Standard Classification for Abuse-Resistant Nondecorated Interior Gypsum Panel Products and Fiber-Reinforced Cement Panels

SIGNIFICANCE AND USE
Each abuse/impact property of abuse resistant wall panels is divided into three classification levels. The three levels of classification are: Level I, Level II, and Level III, with Level I representing the lowest rating for any given property. The test methods specified are utilized to establish the abuse-resistance classification of an abuse resistant wall panel. Each classification level requires a minimum overall specified performance. Any classified abuse resistant wall panel can be used at a classification level which is rated lower than the highest level qualified.
SCOPE
1.1 This standard establishes classifications of abuse resistance based on minimum abuse-resistance performance of nondecorated interior gypsum panel products and fiber-reinforced cement panels (abuse resistant wall panels).
1.2 The values stated in inch-pound and SI (metric) units are to be regarded separately as standard. Within the text, the SI units are shown in brackets. The values stated in each system shall be used independent of the other. Values from the two systems shall not be combined.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
31-Oct-2006
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM C1629/C1629M-06 - Standard Classification for Abuse-Resistant Nondecorated Interior Gypsum Panel Products and Fiber-Reinforced Cement Panels
English language
7 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: C1629/C1629M – 06
Standard Classification for
Abuse-Resistant Nondecorated Interior Gypsum Panel
1
Products and Fiber-Reinforced Cement Panels
This standard is issued under the fixed designation C1629/C1629M; the number immediately following the designation indicates the
year of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last
reapproval. A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope* ISO6707-1 BuildingandCivilEngineering--Vocabulary--
Part 1: General Terms
1.1 This standard establishes classifications of abuse resis-
tance based on minimum abuse-resistance performance of
3. Terminology
nondecorated interior gypsum panel products and fiber-
3.1 Definitions of terms shall be in accordance with Termi-
reinforced cement panels (abuse resistant wall panels).
nologies C11 and C1154.
1.2 Thevaluesstatedininch-poundandSI(metric)unitsare
3.2 Definitions of Terms Specific to This Standard:
to be regarded separately as standard. Within the text, the SI
3.2.1 failure (hard body impact), n—test result constituted
units are shown in brackets. The values stated in each system
either by the penetration of the wall cavity by the impacting
shall be used independent of the other. Values from the two
head of the impacting arm or the denting of the panel resulting
systems shall not be combined.
in an indentation of a depth that exceeds the thickness of the
1.3 This standard does not purport to address all of the
test panel.
safety concerns, if any, associated with its use. It is the
3.2.1.1 Discussion—Depth of the indentation on the test
responsibility of the user of this standard to establish appro-
panel is measured from the face side.
priate safety and health practices and determine the applica-
3.2.2 failure (soft body impact), n—a test result constituted
bility of regulatory limitations prior to use.
either by the breaking of the wall cavity by the soft body
2. Referenced Documents impactor or the residual deflection of any area on the test panel
2
that exceeds the thickness of the test panel.
2.1 ASTM Standards:
3.2.2.1 Discussion—Deformation of the test panel in the
C11 TerminologyRelatingtoGypsumandRelatedBuilding
form of residual deflection is measured from the face side.
Materials and Systems
3.2.2.2 deformation, n—change of shape or dimension or
C1154 Terminology for Non-Asbestos Fiber-Reinforced
both. ISO 6707-1
Cement Products
3.2.2.3 surface damage, n—pulverization of the core of the
D4977 Test Method for Granule Adhesion to Mineral Sur-
test panel at the point of impact, which is evidenced by
faced Roofing by Abrasion
cracking, creasing, or other visible damage short of failure as
D5420 Test Method for Impact Resistance of Flat, Rigid
defined in 3.2.2.
Plastic Specimen by Means of a Striker Impacted by a
3.2.3 residual deflection, n—permanent deformation of a
Falling Weight (Gardner Impact)
building element, component, or structure after removal of
E695 Test Method of Measuring Relative Resistance of
applied force.
Wall, Floor, and Roof Construction to Impact Loading
3.2.3.1 Discussion—Also called permanent set or residual
2.2 ISO Documents:
deformation.
1
4. Significance and Use
This classification is under the jurisdiction of ASTM Committee C11 on
Gypsum and Related Building Materials and Systems and is the direct responsibility
4.1 Each abuse/impact property of abuse resistant wall
of Subcommittee C11.01 on Specifications and Test Methods for Gypsum Products.
panels is divided into three classification levels. The three
Current edition approved Nov. 1, 2006. Published November 2006. Originally
approved in 2005. Last previous edition approved in 2005 as C1629/C1629M – 05.
levelsofclassificationare:LevelI,LevelII,andLevelIII,with
DOI: 10.1520/C1629_C1629M-06.
Level I representing the lowest rating for any given property.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
The test methods specified are utilized to establish the abuse-
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
resistance classification of an abuse resistant wall panel. Each
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website.
*A Summary of Changes section appears at the end of this standard.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
C1629/C1629M – 06
TABLE 2 Performance Requirements
classification level requires a minimum overall specified per-
Indentation Resistance
formance.Any classified abuse resistant wall panel can be used
Indentation
at a classification level which is rated lower than the highest
Classification
Maximum
Level
lev
...