Standard Practice for Determining Air Leakage Rates of Aerosol Foam Sealants and Other Construction Joint Fill and Insulation Materials

SIGNIFICANCE AND USE
5.1 This practice is intended to measure air flow through materials used to fill joints found in building construction.  
5.2 This practice does not purport to establish all required criteria for the selection of an air barrier assembly. Therefore, the results should be used only for comparison purposes and should not be seen as the equivalent to field installed building systems.
SCOPE
1.1 This practice is intended to determine the air leakage rate of aerosol foam sealants as measured in a standardized jig. This practice provides a procedure for preparing the test apparatus and further describes the application of aerosol foam sealant and other joint fillers to the apparatus prior to conducting Test Method E283.  
1.2 This practice allows testing laboratories to quantify the air leakage rate of aerosol foam sealants or joint filling products using Test Method E283 and reporting the data in L/(s · m2) according to Practice E29.  
1.3 This practice is used in conjunction with Test Method E283. Although Test Method E283 is a laboratory test method used with fenestration products, individuals interested in performing field air leakage tests on installed units should reference Test Method E783 and AAMA 502.  
1.4 Aerosol foam sealants are used for a variety of end use applications generally intended to reduce air leakage in the building envelope.  
1.5 Insulating type materials also will be found suitable for evaluation with this practice.  
1.6 There are no other known practices or test methods that specify the preparation of the assemblies used to determine the air leakage rate of gap filling sealants, dry preformed foams or insulations.  
1.7 The values stated in SI units are to be regarded as standard. The values given in parentheses after SI units are provided for information only and are not considered standard.  
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

