122,   - addition of the new Annex F and the new Annex G.   This publication is to be read in conjunction with IEC 62271-1:2007.

Hochspannungs-Schaltgeräte und -Schaltanlagen - Teil 203: Gasisolierte metallgekapselte Schaltanlagen für Bemessungsspannungen über 52 kV (IEC 62271-203:2011)

Appareillage à haute tension - Partie 203: Appareillage sous enveloppe métallique à isolation gazeuse de tensions assignées supérieures à 52 kV (CEI 62271-203:2011)

La CEI 62271-203:2011 spécifie les exigences pour l'appareillage sous enveloppe métallique à isolation gazeuse dont l'isolation est réalisée, au moins partiellement, par un gaz isolant autre que l'air à la pression atmosphérique, pour courant alternatif de tensions assignées supérieures à 52 kV, pour l'installation à l'intérieur et à l'extérieur, et pour des fréquences de service inférieures ou égales à 60 Hz. Cette deuxième édition de la CEI 62271-203 annule et remplace la première édition de la CEI 62271-203 publiée en 2003, et constitue une révision technique. Cette édition inclut les modifications techniques majeures suivantes par rapport à l'édition précédente:  - adoption de la structure et du contenu de la CEI 62271-1,   - harmonisation avec l'IEEE C37.122,   - ajout de la nouvelle Annexe F et de la nouvelle Annexe G.   Cette publication doit être lue conjointement avec la CEI 62271-1:2007.

Visokonapetostne stikalne in krmilne naprave - 203. del: Plinsko izolirane stikalne naprave v kovinskih ohišjih za naznačene napetosti nad 52 kV (IEC 62271-203:2011)

Ta del standarda IEC 62271 določa zahteve za plinsko izolirane stikalne naprave v kovinskih ohišjih, ki so vsaj delno izolirane z izolirnim plinom, drugačnim od zraka pri atmosferskem tlaku, za izmenični tok naznačenih napetosti nad 52 kV za notranjo ali zunanjo namestitev in za frekvence delovanja do vključno 60 Hz. Za namene tega standarda se za »plinsko izolirane stikalne naprave v kovinskih ohišjih« uporabljajta izraza »plinsko izolirane stikalne naprave (GIS)« in »stikalne naprave«. Plinsko izolirane stikalne naprave v kovinskih ohišjih, zajete v tem standardu, so sestavljene iz posameznih komponent, ki se neposredno medsebojno povežejo in lahko delujejo le na ta način. Ta standard po potrebi dopolnjuje in spreminja različne ustrezne standarde, ki veljajo za posamezne komponente plinsko izoliranih stikalnih naprav.

General Information

Status
Published
Publication Date
20-May-2012
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
16-May-2012
Due Date
21-Jul-2012
Completion Date
21-May-2012

Relations

Buy Standard

Standard
EN 62271-203:2012
English language
82 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 62271-203:2012
01-julij-2012
1DGRPHãþD
SIST EN 62271-203:2004
9LVRNRQDSHWRVWQHVWLNDOQHLQNUPLOQHQDSUDYHGHO3OLQVNRL]ROLUDQHVWLNDOQH
QDSUDYHYNRYLQVNLKRKLãMLK]DQD]QDþHQHQDSHWRVWLQDGN9 ,(&

High-voltage switchgear and controlgear - Part 203: Gas-insulated metal-enclosed
switchgear for rated voltages above 52 kV (IEC 62271-203:2011)
Hochspannungs-Schaltgeräte und -Schaltanlagen - Teil 203: Gasisolierte
metallgekapselte Schaltanlagen für Bemessungsspannungen über 52 kV (IEC 62271-
203:2011)
Appareillage à haute tension - Partie 203: Appareillage sous enveloppe métallique à
isolation gazeuse de tensions assignées supérieures à 52 kV (CEI 62271-203:2011)
Ta slovenski standard je istoveten z: EN 62271-203:2012
ICS:
29.130.10 Visokonapetostne stikalne in High voltage switchgear and
krmilne naprave controlgear
SIST EN 62271-203:2012 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 62271-203:2012

