Standard Practice for Infiltration and Exfiltration Acceptance Testing of Installed Precast Concrete Pipe Sewer Lines (Metric)

SCOPE
1.1 This practice covers procedures for testing installed precast concrete pipe sewer lines using either water infiltration or exfiltration acceptance limits to demonstrate the integrity of the installed materials and construction procedure.  
1.2 This practice is the metric counterpart of Practice C969.  Note 1--The owner should specify the following: who will conduct, observe, and furnish labor, furnish material and measuring devices, and pay for the tests; who is responsible for determining local groundwater conditions; and which test is to be conducted, that is, an infiltration test or an exfiltration test.
Note 2--Test criteria presented in this practice are similar to those in general use. Pipe, 600-mm diameter or larger, may be accepted by visual inspection when testing for infiltration.
1.3  This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
31-Dec-1999
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM C969M-94(2000) - Standard Practice for Infiltration and Exfiltration Acceptance Testing of Installed Precast Concrete Pipe Sewer Lines (Metric)
English language
3 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


NOTICE: This standard has either been superseded and replaced by a new version or discontinued.
Contact ASTM International (www.astm.org) for the latest information.
Designation: C 969M – 94 (Reapproved 2000)
METRIC
Standard Practice for
Infiltration and Exfiltration Acceptance Testing of Installed
Precast Concrete Pipe Sewer Lines [Metric]
This standard is issued under the fixed designation C 969M; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
1. Scope 4.3 For the exfiltration test, the sewer line is filled with
water to the recommended test head and the rate of water loss
1.1 This practice covers procedures for testing installed
is determined. If the rate is less than or equal to the allowable
precast concrete pipe sewer lines using either water infiltration
limit, the section of sewer tested is acceptable.
or exfiltration acceptance limits to demonstrate the integrity of
the installed materials and construction procedure.
5. Significance and Use
1.2 This practice is the metric counterpart of Practice C 969.
5.1 This is not a routine test. The values recorded are
NOTE 1—The owner should specify the following: who will conduct,
applicable only to the sewer being tested and at the time of
observe, and furnish labor, furnish material and measuring devices, and
testing.
pay for the tests; who is responsible for determining local groundwater
conditions; and which test is to be conducted, that is, an infiltration test or
6. Preparation of the Sewer Line
an exfiltration test.
6.1 The sewer line should be free of debris prior to testing.
NOTE 2—Test criteria presented in this practice are similar to those in
general use. Pipe, 600-mm diameter or larger, may be accepted by visual 6.2 The manholes, the ends of the branches, laterals, wyes,
inspection when testing for infiltration.
and stubs to be included in the test shall be plugged. All plugs
shall be secured to prevent leakage blowout due to testing
1.3 This standard does not purport to address all of the
pressure.
safety concerns, if any, associated with its use. It is the
responsibility of the user of this standard to establish appro-
7. Procedure
priate safety and health practices and determine the applica-
7.1 Infiltration Testing:
bility of regulatory limitations prior to use.
7.1.1 Conduct testing from manhole to manhole or between
2. Referenced Documents
more than two manholes. The length of main tested shall not
exceed 213 m.
2.1 ASTM Standards:
7.1.2 Stop all dewatering operations and allow the ground-
C 822 Terminology Relating to Concrete Pipe and Related
water to return to its normal level. Infiltration testing should
Products
not be used unless the groundwater level is at least 0.6 m above
3. Terminology
the crown of the pipe for the entire length of the test section.
7.1.3 Plug all pipe outlets discharging into the upstream
3.1 Definitions—For definitions of terms relating to con-
manhole.
crete pipe, see Terminology C 822.
7.1.4 Measure the groundwater elevation and determine the
4. Summary of Practice
average head over the test section.
7.1.5 Measure infiltration leakage at the outlet of the test
4.1 Determine the groundwater conditions surrounding the
section. Because leakage allowances are small, measurements
section of sewer to be tested and select the type of test to be
are best made by either timing the filling of a small container
conducted.
of known volume, or by directing flow into a container for a
4.2 For the infiltration test, the amount of water leaking into
specified time and measuring the content, or by using small
the sewer line is measured, and the rate of infiltration is
weirs.
determined. If the rate is less than or equal to the allowable
7.1.6 If the measured rate of leakage is less than or equal to
limit, the section of sewer tested is acceptable.
the allowable leakage in accordance with 8.1, the section of
sewer tested is acceptable.
This practice is under the jurisdiction of ASTM Committee C13 on Concrete
7.1.7 If the test section tails, it may be repaired and retested
Pipe and is the direct responsibility of Subcommittee C13.09 on Methods of Test.
in accordance with this practice.
Current edition approved July 15, 1994. Published September 1994. Originally
e1 7.2 Exfiltration Testing:
published as C 969M–82. Last previous edition C 969M–82(1990) .
7.2.1 Conduct testing from manhole to manhole or between
Annual Book of ASTM Standards, Vol 04.05.
Copyright © ASTM, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959, United States.
NOTICE: This standard has either been superseded and replaced by a new version or discontinued.
Contact ASTM International (www.astm.org) for the latest information.
C 969M
crown of the pipe at the upstream manhole plus the head above the crown
more than two manholes. The length of main tested shall not
of the pipe at the downstream manhole divided by two.
exceed 213 m.
7.2.2 Determine the groundwater elevation at both ends of
8.1.2 When the average groundwater head on the test
the test section. If the groundwater level is less than 0.6 m
section is greater than 1.8 m, the allowable leakage should be
above the crown of the pipe measured from the highest
increased in proportion to the ratio of the square root of the
elevation of the sewer, the exfiltration test should be used.
average groundwater head to the square root of the base head
7.2.3 Plug all pipe outlets discharging into the upstream
of 1.8 m.
manhole and the test section outlet, and fill the sewer line with
8.1.3 Manholes may be tested separately and independently
water.
with the allowance of 4 L/(m of diameter) (m of head) (h). If
7.2.4 At the upstream manhole, the test head should be
building or house leads are connected to the main line being
established a minimum of 0.6 m ab
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.