ASTM E580/E580M-22
(Practice)Standard Practice for Installation of Ceiling Suspension Systems for Acoustical Tile and Lay-in Panels in Areas Subject to Earthquake Ground Motions
Standard Practice for Installation of Ceiling Suspension Systems for Acoustical Tile and Lay-in Panels in Areas Subject to Earthquake Ground Motions
ABSTRACT
This practice covers acoustical ceiling suspension systems and their additional requirements for application in areas subject to light to moderate seismic disturbance such as Uniform Building Code Seismic Zone 2, the BOCA Basic National Building Code where Av is less than 0.20 but greater than 0.10, and the Standard Building Code (SBC) where Av is less than 0.20 but greater than 0.05. This practice also covers areas subject to moderate to severe seismic disturbance such as Uniform Building Code Seismic Zones 3 and 4, the BOCA Basic National Building Code where Av is greater than 0.20, and the SBC where Av is greater than 0.20. The application of this practice is to be determined by local authorities. Current seismic maps published by recognized authorities such as those previously mentioned, as well as related material such as Open File 82-1033 and MS-812 Seismicity Maps, should be consulted. This practice is not intended to stifle research and development of new products or methods which may simplify the application method specified herein. A variation, however, must be substantiated by verifiable engineering data. A ceiling area of 144 ft2 [13m2] or less, surrounded by walls that connect directly to the structure above shall be exempt from this practice.
SIGNIFICANCE AND USE
3.1 This practice is a prescriptive set of installation methods to be used for suspended ceilings and is often used in lieu of designing a separate lateral restraint system. The authority having jurisdiction shall determine the applicability of this practice to local code requirements.
3.2 This practice covers installation of suspended ceiling systems and related components in areas that require resistance to the effects of earthquake motions as defined by ASCE 7 and the International Building Code.
3.3 The practice is broken into two main sections. The first section covers areas with light to moderate earthquake potential (Seismic Design Category C) while the second deals with severe earthquake potential (Seismic Design Category D, E & F).
3.4 This practice includes requirements from multiple sources including previous versions of this practice, CISCA Seismic Recommendations for Direct-hung Acoustical Tile and Lay-in Ceilings, Seismic Zones 0-2 and CISCA Guidelines for Seismic Restraint for Direct Hung Suspended Ceiling Assemblies, Seismic Zones 3 & 4, suspended ceiling requirements from the International Building Code and ASCE 7. The purpose is to combine the requirements from these sources into a single comprehensive document.
SCOPE
1.1 This practice covers the installation of suspended systems for acoustical tile and lay-in panels and their additional requirements for two groups of buildings that are constructed to resist the effects of earthquake motions as defined by ASCE 7 and the International Building Code. These groupings are for Seismic Design Category C and Seismic Design Categories D, E and F.
1.2 The authority having jurisdiction shall determine the applicability of this practice.
1.3 Test Methods E3090/E3090M, Specification C635, and Practice C636 cover suspension systems, their installation, and testing without special regard to seismic lateral restraint needs. They remain applicable and shall be followed when this practice is specified.
1.4 Ceilings less than or equal to 144 ft2 [13.4 m2] and surrounded by walls connected to the structure above are exempt from the requirements of this practice.
1.5 This practice is not intended to stifle research and development of new products or methods. This practice is not intended to prevent the installation of any material or prohibit any design or method of construction not prescribed in this practice, provided that any such alternative has been substantiated by verifiable engineering data or full-scale dynamic testing that is acceptable to the authority having jurisdiction.
1.6 Ceiling areas of 1000 ft2 [92.9 m2] or less shall be exempt from the...
General Information
Buy Standard
Standards Content (Sample)
This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
Designation: E580/E580M − 22
Standard Practice for
Installation of Ceiling Suspension Systems for Acoustical
Tile and Lay-in Panels in Areas Subject to Earthquake
1
Ground Motions
This standard is issued under the fixed designation E580/E580M; the number immediately following the designation indicates the year
of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval.
A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the U.S. Department of Defense.
1. Scope 1.8 Free floating ceilings (those not attached directly to any
structural walls) supported by chains or cables from the
1.1 This practice covers the installation of suspended sys-
structure are not required to satisfy the seismic force require-
tems for acoustical tile and lay-in panels and their additional
ments provided they meet the following requirements:
requirements for two groups of buildings that are constructed
1.8.1 The design load for such items shall equal 1.4 times
to resist the effects of earthquake motions as defined byASCE
the vertical operating weight.
7 and the International Building Code.These groupings are for
1.8.2 Seismic interaction effects shall be considered in
Seismic Design Category C and Seismic Design Categories D,
accordance with 5.7.
E and F.
1.8.3 The connection to the structure shall allow a 360°
1.2 The authority having jurisdiction shall determine the
range of motion in the horizontal plane.
applicability of this practice.
1.9 The values stated in either inch-pound or SI units are to
1.3 Test Methods E3090/E3090M, Specification C635, and
be regarded as standard.Within the text, the SI units are shown
Practice C636 cover suspension systems, their installation, and
in brackets. The values stated in each system are not exact
testing without special regard to seismic lateral restraint needs.
equivalents;therefore,eachsystemshallbeusedindependently
They remain applicable and shall be followed when this
of the other. Combining values from the two systems result in
practice is specified.
nonconformance with the specification.