---------------------- Page: 2 ----------------------

SIST EN 62271-203:2012

EUROPEAN STANDARD
EN 62271-203

NORME EUROPÉENNE
May 2012
EUROPÄISCHE NORM

ICS 29.130.10 Supersedes EN 62271-203:2004


English version


High-voltage switchgear and controlgear -
Part 203: Gas-insulated metal-enclosed switchgear for rated voltages
above 52 kV
(IEC 62271-203:2011)


Appareillage à haute tension -  Hochspannungs-Schaltgeräte und -
Partie 203: Appareillage sous enveloppe Schaltanlagen -
métallique à isolation gazeuse de tensions Teil 203: Gasisolierte metallgekapselte
assignées supérieures à 52 kV Schaltanlagen für
(CEI 62271-203:2011) Bemessungsspannungen über 52 kV
(IEC 62271-203:2011)





This European Standard was approved by CENELEC on 2011-10-12. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the CEN-CENELEC Management Centre or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the CEN-CENELEC Management Centre has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus,
the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy,
Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia,
Spain, Sweden, Switzerland, Turkey and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Management Centre: Avenue Marnix 17, B - 1000 Brussels


© 2012 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 62271-203:2012 E

---------------------- Page: 3 ----------------------

SIST EN 62271-203:2012
EN 62271-203:2012 - 2 -

Foreword
The text of document 17C/512/FDIS, future edition 2 of IEC 62271-203, prepared by SC 17C, "High-
voltage switchgear and controlgear assemblies", of IEC TC 17, "Switchgear and controlgear" was
submitted to the IEC-CENELEC parallel vote and approved by CENELEC as EN 62271-203:2012.

The following dates are fixed:
(dop) 2012-11-11
• latest date by which the document has
to be implemented at national level by
publication of an identical national
standard or by endorsement
• latest date by which the national (dow) 2014-10-12

standards conflicting with the
document have to be withdrawn

This document supersedes EN 62271-203:2004.
EN 62271-203:2012 includes the following significant technical changes with respect to EN 62271-
203:2004:
— adopting the structure and the content to EN 62271-1,
— harmonisation with IEEE C37.122,
— addition of the new Annex F and the new Annex G.
EN 62271-203:2012 should be read in conjunction with EN 62271-1:2008, to which it refers and which is
applicable unless otherwise specified. In order to simplify the indication of corresponding requirements,
the same numbering of clauses and subclauses is used as in EN 62271-1. Amendments to these clauses
and subclauses are given under the same numbering, whilst additional subclauses, are numbered from
101.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC [and/or CEN] shall not be held responsible for identifying any or all such patent
rights.

Endorsement notice
The text of the International Standard IEC 62271-203:2011 was approved by CENELEC as a European
Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standards indicated:
IEC 60038 NOTE  Harmonized as EN 60038.
IEC 60060-1 NOTE  Harmonized as EN 60060-1.
IEC 60071-1:2006 NOTE  Harmonized as EN 60071-1:2006 (not modified).
IEC 61462 NOTE  Harmonized as EN 61462.
IEC 61672-1 NOTE  Harmonized as EN 61672-1.
IEC 61672-2 NOTE  Harmonized as EN 61672-2.
IEC 62155 NOTE  Harmonized as EN 62155.
IEC 62271-207 NOTE  Harmonized as EN 62271-207.

---------------------- Page: 4 ----------------------

SIST EN 62271-203:2012
- 3 - EN 62271-203:2012
Annex ZA
(normative)

Normative references to international publications
with their corresponding European publications

The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies.

NOTE  When an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD
applies.

Publication Year Title EN/HD Year

IEC 60044-1 (mod) 1996 Instrument transformers - EN 60044-1 1999
Part 1: Current transformers


1)
IEC 60044-2 (mod) 1997 Instrument transformers - EN 60044-2 1999
Part 2: Inductive voltage transformers


IEC 60068-2-11 - Environmental testing - EN 60068-2-11 -
Part 2: Tests - Test Ka: Salt mist


IEC 60137 2008 Insulated bushings for alternating voltages EN 60137 2008
above 1 000 V


IEC 60141-1 - Tests on oil-filled and gas-pressure cables - -
and their accessories -
Part 1: Oil-filled, paper- insulated, metal-
shealthed cables and accessories for
alternating voltages up to and including 400
kV


