Standard Specification for Reinforced Concrete Elliptical Culvert, Storm Drain, and Sewer Pipe

SCOPE
1.1 This specification covers reinforced elliptically shaped concrete pipe to be used for the conveyance of sewage, industrial wastes, storm water, and for the construction of culverts.  
1.2 Pipe designed for placement with the major axis horizontal shall be designated as "Horizontal Elliptical Pipe." Pipe designed for placement with the major axis vertical shall be designated as "Vertical Elliptical Pipe."  
1.3 A complete metric companion to this specification has been developed-C507M; therefore, no metric equivalents are presented in this specification.  
Note 1-This specification is a manufacturing and purchase specification only, and does not include requirements for bedding, backfill, or the relationship between field load condition and the strength classification of pipe. However, experience has shown that the successful performance of this product depends upon the proper selection of the class of pipe, type of bedding and backfill, and care that the installation conforms to the construction specifications. The owner of the reinforced concrete pipe specified herein is cautioned that he must correlate the field requirements with the class of pipe specified and provide inspection at the construction site.

General Information

Status
Historical
Publication Date
09-Jun-2000
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM C507-00 - Standard Specification for Reinforced Concrete Elliptical Culvert, Storm Drain, and Sewer Pipe
English language
8 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

Designation: C 507 – 00
Standard Specification for
Reinforced Concrete Elliptical Culvert, Storm Drain, and
1
Sewer Pipe
This standard is issued under the fixed designation C 507; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the Department of Defense.
4
1. Scope C 150 Specification for Portland Cement
C 309 Specification for Liquid Membrane-Forming Com-
1.1 This specification covers reinforced elliptically shaped
3
pounds for Curing Concrete
concrete pipe to be used for the conveyance of sewage,
C 497 Test Methods for Concrete Pipe, Manhole Sections,
industrial wastes, storm water, and for the construction of
5
or Tile
culverts.
4
C 595 Specification for Blended Hydraulic Cements
1.2 Pipe designed for placement with the major axis hori-
C 618 Specification for Coal Fly Ash and Raw or Calcined
zontal shall be designated as “Horizontal Elliptical Pipe.” Pipe
Natural Pozzolan for Use as a Mineral Admixture in
designed for placement with the major axis vertical shall be
3
Concrete
designated as “Vertical Elliptical Pipe.”
C 822 Terminology Relating to Concrete Pipe and Related
1.3 A complete metric companion to this specification has
5
Products
been developed—C 507M; therefore, no metric equivalents are
C 1116 Specification for Fiber-Reinforced Concrete and
presented in this specification.
3
Shotcrete
NOTE 1—This specification is a manufacturing and purchase specifica-
tion only, and does not include requirements for bedding, backfill, or the
3. Terminology
relationship between field load condition and the strength classification of
3.1 Definitions—For definitions of terms relating to con-
pipe. However, experience has shown that the successful performance of
crete pipe, see Terminology C 822.
this product depends upon the proper selection of the class of pipe, type
of bedding and backfill, and care that the installation conforms to the
4. Classification
construction specifications. The owner of the reinforced concrete pipe
specified herein is cautioned that he must correlate the field requirements
4.1 Pipe manufactured according to this specification shall
with the class of pipe specified and provide inspection at the construction
be of five classes each for horizontal elliptical and vertical
site.
elliptical pipe with identification as follows:
Horizontal Elliptical Pipe Vertical Elliptical Pipe
2. Referenced Documents
Class HE-A Class VE-II
2.1 ASTM Standards:
Class HE-I Class VE-III
Class HE-II Class VE-IV
A 82 Specification for Steel Wire, Plain, for Concrete Re-
Class HE-III Class VE-V
2
inforcement
Class HE-IV Class VE-VI
A 185 Specification for Steel Welded Wire Fabric, Plain, for
2 4.2 The strength requirements for horizontal elliptical pipe
Concrete Reinforcement
are prescribed in Table 1 and for vertical elliptical pipe are
A 496 Specification for Steel Wire, Deformed, for Concrete
2 prescribed in Table 2.
Reinforcement
A 497 Specification for Steel Welded Wire Fabric, De-
5. Basis of Acceptance
2
formed, for Concrete Reinforcement
5.1 Unless otherwise designated by the owner at the time of,
A 615/A 615M Specification for Deformed and Plain
or before, placing an order, two separate and alternative bases
2
Billet-Steel Bars for Concrete Reinforcement
of acceptance shall be permitted as follows:
3
C 33 Specification for Concrete Aggregates
5.1.1 Acceptance on Basis of Plant Load Bearing Tests,
Material Tests, and Inspection of the Complete Product
—Acceptability of the pipe in all sizes and classes produced in
1
This specification is under the jurisdiction of ASTM Committee C13 on
accordance with 7.1 or 7.2 shall be determined by the results of
Concrete Pipe and is the direct responsibility of Subcommittee C13.02 on
the three-edge-bearing tests for either the load to produce a
Reinforced Sewer and Culvert Pipe.
Current edition approved June 10, 2000. Published August 2000. Originally
published as C 507–63T. Last previous edition C 507–99.
2 4
Annual Book of ASTM Standards, Vol 01.04. Annual Book of ASTM Standards, Vol 04.01.
3 5
Annual Book of ASTM Standards, Vol 04.02. Annual Book of ASTM Standards, Vol 04.05.
Copyright © ASTM, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
C 507
A
TABLE 1 Design Requirements for Horizontal Elliptical (HE) Pipe
NOTE 1—The test load in pounds per linear foot equals D-load 3 inside span in feet.
NOTE 2—Single cage reinforcement, providing tension steel at the top, bottom, and springline, shall be permitted instead of double cage reinforcement.
The area of such reinforcement shall be 112 % of the tabulated inner cage area.
NOTE 3—An inner and outer cage plus quadrant mats shall be permitted instead of double cag
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.