Standard Specification for Threaded Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 80

ABSTRACT
This specification covers poly(vinyl chloride) (PVC) threaded Schedule 80 pipe fittings, which are PVC 12454, 12454, 13354, 11443, and 14333. The pipe fittings are intended for use with the distribution of pressurized liquids only, which are chemically compatible with the piping materials. The materials shall conform to the required dimensions and burst pressure limits.
SCOPE
1.1 This specification covers poly(vinyl chloride) (PVC) threaded Schedule 80 pipe fittings. Included are requirements for materials, workmanship, dimensions, and burst pressure. Note 1Threaded CPVC plastic pipe fittings, Schedule 80, which were formerly included in this standard, are now covered by Specification F 437.
1.2 The products covered by this specification are intended for use with the distribution of pressurized liquids only, which are chemically compatible with the piping materials. Due to inherent hazards associated with testing components and systems with compressed air or other compressed gases some manufacturers do not allow pneumatic testing of their products. Consult with specific product/component manufacturers for their specific testing procedures prior to pneumatic testing.Note 2
Pressurized (compressed) air or other compressed gases contain large amounts of stored energy which present serious saftey hazards should a system fail for any reason.
1.3 The text of this specification references notes, footnotes, and appendixes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the specification.
1.4 The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are provided for information only.
The following safety hazards caveat pertains only to the test method portion, Section 7, of this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
28-Feb-2006
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM D2464-06 - Standard Specification for Threaded Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 80
English language
5 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:D2464 −06 AnAmerican National Standard
Standard Specification for
Threaded Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings,
1
Schedule 80
This standard is issued under the fixed designation D2464; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the Department of Defense.
1. Scope 2. Referenced Documents
2
2.1 ASTM Standards:
1.1 This specification covers poly(vinyl chloride) (PVC)
D618 Practice for Conditioning Plastics for Testing
threaded Schedule 80 pipe fittings. Included are requirements
D1599 Test Method for Resistance to Short-Time Hydraulic
for materials, workmanship, dimensions, and burst pressure.
Pressure of Plastic Pipe, Tubing, and Fittings
NOTE 1—Threaded CPVC plastic pipe fittings, Schedule 80, which
D1600 Terminology forAbbreviatedTerms Relating to Plas-
were formerly included in this standard, are now covered by Specification
tics
F437.
D1784 Specification for Rigid Poly(Vinyl Chloride) (PVC)
Compounds and Chlorinated Poly(Vinyl Chloride)
1.2 The products covered by this specification are intended
(CPVC) Compounds
for use with the distribution of pressurized liquids only, which
D2122 Test Method for Determining Dimensions of Ther-
are chemically compatible with the piping materials. Due to
moplastic Pipe and Fittings
inherent hazards associated with testing components and sys-
D2749 Symbols for Dimensions of Plastic Pipe Fittings
tems with compressed air or other compressed gases some
F412 Terminology Relating to Plastic Piping Systems
manufacturersdonotallowpneumatictestingoftheirproducts.
F437 Specification for Threaded Chlorinated Poly(Vinyl
Consult with specific product/component manufacturers for
Chloride) (CPVC) Plastic Pipe Fittings, Schedule 80
their specific testing procedures prior to pneumatic testing.
F1498 Specification forTaper PipeThreads 60° forThermo-
NOTE 2—Pressurized (compressed) air or other compressed gases
plastic Pipe and Fittings
contain large amounts of stored energy which present serious safety
2.2 Federal Standard:
hazards should a system fail for any reason.
3
Fed. Std. No. 123 Marking for Shipment (Civil Agencies)
1.3 The text of this specification references notes, footnotes,
2.3 Military Standard:
and appendixes which provide explanatory material. These
3
MIL-STD-129 Marking for Shipment and Storage
notesandfootnotes(excludingthoseintablesandfigures)shall
2.4 NSF Standard:
not be considered as requirements of the specification.
Standard No. 14 for Plastic Piping Components and Related
4
Materials
1.4 The values stated in inch-pound units are to be regarded
Standard No. 61 for DrinkingWater Systems Components—
as the standard. The values given in parentheses are provided
4
Health Effects
for information only.
3. Terminology
1.5 The following safety hazards caveat pertains only to the
test method portion, Section 7, of this specification. This
3.1 General—Definitions are in accordance with Terminol-
standarddoesnotpurporttoaddressallofthesafetyconcerns,
ogy F412, and abbreviations are in accordance with Terminol-
ifany,associatedwithitsuse.Itistheresponsibilityoftheuser
ogy D1600, unless otherwise indicated. The abbreviation for
of this standard to establish appropriate safety and health
poly(vinyl chloride) plastic is PVC.
practices and determine the applicability of regulatory limita-
tions prior to use.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website.
1 3
This specification is under the jurisdiction ofASTM Committee F17 on Plastic Available from Standardization Documents Order Desk, DODSSP, Bldg. 4,
Piping Systems and is the direct responsibility of Subcommittee F17.10 on Fittings. Section D, 700 Robbins Ave., Philadelphia, PA 19111-5098, http://
Current edition approved March 1, 2006. Published March 2006. Originally dodssp.daps.dla.mil.
ϵ1
4
approved in 1965. Last previous edition approved in 1999 as D2464 – 99 . DOI: Available from NSF International, P.O. Box 130140, 789 N. Dixboro Rd.,Ann
10.1520/D2464-06. Arbor, MI 48113-0140, http://www.nsf.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
D2464−06
4. Classification shown in Table 1, and is not included in the center-to-end or
end-to-end dimensions.
4.1 General—This specification covers threaded Schedule
6.1.2 Fittings Not
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.