IEC 60270 - High-voltage test techniques - Partial EN 60270 -
discharge measurements


IEC 60376 - Specification of technical grade sulfur EN 60376 -
hexafluoride (SF6) for use in electrical
equipment


IEC 60480 - Guidelines for the checking and treatment of EN 60480 -
sulphur hexafluoride (SF6) taken from
electrical equipment and specification for its
re-use


IEC 60840 - Power cables with extruded insulation and - -
their accessories for rated voltages above 30
kV (Um = 36 kV) up to 150 kV (Um = 170 kV)
- Test methods and requirements


IEC/TS 61639 1996 Direct connection between power - -
transformers and gas-insulated metal-
enclosed switchgear for rated voltages of 72,5
kV and above


IEC 62067 - Power cables with extruded insulation and - -
their accessories for rated voltages above 150
kV (Um = 170 kV) up to 500 kV (Um = 550 kV)
- Test methods and requirements


IEC 62271-1 2007 High-voltage switchgear and controlgear - EN 62271-1 2008
Part 1: Common specifications


IEC 62271-100 2008 High-voltage switchgear and controlgear - EN 62271-100 2009
Part 100: Alternating current circuit-breakers



1)
EN 60044-2 is superseded by EN 61869-3:2011, which is based on IEC 61869-3:2011.

---------------------- Page: 5 ----------------------

SIST EN 62271-203:2012
EN 62271-203:2012 - 4 -
Publication Year Title EN/HD Year

IEC 62271-102 2001 High-voltage switchgear and controlgear - EN 62271-102 2002
+ corr. April 2002 Part 102: Alternating current disconnectors + corr. July 2008
+ corr. February 2005 and earthing switches + corr. March 2005
+ corr. May 2003


IEC 62271-209 2007 High-voltage switchgear and controlgear - EN 62271-209 2007
Part 209: Cable connections for gas-insulated
metal-enclosed switchgear for rated voltages
above 52 kV - Fluid-filled and extruded
insulation cables - Fluid-filled and dry-type
cable-terminations


IEC/TR 62271-303 - High-voltage switchgear and controlgear - CLC/TR 62271-303 -
Part 303: Use and handling of sulphur
hexafluoride (SF6)


ISO 3231 - Paints and varnishes - Determination of EN ISO 3231 -
resistance to humid atmospheres containing
sulphur dioxide

---------------------- Page: 6 ----------------------

SIST EN 62271-203:2012
- 5 - EN 62271-203:2012
Annex ZB
(informative)

A-deviations
A-deviation: National deviation due to regulations, the alteration of which is for the time being outside the
competence of the CENELEC member.
This European Standard does not fall under any Directive of the EU.
In the relevant CEN-CENELEC countries these A-deviations are valid instead of the provisions of the
European Standard until they have been removed.
Article Deviation
5.103.2 Italy (Italian pressure vessel code for electrical switchgear DM 1 December 1980 and DM
10 September 1981 published in Gazzetta Ufficiale della Repubblica Italiana n° 285 dated
16.10.1981)
For metal-enclosed switchgear and controlgear containing gas-filled compartments, the
design pressure is limited to a maximum of 0,5 bar (gauge) and the volume is limited to a
3
maximum of 2 m . Gas filled compartments having a design pressure exceeding 0,5 bar
(gauge) or a volume exceeding 2 m3 shall be designed according to the Italian pressure
vessel code for electrical switchgear.

---------------------- Page: 7 ----------------------

SIST EN 62271-203:2012

---------------------- Page: 8 ----------------------

SIST EN 62271-203:2012
IEC 62271-203
®

Edition 2.0 2011-09
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE


High-voltage switchgear and controlgear –
Part 203: Gas-insulated metal-enclosed switchgear for rated voltages above
52 kV

Appareillage à haute tension –
Partie 203: Appareillage sous enveloppe métallique à isolation gazeuse de
tensions assignées supérieures à 52 kV

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
CODE PRIX XC
ICS 29.130.10 ISBN 978-2-88912-664-4

® Registered trademark of the International Electrotechnical Commission
Marque déposée de la Commission Electrotechnique Internationale

