Standard Specification for Manufacture, Performance, and Testing of Metal Suspension Systems for Acoustical Tile and Lay-in Panel Ceilings

ABSTRACT
This specification covers metal ceiling suspension systems used primarily to support acoustical tile or acoustical lay-in panels. Some suspension systems incorporate locking assembly details that enhance performance by providing some continuity or load transfer capability between adjacent sections of the ceiling grid. The structural classification or grade of ceiling suspension systems shall be determined by the capability of main runners or nailing bars to support a uniformly distributed load. These classifications shall be: light-duty systems; intermediate-duty systems; and heavy-duty systems. The structural classification of ceiling suspension systems shall be based on the load-carrying capacity of the main runners of the structural network. Suspension system structural members shall conform to the following tolerance requirements: metal thickness; straightness; length; overall cross-section dimensions; and section squareness.
SCOPE
1.1 This specification covers metal ceiling suspension systems used primarily to support acoustical tile or acoustical lay-in panels.  
1.2 Some suspension systems incorporate locking assembly details that enhance performance by providing some continuity or load transfer capability between adjacent sections of the ceiling grid. The test methods of Test Methods E3090/E3090M referenced in this specification do not provide the means for making a complete evaluation of continuous beam systems, nor for assessing the continuity contribution to overall system performance. However, the test methods can be used for evaluating primary structural members in conjunction with secondary members that interlock, as well as with those of noninterlocking type.  
1.3 While this specification is applicable to the exterior installation of metal suspension systems, the atmospheric conditions and wind loading require additional design attention to ensure safe implementation. For that reason, a specific review and approval should be solicited from the responsible architect and engineer, or both, for any exterior application of metal suspension systems in the construction of a new building or building modification.  
1.4 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.5 The following safety hazards caveat pertains only to the test methods described in this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.6 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