General Information

Status
Published
Publication Date
31-Jul-2020
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM C1642-20 - Standard Practice for Determining Air Leakage Rates of Aerosol Foam Sealants and Other Construction Joint Fill and Insulation Materials
English language
7 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM C1642-20 - Standard Practice for Determining Air Leakage Rates of Aerosol Foam Sealants and Other Construction Joint Fill and Insulation Materials
English language
7 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
Designation: C1642 − 20
Standard Practice for
Determining Air Leakage Rates of Aerosol Foam Sealants
1
and Other Construction Joint Fill and Insulation Materials
This standard is issued under the fixed designation C1642; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope* 1.9 This international standard was developed in accor-
dance with internationally recognized principles on standard-
1.1 This practice is intended to determine the air leakage
ization established in the Decision on Principles for the
rate of aerosol foam sealants as measured in a standardized jig.
Development of International Standards, Guides and Recom-
This practice provides a procedure for preparing the test
mendations issued by the World Trade Organization Technical
apparatus and further describes the application of aerosol foam
Barriers to Trade (TBT) Committee.
sealant and other joint fillers to the apparatus prior to conduct-
ing Test Method E283.
2. Referenced Documents
1.2 This practice allows testing laboratories to quantify the 2
2.1 ASTM Standards:
air leakage rate of aerosol foam sealants or joint filling
C717 Terminology of Building Seals and Sealants
products using Test Method E283 and reporting the data in
C1330 Specification for Cylindrical Sealant Backing for Use
2
L/(s · m ) according to Practice E29.
with Cold Liquid-Applied Sealants
1.3 This practice is used in conjunction with Test Method
C1620 Specification for Aerosol Polyurethane and Aerosol
E283. Although Test Method E283 is a laboratory test method Latex Foam Sealants
used with fenestration products, individuals interested in per-
E29 Practice for Using Significant Digits in Test Data to
forming field air leakage tests on installed units should Determine Conformance with Specifications
reference Test Method E783 and AAMA 502.
E283 Test Method for Determining Rate of Air Leakage
Through Exterior Windows, Skylights, Curtain Walls, and
1.4 Aerosol foam sealants are used for a variety of end use
Doors Under Specified Pressure Differences Across the
applications generally intended to reduce air leakage in the
Specimen
building envelope.
E631 Terminology of Building Constructions
1.5 Insulating type materials also will be found suitable for
E783 Test Method for Field Measurement of Air Leakage
evaluation with this practice.
Through Installed Exterior Windows and Doors
1.6 There are no other known practices or test methods that 2.2 Other Standards:
specify the preparation of the assemblies used to determine the
AAMA 502 Voluntary Specification for Field Testing of
3
air leakage rate of gap filling sealants, dry preformed foams or Newly Installed Fenestration Products
insulations.
ISO/IEC 17025 General requirements for the competence of
4
testing and calibration laboratories
1.7 The values stated in SI units are to be regarded as
standard. The values given in parentheses after SI units are
3. Terminology
provided for information only and are not considered standard.
3.1 Definitions: See also Terminology E631.
1.8 This standard does not purport to address all of the
3.1.1 air barrier—the assembly of material(s) used in build-
safety concerns, if any, associated with its use. It is the
ing construction to reduce or retard the uncontrolled passage of
responsibility of the user of this standard to establish appro-
air into and out of the building.
priate safety, health, and environmental practices and deter-
mine the applicability of regulatory limitations prior to use.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
contact ASTM Customer Service at service@astm.org. For Anual Book of ASTM
Standards volume information, refer to the standard’s Document Summary page on
1
This practice is under the jurisdiction of ASTM Committee C24 on Building the ASTM website.
3
Seals and Sealants and is the direct responsibility of Subcommittee C24.61 on Available from American Architectural Manufacturers Association (AAMA),
Aerosol Foam Sealants. 1827 Walden Office Square, Suite 550, Schaumburg, IL 60173-4268, http://
Current edition approved Aug. 1, 2020. Published September 2020. Originally www.aamanet.org.
4
approved in 2007. Last previous edition approved in 2014 as C1642-14. DOI: Available from American National Standards Institute (ANSI), 25 W. 43rd St.,
10.1520/C1642-20. 4th Floor, New York, NY 10036, http://www.ansi.org.
*A Summary of Changes section appears at the end of this standard
Copyright ©
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: C1642 − 14 C1642 − 20
Standard Practice for
Determining Air Leakage Rates of Aerosol Foam Sealants
1
and Other Construction Joint Fill and Insulation Materials
This standard is issued under the fixed designation C1642; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope*
1.1 This practice is intended to determine the air leakage rate of aerosol foam sealants as measured in a standardized jig. This
practice provides a procedure for preparing the test apparatus and further describes the application of aerosol foam sealant and
other joint fillers to the apparatus prior to conducting Test Method E283.
1.2 This practice allows testing laboratories to quantify the air leakage rate of aerosol foam sealants or joint filling products using
2
Test Method E283 and reporting the data in L/(s · m ) according to Practice E29.
1.3 This practice is used in conjunction with Test Method E283. Although Test Method E283 is a laboratory test method used with
fenestration products, individuals interested in performing field air leakage tests on installed units should reference Test Method
E783 and AAMA 502.
1.4 Aerosol foam sealants are used for a variety of end use applications generally intended to reduce air leakage in the building
envelope.
1.5 Insulating type materials also will be found suitable for evaluation with this practice.
1.6 There are no other known practices or test methods that specify the preparation of the assemblies used to determine the air
leakage rate of gap filling sealants, dry preformed foams or insulations.
1.7 The values givenstated in SI units are the to be regarded as standard. The inch-pound unitsvalues given in parentheses are for
information only.after SI units are provided for information only and are not considered standard.
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety safety, health, and healthenvironmental practices and determine the
applicability of regulatory limitations prior to use.
1.9 This international standard was developed in accordance with internationally recognized principles on standardization
established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued
by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
1
This practice is under the jurisdiction of ASTM Committee C24 on Building Seals and Sealants and is the direct responsibility of Subcommittee C24.61 on Aerosol Foam
Sealants.
Current edition approved Sept. 15, 2014Aug. 1, 2020. Published November 2014September 2020. Originally approved in 2007. Last previous edition approved in
20072014 as C1642-07.-14. DOI: 10.1520/C1642-14.10.1520/C1642-20.
*A Summary of Changes section appears at the end of this standard
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
C1642 − 20
2. Referenced Documents
2
2.1 ASTM Standards:
C717 Terminology of Building Seals and Sealants
C1330 Specification for Cylindrical Sealant Backing for Use with Cold Liquid-Applied Sealants
C1536 Test Method for Measuring the Yield for Aerosol Foam Sealants
C1620 Specification for Aerosol Polyurethane and Aerosol Latex Foam Sealants
E29 Practice for Using Significant Digits in Test Data to Determine Conformance with Specifications
E283 Test Method for Determining Rate of Air Leakage Through Exterior Windows, Skylights, Curtain Walls, and Doors Under
Specified Pressure Differences Across the Specimen
E631 Terminology of Building Constructions
E783 Test Method for Field Measurement of Air Leakage Through Installed Exterior Windows and Doors
2.2 Other Standards:
3
AAMA 502 Voluntary Specification for Field Testing of Newly Installed Fenestration Products
4
ISO/IEC 17025 General requirements for the competence of testing and calibration laboratories
3. Terminology
3.1 Definitions: See also Terminology E631.
3.1.1 air barrier—the assembly of material(s) used in building construction to reduce or retard the uncontrolled passage of air into
and out of the building.
3.1.2 exfiltration—air flow direction from building interior toward
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.