---------------------- Page: 9 ----------------------

SIST EN 62271-203:2012
– 2 – 62271-203  IEC:2011
CONTENTS
FOREWORD . 6
1 General . 8
1.1 Scope . 8
1.2 Normative references . 8
2 Normal and special service conditions . 9
2.1 Normal service conditions . 9
2.2 Special service conditions . 9
3 Terms and definitions . 10
4 Ratings . 12
4.1 Rated voltage (U ) . 13
r
4.2 Rated insulation level . 13
4.3 Rated frequency (f ) . 15
r
4.4 Rated normal current and temperature rise . 15
4.4.1 Rated normal current (I ) . 15
r
4.4.2 Temperature rise . 15
4.5 Rated short-time withstand current (I ) . 15
k
4.6 Rated peak withstand current (I ) . 15
p
4.7 Rated duration of short-circuit (t ) . 15
k
4.8 Rated supply voltage of closing and opening devices and of auxiliary and
control circuits (U ) . 15
a
4.9 Rated supply frequency of closing and opening devices and of auxiliary
circuits . 16
4.10 Rated pressure of compressed gas supply for controlled pressure systems . 16
4.11 Rated filling levels for insulation and/or operation . 16
5 Design and construction . 16
5.1 Requirements for liquids in switchgear and controlgear . 16
5.2 Requirements for gases in switchgear and controlgear . 16
5.3 Earthing of switchgear and controlgear . 16
5.4 Auxiliary and control equipment . 17
5.5 Dependent power operation . 17
5.6 Stored energy operation . 17
5.7 Independent manual or power operation (independent unlatched operation) . 17
5.8 Operation of releases . 17
5.9 Low- and high-pressure interlocking and monitoring devices . 17
5.10 Nameplates . 18
5.11 Interlocking devices . 18
5.12 Position indication. 18
5.13 Degrees of protection by enclosures . 18
5.14 Creepage distances for outdoor insulators . 18
5.15 Gas and vacuum tightness . 19
5.15.1 Controlled pressure systems for gas . 19
5.15.2 Closed pressure systems for gas . 19
5.15.3 Sealed pressure systems . 19
5.16 Liquid tightness . 19
5.17 Fire hazard (flammability) . 19
5.18 Electromagnetic compatibility (EMC) . 19

---------------------- Page: 10 ----------------------

SIST EN 62271-203:2012
62271-203  IEC:2011 – 3 –
5.19 X-Ray emission . 20
5.20 Corrosion . 20
5.101 Pressure coordination . 20
5.102 Internal fault . 21
5.103 Enclosures . 22
5.104 Partitions . 23
5.105 Pressure relief . 25
5.106 Noise . 26
5.107 Interfaces . 26
6 Type tests . 27
6.1 General . 27
6.1.1 Grouping of tests . 27
6.1.2 Information for identification of specimens . 28
6.1.3 Information to be included in type-tests reports . 29
6.2 Dielectric tests . 29
6.2.1 Ambient air conditions during tests . 29
6.2.2 Wet test procedure . 29
6.2.3 Conditions of switchgear and controlgear during dielectric tests. 29
6.2.4 Criteria to pass the test . 29
6.2.5 Application of the test voltage and test conditions . 29
6.2.6 Tests of switchgear and controlgear of U ≤ 245 kV . 30
r
6.2.7 Tests of switchgear and controlgear of rated voltage U >245 kV . 30
r
6.2.8 Artificial pollution tests for outdoor insulators . 31
6.2.9 Partial discharge tests . 31
6.2.10 Dielectric tests on auxiliary and control circuits . 32
6.2.11 Voltage test as condition check . 32
6.3 Radio interference voltage (r.i.v.) test . 32
6.4 Measurement of the resistance of circuits . 32
6.4.1 Main circuit . 32
6.4.2 Auxiliary circuits . 32
6.5 Temperature-rise tests. 32
6.5.1 Conditions of the switchgear and controlgear to be tested . 32
6.5.2 Arrangement of the equipment . 32
6.5.3 Measurement of the temperature and the temperature rise . 33
6.5.4 Ambient air temperature . 33
6.5.5 Temperature-rise test of the auxiliary and control equipment . 33
6.5.6 Interpretation of the temperature-rise tests . 33
6.6 Short-time withstand current and peak withstand current tests. 33
6.6.1 Arrangement of the switchgear and controlgear and of the test circuit . 33
6.6.2 Test current and duration . 33
6.6.3 Behaviour of switchgear and controlgear during test . 33
6.6.4 Conditions of switchgear and controlgear after test. 34
6.7 Verification of the protection . 34
6.7.1 Verification of the IP coding . 34
6.7.2 Verification of the IK coding . 34
6.8 Tightness tests . 34
6.8.1 Controlled pressure systems for gas . 34
6.8.2 Closed pressure systems for gas . 34
6.8.3 Sealed pressure systems . 35