2 2
1.4 Ceilings less than or equal to 144 ft [13.4 m ] and
1.10 This standard does not purport to address all of the
surrounded by walls connected to the structure above are
safety concerns, if any, associated with its use. It is the
exempt from the requirements of this practice.
responsibility of the user of this standard to establish appro-
priate safety, health, and environmental practices and deter-
1.5 This practice is not intended to stifle research and
mine the applicability of regulatory limitations prior to use.
development of new products or methods. This practice is not
1.11 This international standard was developed in accor-
intended to prevent the installation of any material or prohibit
dance with internationally recognized principles on standard-
any design or method of construction not prescribed in this
ization established in the Decision on Principles for the
practice, provided that any such alternative has been substan-
Development of International Standards, Guides and Recom-
tiated by verifiable engineering data or full-scale dynamic
mendations issued by the World Trade Organization Technical
testing that is acceptable to the authority having jurisdiction.
Barriers to Trade (TBT) Committee.
2 2
1.6 Ceiling areas of 1000 ft [92.9 m ] or less shall be
exempt from the lateral force bracing requirements of 5.2.8.
2. Referenced Documents
1.7 Ceilings constructed of gypsum board which is screw or 2
2.1 ASTM Standards:
nail attached to suspended members that support a ceiling on
C635 Specification for Manufacture, Performance, and Test-
one level extending from wall to wall shall be exempt from the
ing of Metal Suspension Systems for Acoustical Tile and
requirements of this practice.
Lay-in Panel Ceilings
C636 Practice for Installation of Metal Ceiling Suspension
1
This practice is under the jurisdiction of ASTM Committee E33 on Building
and Environmental Acoustics and is the direct responsibility of Subcommittee
2
E33.04 on Application of Acoustical Materials and Systems. For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Current edition approved March 1, 2022. Published April 2022. Originally contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
approved in 1976. Last previous edition approved in 2020 as E580/E580M – 20. Standards volume information, refer to the standard’s Document Summary page on
DOI: 10.1520/E0580_E0580M-22. the ASTM website.
Copyright © ASTM In
...
This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: E580/E580M − 20 E580/E580M − 22
Standard Practice for
Installation of Ceiling Suspension Systems for Acoustical
Tile and Lay-in Panels in Areas Subject to Earthquake
1
Ground Motions
This standard is issued under the fixed designation E580/E580M; the number immediately following the designation indicates the year
of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval.
A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the U.S. Department of Defense.
1. Scope
1.1 This practice covers the installation of suspended systems for acoustical tile and lay-in panels and their additional requirements
for two groups of buildings that are constructed to resist the effects of earthquake motions as defined by ASCE 7 and the
International Building Code. These groupings are for Seismic Design Category C and Seismic Design Categories D, E and F.
1.2 The authority having jurisdiction shall determine the applicability of this practice.
1.3 Test Methods E3090/E3090M, Specification C635, and Practice C636 cover suspension systems, their installation, and testing
without special regard to seismic lateral restraint needs. They remain applicable and shall be followed when this practice is
specified.
2 2
1.4 Ceilings less than or equal to 144 ft [13.4 m ] and surrounded by walls connected to the structure above are exempt from
the requirements of this practice.
1.5 This practice is not intended to stifle research and development of new products or methods. This practice is not intended to
prevent the installation of any material or prohibit any design or method of construction not prescribed in this practice, provided
that any such alternative has been substantiated by verifiable engineering data or full-scale dynamic testing that is acceptable to
the authority having jurisdiction.
2 2
1.6 Ceiling areas of 1000 ft [92.9 m ] or less shall be exempt from the lateral force bracing requirements of 5.2.8.
1.7 Ceilings constructed of gypsum board which is screw or nail attached to suspended members that support a ceiling on one level
extending from wall to wall shall be exempt from the requirements of this practice.
1.8 Free floating ceilings (those not attached directly to any structural walls) supported by chains or cables from the structure are
not required to satisfy the seismic force requirements provided they meet the following requirements:
1.8.1 The design load for such items shall equal 1.4 times the vertical operating weight.
1
This practice is under the jurisdiction of ASTM Committee E33 on Building and Environmental Acoustics and is the direct responsibility of Subcommittee E33.04 on
Application of Acoustical Materials and Systems.
Current edition approved April 1, 2020March 1, 2022. Published April 2020April 2022. Originally approved in 1976. Last previous edition approved in 20172020 as
E580/E580M – 17.E580/E580M – 20. DOI: 10.1520/E0580_E0580M-20.10.1520/E0580_E0580M-22.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1
---------------------- Page: 1 ----------------------
E580/E580M − 22
1.8.2 Seismic interaction effects shall be considered in accordance with 5.7.
1.8.3 The connection to the structure shall allow a 360° range of motion in the horizontal plane.
1.9 The values stated in either inch-pound or SI units are to be regarded as standard. Within the text, the SI units are shown in
brackets. The values stated in each system are not exact equivalents; therefore, each system shall be used independently of the
other. Combining values from the two systems result in nonconformance with the specification.
1.10 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of
regulatory limitations prior to use.
1.11 This international standard was developed in accordance with internationally recognized principles on standardization
established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued
by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
2. Referenced Documents