Standard Specification for Faced Rigid Cellular Polyisocyanurate Thermal Insulation Board

ABSTRACT
This specification covers the general requirements for faced thermal insulation boards composed of rigid cellular polyisocyanurate surfaced with other materials. This standard is intended to apply to rigid cellular polyurethane-modified polyisocyanurate thermal insulation board products that are commercially acceptable as nonstructural panels useful in building construction. The materials are classified as follows: Types I, II, III, IV, and V. Under Type I are Classes 1 and 2. Under Type II are Classes 1, 2, and 3. Under Type II Class 1 are Grades 1, 2, and 3. Rigid polyisocyanurate thermal insulation boards shall be based upon the reaction of an isocyanate with a polyol, or the reaction of an isocyanate with itself, or both, using a catalyst and blowing agents to form a rigid closed-cell-structured polyisocyanurate foam. The insulation foam core shall be homogeneous and of uniform density. The following test methods shall be performed to conform to the specified requirements: conditioning; thermal resistance; compressive strength; dimensional stability; flexural strength; tensile strength perpendicular to board surface; water absorption; and water vapor transmission.
SCOPE
1.1 This specification covers the general requirements for faced thermal insulation boards composed of rigid cellular polyisocyanurate surfaced with other materials. The insulation boards are intended for use at temperatures between −40 and 200°F (−40 and 93°C). This specification does not cover cryogenic applications. Consult the manufacturer for specific recommendations and properties in cryogenic conditions. For specific applications, the actual temperature limits shall be agreed upon by the manufacturer and the purchaser.  
1.2 This standard is intended to apply to rigid cellular polyurethane-modified polyisocyanurate thermal insulation board products that are commercially acceptable as non-structural panels useful in building construction. The term polyisocyanurate encompasses the term polyurethane. For engineering and design purposes, users should follow specific product information provided by board manufacturers regarding physical properties, system design considerations and installation recommendations.Note 1—See Appendix X1 for guidance on determining wind pressure resistance of panels when required for wall sheathing applications.  
1.3 The use of thermal insulation materials covered by this specification is typically regulated by building codes, or other agencies that address fire performance. Where required, the fire performance of the material shall be addressed through standard fire test methods established by the appropriate governing documents.  
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.Note 2—For conversion to metric units other than those contained in this standard, refer to IEEE/ASTM SI 10.  
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
31-Dec-2013
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM C1289-14 - Standard Specification for Faced Rigid Cellular Polyisocyanurate Thermal Insulation Board
English language
7 pages
sale 15% off
Preview
sale 15% off
Preview
Technical specification
REDLINE ASTM C1289-14 - Standard Specification for Faced Rigid Cellular Polyisocyanurate Thermal Insulation Board
English language
7 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:C1289 −14
StandardSpecification for
Faced Rigid Cellular Polyisocyanurate Thermal Insulation
1
Board
This standard is issued under the fixed designation C1289; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the U.S. Department of Defense.
NOTE 2—For conversion to metric units other than those contained in
1. Scope
this standard, refer to IEEE/ASTM SI 10.
1.1 This specification covers the general requirements for
1.5 This standard does not purport to address all of the
faced thermal insulation boards composed of rigid cellular
safety concerns, if any, associated with its use. It is the
polyisocyanurate surfaced with other materials. The insulation
responsibility of the user of this standard to establish appro-
boards are intended for use at temperatures between−40 and
priate safety and health practices and determine the applica-
200°F (−40 and 93°C). This specification does not cover
bility of regulatory limitations prior to use.
cryogenic applications. Consult the manufacturer for specific
recommendations and properties in cryogenic conditions. For
2. Referenced Documents
specific applications, the actual temperature limits shall be
2.1 The following documents, of the issue in effect on the
agreed upon by the manufacturer and the purchaser.
date of material purchase, form a part of this specification to
1.2 This standard is intended to apply to rigid cellular
the extent specified herein:
polyurethane-modified polyisocyanurate thermal insulation
2
2.2 ASTM Standards:
board products that are commercially acceptable as non-
C168Terminology Relating to Thermal Insulation
structural panels useful in building construction. The term
C177Test Method for Steady-State Heat Flux Measure-
polyisocyanurate encompasses the term polyurethane. For
ments and Thermal Transmission Properties by Means of
engineering and design purposes, users should follow specific
the Guarded-Hot-Plate Apparatus
product information provided by board manufacturers regard-
C203Test Methods for Breaking Load and Flexural Proper-
ing physical properties, system design considerations and
ties of Block-Type Thermal Insulation
installation recommendations.
C208Specification for Cellulosic Fiber Insulating Board
NOTE 1—See Appendix X1 for guidance on determining wind pressure
C209Test Methods for Cellulosic Fiber Insulating Board
resistance of panels when required for wall sheathing applications.