---------------------- Page: 11 ----------------------

SIST EN 62271-203:2012
– 4 – 62271-203  IEC:2011
6.8.4 Liquid tightness tests . 35
6.9 Electromagnetic compatibility tests (EMC) . 35
6.10 Additional tests on auxiliary and control circuits . 35
6.11 X-radiation test procedure for vacuum interrupters . 35
6.101 Verification of making and breaking capacities . 35
6.102 Mechanical and environmental tests. 35
6.103 Proof tests for enclosures . 36
6.104 Pressure test on partitions . 37
6.105 Test under conditions of arcing due to an internal fault . 37
6.106 Insulator tests . 38
6.107 Corrosion test on earthing connections . 38
6.108 Corrosion tests on enclosures . 39
7 Routine tests . 39
7.1 Dielectric test on the main circuit . 39
7.1.101 Power-frequency voltage tests on the main circuit . 40
7.1.102 Partial discharge measurement . 40
7.2 Tests on auxiliary and control circuits . 40
7.3 Measurement of the resistance of the main circuit . 40
7.4 Tightness test . 40
7.5 Design and visual checks. 40
7.101 Pressure tests of enclosures . 40
7.102 Mechanical operation tests . 41
7.103 Tests on auxiliary circuits, equipment and interlocks in the control mechanism . 41
7.104 Pressure test on partitions . 41
8 Guide to the selection of switchgear and controlgear . 41
8.1 Selection of rated values . 41
8.2 Continuous or temporary overload due to changed service conditions . 41
9 Information to be given with enquiries, tenders and orders . 42
9.1 Information with enquiries and orders . 42
9.2 Information with tenders . 42
10 Transport, storage, installation, operation and maintenance . 42
10.1 Conditions during transport, storage and installation . 42
10.2 Installation . 42
10.3 Operation . 47
10.4 Maintenance . 48
11 Safety . 48
12 Influence of the product on the environment . 48
Annex A (normative) Test procedure for dielectric test on three-phase encapsulated
GIS, range II . 49
Annex B (normative) Methods for testing gas-insulated metal-enclosed switchgear
under conditions of arcing due to an internal fault . 50
Annex C (informative) Technical and practical considerations of site testing . 53
Annex D (informative) Calculation of pressure rise due to an internal fault . 58
Annex E (informative) Information to be given with enquiries, tenders and orders . 59
Annex F (informative) Service continuity . 65
Annex G (informative) Insulation levels for GIS with rated voltages higher than 800 kV . 74
Annex H (informative) List of notes concerning certain countries . 75

---------------------- Page: 12 ----------------------

SIST EN 62271-203:2012
62271-203  IEC:2011 – 5 –
Bibliography . 76

Figure 1 – Pressure coordination . 20
Figure 2 – Example of arrangement of enclosures and gas compartments . 25
Figure F.1 – Impact due to the removal of common partition between busbar-
disconnector . 66
Figure F.2 – Impact of GIS partitioning on service continuity . 67
Figure F.3 – Single line diagram with gas partitioning scheme . 67
Figure F.4 – Localisation and isolation . 69
Figure F.5 – Removal of busbar disconnector in SECTION-1 . 69
Figure F.6 – Removal of busbar disconnector in SECTION-3 . 70
Figure F.7 – Extension . 70
Figure F.8 – On-site dielectric test . 71

Table 1 – Reference table of service conditions relevant to GIS . 10
Table 2 – Rated insulation levels for rated voltages for equipment of range I. 14
Table 3 – Rated insulation levels for rated voltages for equipment of range II. 14
Table 4 – Performance criteria .
...