Standard Specification for Field-assembled Anodeless Riser Kits for Use on Outside Diameter Controlled Polyethylene Gas Distribution Pipe and Tubing

ABSTRACT
This specification covers the qualification requirements and test methods for field-assembled anodeless riser kits for use with outside diameter controlled polyethylene gas distribution pipes and tubing in sizes of up to 2 IPS. The anodeless riser kits shall be manufactured in accordance with the specified materials, physical properties, and design, which include the riser casings, moisture seals, threads, bend radius, coatings, welding procedures, and riser adapter to riser casing connections. The riser adapter to riser casing connections shall tested by tensile pull testing.
SCOPE
1.1 This specification covers requirements and test methods for field-assembled anodeless riser kits for use with outside diameter controlled polyethylene gas distribution pipe and tubing in sizes through 2 IPS as specified in specification D2513.
1.2 The test methods described are not intended to be routine quality control tests.
1.3 This specification covers the types of field-assembled anodeless riser kits described in 3.3.2.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and not considered standard.
1.5 The text of this standard references notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures), shall not be considered as requirements of the standard.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and to determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
31-Jan-2012
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM F2509-06(2012) - Standard Specification for Field-assembled Anodeless Riser Kits for Use on Outside Diameter Controlled Polyethylene Gas Distribution Pipe and Tubing
English language
3 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:F2509 −06(Reapproved 2012) An American National Standard
Standard Specification for
Field-assembled Anodeless Riser Kits for Use on Outside
Diameter Controlled Polyethylene Gas Distribution Pipe and
Tubing
This standard is issued under the fixed designation F2509; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope D638 Test Method for Tensile Properties of Plastics
D1600 Terminology forAbbreviatedTerms Relating to Plas-
1.1 This specification covers requirements and test methods
tics
for field-assembled anodeless riser kits for use with outside
D2513 Specification for Polyethylene (PE) Gas Pressure
diameter controlled polyethylene gas distribution pipe and
Pipe, Tubing, and Fittings
tubing in sizes through 2 IPS as specified in specification
F412 Terminology Relating to Plastic Piping Systems
D2513.
F1948 Specification for Metallic Mechanical Fittings for
1.2 The test methods described are not intended to be
Use on Outside Diameter Controlled Thermoplastic Gas
routine quality control tests.
Distribution Pipe and Tubing
1.3 This specification covers the types of field-assembled
2.2 ASME Standards:
anodeless riser kits described in 3.3.2.
ASME Boiler and Pressure Vessel Code
ASME B1.20.1 Pipe Threads, General Purpose (Inch)
1.4 The values stated in inch-pound units are to be regarded
B31.8 Gas Transmission and Distribution Piping Systems
as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only
2.3 Federal Regulations:
and not considered standard.
United States CFR, Title 49, Part 192 Pipeline Safety
Regulations
1.5 The text of this standard references notes and footnotes
which provide explanatory material. These notes and footnotes
2.4 UL Standard:
(excluding those in tables and figures), shall not be considered UL 360 Standard for Liquid-Tight Flexible Steel Conduit
as requirements of the standard.
3. Terminology
1.6 This standard does not purport to address all of the
safety concerns, if any, associated with its use. It is the
3.1 The gas industry terminology used in this specification
responsibility of the user of this standard to establish appro-
is in accordance with ASME B31.8 or the United States CFR,
priate safety and health practices and to determine the
Title 49, Part 192, unless otherwise indicated.
applicability of regulatory limitations prior to use.
3.1.1 pipe—used herein refers to both “pipe” and “tubing”
unless specifically stated otherwise.
2. Referenced Documents
3.1.2 gas—used herein refers to any fuel gas unless specifi-
cally stated otherwise.
2.1 ASTM Standards:
A513 Specification for Electric-Resistance-Welded Carbon
3.2 Definitions—Definitions are in accordance with Termi-
and Alloy Steel Mechanical Tubing
nology F412 unless otherwise specified. Abbreviations are in
A53/A53M Specification for Pipe, Steel, Black and Hot-
accordance with Terminology D1600 unless otherwise speci-
Dipped, Zinc-Coated, Welded and Seamless
fied.
3.3 Definitions:
This specification is under the jurisdiction ofASTM Committee F17 on Plastic
Piping Systems and is the direct responsibility of Subcommittee F17.60 on Gas.
Current edition approved Feb. 1, 2012. Published February 2012. Originally Available from American Society of Mechanical Engineers (ASME), ASME
approved in 2006. Last previous edition approved in 2006 as F2509–06. DOI: International Headquarters, Three Park Ave., New York, NY 10016-5990, http://
10.1520/F2509-06R12. www.asme.org.
2 4
For referenced ASTM standards, visit the ASTM website, www.astm.org, or Available from the Superintendent of Documents, U.S. Government Printing
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Office, Washington, DC 20402.
Standards volume information, refer to the standard’s Document Summary page on Available from Underwriters Laboratories (UL), 2600 N.W. Lake Rd., Camas,
the ASTM website. WA 98607-8542, http://www.ul.com.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
F2509−06 (2012)
3.3.1 anodeless riser, n—a type of mechanical fitting which 4.3 Moisture Seal:
is designed to transport gas from underground polyethylene 4.3.1 The riser casing shall include a bushing or seal at the
piping to above-ground metallic piping. When properly in- point where the PE pipe will enter the casing. This seal shall
stalled,polyethylenepipeisthegascarrierinthebelowground protect the PE pipe from being damaged by the casing end
portionofananodelessriserandisprotectedbyametallicriser during field assembly and resist the entry of moisture into the
casing when it extends above ground level. casing interior after installation.
3.3.2 field-assembled anodeless riser kit, n—A kit contain- 4.4 Specifications outlining the properties of the field-
ing all of the elements required to assemble an anodeless riser
assembled riser kit shall be available from the manufacturer
at the point of installation with the exception of the gas- upon request.
carryingpolyethylenepipe.Itconsistsof,ataminimum,ariser
5. Physical Properties
casing and a riser adapter. These components may be either
integrally combined or include provisions for attachment to
5.1 Thread Requirements:
one another at the point of installation.
5.1.1 AllgascarryingpipethreadsshallcomplywithASME
3.3.3 mechanical fitting, n—a device for making a connec- B1.20.1
tionbetweenpipingcomponentsthatemploysphysicalforceto
5.2 Bend Radius Requirements:
develop a leak-tight seal, produce alignment, and provide
5.2.1 The bend radius of prebent rigid casings shall be such
resistance to pullout caused by axial loads.
that the PE piping can be inserted during field-assembly
3.3.4 riser adapter, n—a type of mechanical fitting used to without causing damage to the PE pipe.
join polyethylene pipe to a metallic piping connection (typi-
5.3 Coatings:
callyapipethread).Riseradaptersaresometimesreferredtoas
5.3.1 Field-assembled riser kit coatings, if any, shall be as
service head adapters.
agreed upon between the buyer and seller.
3.3.5 riser casing, n—the metallic, non-gas carrying portion
5.4 Welding Requirements:
of an anodeless riser that serves as a protective conduit for the
5.4.1 All gas pressure containing factory welding shall
polyethylene pipe. It may be either rigid, flexible, or a
comply with the requirements of the ASME Boiler and
combination of both.
Pressure Vessel Code, Section IX or API 1104.
3.3.6 qualified installation instructions, n—a written
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.