C303Test Method for Dimensions and Density of Pre-
1.3 The use of thermal insulation materials covered by this
formed Block and Board–Type Thermal Insulation
specification is typically regulated by building codes, or other
C390Practice for Sampling and Acceptance of Thermal
agenciesthataddressfireperformance.Whererequired,thefire
Insulation Lots
performance of the material shall be addressed through stan-
C518Test Method for Steady-State Thermal Transmission
dardfiretestmethodsestablishedbytheappropriategoverning
Properties by Means of the Heat Flow Meter Apparatus
documents.
C550Test Method for Measuring Trueness and Squareness
of Rigid Block and Board Thermal Insulation
1.4 Thevaluesstatedininch-poundunitsaretoberegarded
C728Specification for Perlite Thermal Insulation Board
as standard. The values given in parentheses are mathematical
C1045Practice for Calculating Thermal Transmission Prop-
conversions to SI units that are provided for information only
erties Under Steady-State Conditions
and are not considered standard.
C1058Practice for Selecting Temperatures for Evaluating
and Reporting Thermal Properties of Thermal Insulation
1
This specification is under the jurisdiction of ASTM Committee C16 on
Thermal Insulation and is the direct responsibility of Subcommittee C16.22 on
2
Organic and Nonhomogeneous Inorganic Thermal Insulations. For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Current edition approved Jan. 1, 2014. Published January 2014. Originally contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
ε1
approved in 1995. Last previous edition approved in 2013 as C1289–13 . DOI: Standards volume information, refer to the standard’s Document Summary page on
10.1520/C1289-14. the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
C1289−14
C1114Test Method for Steady-State Thermal Transmission 4.1.2.3 Class 3—Faced with uncoated polymer-bonded
Properties by Means of the Thin-HeaterApparatus (With- glass fiber mat f
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
´1
Designation: C1289 − 13 C1289 − 14
Standard Specification for
Faced Rigid Cellular Polyisocyanurate Thermal Insulation
1
Board
This standard is issued under the fixed designation C1289; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the U.S. Department of Defense.
1
ε NOTE—Footnote 6 was editorially corrected in June 2013.
1. Scope
1.1 This specification covers the general requirements for faced thermal insulation boards composed of rigid cellular
polyisocyanurate surfaced with other materials. The insulation boards are intended for use at temperatures between −40 and 200°F
(−40 and 93°C). This specification does not cover cryogenic applications. Consult the manufacturer for specific recommendations
and properties in cryogenic conditions. For specific applications, the actual temperature limits shall be agreed upon by the
manufacturer and the purchaser.
1.2 This standard is intended to apply to rigid cellular polyurethane-modified polyisocyanurate thermal insulation board
products that are commercially acceptable as non-structural panels useful in building construction. The term polyisocyanurate
encompasses the term polyurethane. For engineering and design purposes, users should follow specific product information
provided by board manufacturers regarding physical properties, system design considerations and installation recommendations.
NOTE 1—See Appendix X1 for guidance on determining wind pressure resistance of panels when required for wall sheathing applications.
1.3 The use of thermal insulation materials covered by this specification is typically regulated by building codes, or other
agencies that address fire performance. Where required, the fire performance of the material shall be addressed through standard
fire test methods established by the appropriate governing documents.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
NOTE 2—For conversion to metric units other than those contained in this standard, refer to IEEE/ASTM SI 10.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
2. Referenced Documents
2.1 The following documents, of the issue in effect on the date of material purchase, form a part of this specification to the extent
specified herein:
2
2.2 ASTM Standards:
C168 Terminology Relating to Thermal Insulation
C177 Test Method for Steady-State Heat Flux Measurements and Thermal Transmission Properties by Means of the
Guarded-Hot-Plate Apparatus
C203 Test Methods for Breaking Load and Flexural Properties of Block-Type Thermal Insulation
C208 Specification for Cellulosic Fiber Insulating Board
C209 Test Methods for Cellulosic Fiber Insulating Board
C303 Test Method for Dimensions and Density of Preformed Block and Board–Type Thermal Insulation
1
This specification is under the jurisdiction of ASTM Committee C16 on Thermal Insulation and is the direct responsibility of Subcommittee C16.22 on Organic and
Nonhomogeneous Inorganic Thermal Insulations.
Current edition approved May 1, 2013Jan. 1, 2014. Published May 2013January 2014. Originally approved in 1995. Last previous edition approved in 20122013 as
ε1
C1289 – 12a.C1289 – 13 . DOI: 10.1520/C1289-13E01.10.1520/C1289-14.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
C1289 − 14
C390 Practice for Sampling and Acceptance of Thermal Insulation Lots
C518 Test Method for Steady-State Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus
C550 Test Method for Measuring Trueness and Squareness of Rigid Block and Board Thermal Insulatio
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.