Standard Specification for Standard Metric Sizes of Electrical Conductors

ABSTRACT
This specification prescribes the recommended standard metric sizes of solid round electrical conductors. The standard diameters of metric sizes of wires are preferred numbers calculated in accordance with the conventional mathematical principles. The standard metric size of stranded conductors and equivalent cross-sectional areas shall be designated.
SCOPE
1.1 This specification prescribes the recommended standard metric sizes of solid round electrical conductors.
1.2 This specification prescribes the recommended standard metric size designations of stranded electrical conductors (see Explanatory Note 1).
Note 2--Physical properties, construction requirements, and manufacturing tolerances for specific products should be included in individual product specifications developed in accordance with appropriate sizes in this specification.
1.3 The values stated in inch-pound or SI units are to be regarded separately as standard. Each system shall be used independently of the other. Combining values from the two systems may result in nonconformance with the specification. For conductor sizes designated by AWG or kcmil, the requirements in SI units have been numerically converted from corresponding values, stated or derived, in inch-pound units. For conductor sizes designated by SI units only, the requirements are stated or derived in SI units.

General Information

Status
Historical
Publication Date
09-Mar-2001
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM B682-01 - Standard Specification for Standard Metric Sizes of Electrical Conductors
English language
4 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information 1
Designation: B 682 – 01
Standard Specification for
1
Standard Metric Sizes of Electrical Conductors
This standard is issued under the fixed designation B 682; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
1. Scope 2. Referenced Documents
1.1 This specification prescribes the recommended standard 2.1 ASTM Standards:
metric sizes of solid round electrical conductors. E 29 Practice for Using Significant Digits in Test Data to
2
1.2 This specification prescribes the recommended standard Determine Conformance with Specifications
metric size designations of stranded electrical conductors (see F 205 Test Method for Measuring Diameter of FineWire by
3
Explanatory Note 1). Weighing
2.2 IEC Standards:
NOTE 1—Physical properties, construction requirements, and manufac-
4
IEC 182 Basic Dimensions of Winding Wires
turing tolerances for specific products should be included in individual
IEC 228 Nominal Cross-Sectional Areas and Composition
product specifications developed in accordance with appropriate sizes in
4
this specification. of Conductors of Insulated Cables
2.3 ISO Standards:
1.3 The values stated in inch-pound or SI units are to be
ISO R388 Metric Series for Basic Thickness of Sheet and
regarded separately as standard. Each system shall be used
4
Diameters of Wire
independently of the other. Combining values from the two
systems may result in nonconformance with the specification.
3. Standard Reference Temperature
For conductor sizes designated byAWG or kcmil, the require-
3.1 Forthepurposeofthisspecification,allwiredimensions
ments in SI units have been numerically converted from
and properties shall be considered as occurring at the interna-
corresponding values, stated or derived, in inch-pound units.
tionally standardized reference temperature of 20°C.
For conductor sizes designated by SI units only, the require-
ments are stated or derived in SI units.
1 2
This specification is under the jurisdiction ofASTM Committee B01 on Wires Annual Book of ASTM Standards, Vol 14.02.
3
for Electrical Conductorsand is the direct responsibility of Subcommittee B01.02on Annual Book of ASTM Standards, Vol 10.04.
4
Methods of Test and Sampling Procedure. International Electrotechnical Commission and International Organization for
Current edition approved Mar. 10, 2001. Published May 2001. Originally Standardization documents are available from the American National Standards
published as B 682 – 81. Last previous edition B 682 – 81 (1996). Institute (ANSI), 11 West 42nd St., 13th Floor, New York, NY 10036.
TABLE 1 Standard Metric Diameters and Cross-Sectional Areas of Solid Round Wires at 20°C
Diameter Cross-Sectional Area
A 2 2A A
mm (R 20 Series) in. mm in. kcmil
18.0 0.708 7 254.5 0.394 4 502.2
16.0 0.629 9 201.1 0.311 6 396.8
14.0 0.551 8 153.9 0.238 6 303.8
12.5 0.492 1 122.7 0.190 2 242.2
11.2 0.440 9 98.52 0.152 7 194.4
10.0 0.393 7 78.54 0.121 7 155.0
9.00 0.354 3 63.62 0.098 61 125.6
8.00 0.315 0 50.27 0.077 91 99.2
7.10 0.279 5 39.59 0.061 37 78.14
6.30 0.248 0 31.17 0.048 32 61.52
5.60 0.220 5 24.63 0.038 18 48.61
5.00 0.196 9 19.63 0.030 43 38.75
4.50 0.177 2 15.90 0.024 65 31.39
4.00 0.157 5 12.57 0.019 48 24.80
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
B 682
TABLE 1 Continued
Diameter Cross-Sectional Area
A 2 2A A
mm (R 20 Series) in. mm in. kcmil
3.55 0.139 8 9.898 0.015 34 19.53
3.15 0.124 0 7.793 0.012 08 15.38
2.80 0.110 2 6.158 0.009 54 12.15
2.50 0.098 4 4.909 0.007 61 9.69
2.24 0.088 2 3.941 0.006 11 7.78
2.00 0.078 7 3.142 0.004 87 6.20
1.80 0.070 9 2.545 0.003 94 5.02
1.60 0.063 0 2.011 0.003 12 3.97
1.40 0.055 1 1.539 0.002 39 3.04
1.25 0.049 2 1.227 0.001 90 2.42
1.12 0.044 1 0.985 0.001 53 1.94
1.00 0.039 4 0.785 0.001 22 1.55
0.900 0.035 4 0.636 0.000 986 1.26
0.800 0.031 5 0.503 0.000 779 0.992
0.710 0.028 0 0.396 0.000 614 0.781
0.630 0.024 8 0.312 0.000 483 0.615
0.560 0.022 0 0.246 0.000 382 0.486
0.500 0.019 7 0.196 0.000 304 0.388
0.450 0.017 7 0.159 0.000 247 0.314
0.400 0.015 7 0.126 0.000 195 0.248
0.355 0.014 0 0.099 0 0.000 153 0.195
A
cmil
0.315 0.012 4 0.077 9 0.000 121 154
0.280 0.001 0 0.061 6 0.000 095 4 122
0.250 0.009 8 0.049 1 0.000 076 1 96.9
0.224 0.008 8 0.039 4 0.000 061 1 77.8
0.200 0.007 9 0.031 4 0.000 048 7 62.0
0.180 0.007 1 0.025 4 0.000 039 4 50.2
0.160 0.006 3 0.020 1 0.000 031 2 39.7
0.140 0.005 5 0.015 4 0.000 023 9 30.4
0.125 0.004 9 0.012 3 0.000 019 0 24.2
0.112 0.004 4 0.009 85 0.000 015 3 19.4
0.100 0.003 9 0.007 85 0.000 012
...