Standard Specification for Grout for Masonry

SCOPE
1.1 This specification covers two types of grout, fine and coarse grout, for use in the construction of masonry structures. Grout is specified by (1) proportions or (2) strength requirements.
1.2 The text of this specification references notes and footnotes that provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of this specification.

General Information

Status
Historical
Publication Date
31-Jul-2007
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM C476-07 - Standard Specification for Grout for Masonry
English language
3 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: C 476 – 07
Standard Specification for
1
Grout for Masonry
This standard is issued under the fixed designation C 476; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the Department of Defense.
1. Scope* 3.1.1 Cementitious Materials—Cementitiousmaterialsshall
conform to one of the following specifications:
1.1 This specification covers two types of grout, fine and
3.1.1.1 Portland Cement—Type I, IA, II, IIA, III, and IIIA
coarse grout, for use in the construction of masonry structures.
of Specification C 150.
Grout is specified by (1) proportions or (2) strength require-
3.1.1.2 Blended Cements—Type IS, IS(MS), IS-A, IS-
ments.
A(MS), IP, or IP-A of Specification C 595 or types GU, HE,
1.2 The text of this specification references notes and
MS, or HS of Specification C 1157.
footnotes that provide explanatory material. These notes and
3.1.1.3 Quicklime—SpecificationC5.
footnotes (excluding those in tables and figures) shall not be
3.1.1.4 Hydrated Lime—Type S of Specification C 207.
considered as requirements of this specification.
3.1.1.5 Coal Fly Ash or Raw Calcined Natural Pozzolan—
2. Referenced Documents
Specification C 618. Addition rates shall be in an amount
2
governed by the portland-pozzolan cement category of Speci-
2.1 ASTM Standards:
fication C 595. The grout produced with blends of portland
C5 Specification for Quicklime for Structural Purposes
cement and fly ash or raw calcined natural pozzolan shall have
C 143/C 143M Test Method for Slump of Hydraulic-
the compressive strength specified (4.2.2).
Cement Concrete
3.1.1.6 Granulated Blast Furnace Slag—Specification
C 150 Specification for Portland Cement
C 989.Additionratesshallbeasgovernedbytheportlandblast
C 207 Specification for Hydrated Lime for Masonry Pur-
furnace slag cement category of Specification C 595. Grouts
poses
produced with blends of portland cement and granulated blast
C 260 Specification forAir-EntrainingAdmixtures for Con-
furnace slag shall have the compressive strength specified
crete
(4.2.2).
C 404 Specification for Aggregates for Masonry Grout
3.1.2 Air-Entraining Admixtures—Air-entraining admix-
C 595 Specification for Blended Hydraulic Cements
tures shall conform to Specification C 260.
C 618 Specification for Coal Fly Ash and Raw or Calcined
3.1.3 Aggregates—Aggregates shall conform to Specifica-
Natural Pozzolan for Use in Concrete
tion C 404.
C 989 Specification for Ground Granulated Blast-Furnace
3.1.4 Water—Water shall be clean and potable.
Slag for Use in Concrete and Mortars
3.1.5 Admixtures—Integral waterproofing compounds, ac-
C 1019 Test Method for Sampling and Testing Grout
celerators, or other admixtures not mentioned definitely in the
C 1157 Performance Specification for Hydraulic Cement
specification shall not be used in grout for use in reinforced
3. Materials
masonry without approval from the purchaser.
3.1.6 PumpingAids—Pumpingaidsarepermittedtobeused
3.1 Materials used as ingredients in grout shall conform to
in cases where the brand, quality, and quantity are approved in
the requirements specified in 3.1.1-3.1.8.
writing by the purchaser or are definitely stipulated in the
specification.
3.1.7 Antifreeze Compounds—No antifreeze liquids, salts,
1
This specification is under the jurisdiction of ASTM Committee C12 on
or other substances shall be used in grout to lower the freezing
Mortars and Grouts for Unit Masonry and is the direct responsibility of Subcom-
point.
mittee C12.05 on Grout & Grout Admixtures for Masonry.
3.1.8 Storage of Materials—Cementitious materials and
Current edition approved Aug. 1, 2007. Published August 2007. Originally
approved in 1961. Last previous edition approved in 2002 as C 476 – 02.
aggregates shall be stored in such a manner as to prevent
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
deterioration or intrusion of foreign material or moisture. Any
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
materialthathasbecomeunsuitableforgoodconstructionshall
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website. not be used.
*ASummary of Changes section appears at the end of this standard.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
C476–07
TABLE 1 Grout Proportions by Volume
Type Parts by Volume of Parts by Volume of Aggregate,
Portland Cement or Hydrated Lime or Lime Measured in a Damp, Loose Condition
Blended Cemen
...