General Information

Status
Historical
Publication Date
31-Aug-2017
Current Stage
Ref Project

Buy Standard

Technical specification
ASTM C635/C635M-17 - Standard Specification for Manufacture, Performance, and Testing of Metal Suspension Systems for Acoustical Tile and Lay-in Panel Ceilings
English language
6 pages
sale 15% off
Preview
sale 15% off
Preview
Technical specification
REDLINE ASTM C635/C635M-17 - Standard Specification for Manufacture, Performance, and Testing of Metal Suspension Systems for Acoustical Tile and Lay-in Panel Ceilings
English language
6 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:C635/C635M −17
Standard Specification for
Manufacture, Performance, and Testing of Metal Suspension
1
Systems for Acoustical Tile and Lay-in Panel Ceilings
This standard is issued under the fixed designation C635/C635M; the number immediately following the designation indicates the year
of original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.
A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope mental practices and determine the applicability of regulatory
limitations prior to use.
1.1 This specification covers metal ceiling suspension sys-
1.6 This international standard was developed in accor-
tems used primarily to support acoustical tile or acoustical
dance with internationally recognized principles on standard-
lay-in panels.
ization established in the Decision on Principles for the
1.2 Some suspension systems incorporate locking assembly
Development of International Standards, Guides and Recom-
detailsthatenhanceperformancebyprovidingsomecontinuity
mendations issued by the World Trade Organization Technical
or load transfer capability between adjacent sections of the
Barriers to Trade (TBT) Committee.
ceilinggrid.ThetestmethodsofTestMethodsE3090/E3090M
2. Referenced Documents
referenced in this specification do not provide the means for
2
makingacompleteevaluationofcontinuousbeamsystems,nor
2.1 ASTM Standards:
for assessing the continuity contribution to overall system
B117 Practice for Operating Salt Spray (Fog) Apparatus
performance. However, the test methods can be used for
D1735 Practice for Testing Water Resistance of Coatings
evaluating primary structural members in conjunction with
Using Water Fog Apparatus
secondary members that interlock, as well as with those of
E3090/E3090M Test Methods for Strength Properties of
noninterlocking type.
Metal Ceiling Suspension Systems
1.3 While this specification is applicable to the exterior
3. Terminology
installation of metal suspension systems, the atmospheric
3.1 Where these terms appear in this specification they shall
conditionsandwindloadingrequireadditionaldesignattention
have the meaning herein indicated as follows:
to ensure safe implementation. For that reason, a specific
review and approval should be solicited from the responsible
3.2 Definitions:
architect and engineer, or both, for any exterior application of
3.2.1 backing board, n—a flat sheet of gypsum board to
metalsuspensionsystemsintheconstructionofanewbuilding which acoustical tile is attached using adhesive, screws,
or building modification.
staples, or other suitable means (Fig. 1c).
3.2.2 bow, n—the maximum component of deviation in the
1.4 The values stated in either SI units or inch-pound units
are to be regarded separately as standard. The values stated in vertical plane of a main runner, cross runner, or wall molding
where the centroidal axis of these structural components has
each system may not be exact equivalents; therefore, each
system shall be used independently of the other. Combining been permanently deformed from end to end into the shape of
a simple regular curve during the manufacturing process (Fig.
values from the two systems may result in non-conformance
with the standard. 2).
3.2.2.1 Discussion—The meanings for bow and camber
1.5 The following safety hazards caveat pertains only to the
given here may differ from those applied elsewhere.
test methods described in this specification. This standard does
3.2.3 camber, n—the maximum component of deviation in
not purport to address all of the safety concerns, if any,
the horizontal plane of a main runner, cross runner, or wall
associated with its use. It is the responsibility of the user of this
molding where the centroidal axis of these structural compo-
standard to establish appropriate safety, health, and environ-
nents has been permanently deformed from end to end into the
shape of a simple regular curve during the manufacturing
process (Fig. 2).
1
This specification is under the jurisdiction of ASTM Committee E33 on
Building and Environmental Acoustics and is the direct responsibility of Subcom-
2
mittee E33.04 on Application of Acoustical Materials and Systems. For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Current edition approved Sept. 1, 2017. Published September 2017. Originally contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
approved in 1969. Last previous edition approved in 2013 as C635 – 13a. DOI: Standards volume information, refer to the standard’s Document Summary page on
10.1520/C0635_C0635M-17. the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 -
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: C635/C635M − 13a C635/C635M − 17
Standard Specification for
the Manufacture, Performance, and Testing of Metal
Suspension Systems for Acoustical Tile and Lay-in Panel
1
Ceilings
This standard is issued under the fixed designation C635/C635M; the number immediately following the designation indicates the year
of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval.
A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This specification covers metal ceiling suspension systems used primarily to support acoustical tile or acoustical lay-in
panels.
1.2 Some suspension systems incorporate locking assembly details that enhance performance by providing some continuity or
load transfer capability between adjacent sections of the ceiling grid. The test methods included of Test Methods E3090/E3090M
referenced in this specification do not provide the means for making a complete evaluation of continuous beam systems, nor for
assessing the continuity contribution to overall system performance. However, the test methods can be used for evaluating primary
structural members in conjunction with secondary members that interlock, as well as with those of noninterlocking type.
1.3 While this specification is applicable to the exterior installation of metal suspension systems, the atmospheric conditions and
wind loading require additional design attention to ensure safe implementation. For that reason, a specific review and approval
should be solicited from the responsible architect and engineer, or both, for any exterior application of metal suspension systems
in the construction of a new building or building modification.
1.4 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each
system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the
two systems may result in non-conformance with the standard.
1.5 The following safety hazards caveat pertains only to the test methods described in this specification. This standard does not
purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to
establish appropriate safety safety, health, and healthenvironmental practices and determine the applicability of regulatory
limitations prior to use.
1.6 This international standard was developed in accordance with internationally recognized principles on standardization
established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued
by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
2. Referenced Documents
2
2.1 ASTM Standards:
B117 Practice for Operating Salt Spray (Fog) Apparatus
D1735 Practice for Testing Water Resistance of Coatings Using Water Fog Apparatus
E3090/E3090M Test Methods for Strength Properties of Metal Ceiling Suspension Systems
3. Terminology
3.1 Where these terms appear in this specification they shall have the meaning herein indicated as follows:
3.2 Definitions:
3.1.1 Where these terms appear in this specification they shall have the meaning herein indicated as follows:
1
This specification is under the jurisdiction of ASTM Committee E33 on Building and Environmental Acoustics and is the direct responsibility of Subcommittee E33.04
on Application of Acoustical Materials and Systems.
Current edition approved Sept. 1, 2013Sept. 1, 2017. Published December 2013September 2017. Originally approved in 1969. Last previous edition approved in 2013 as
C635 – 13.C635 – 13a. DOI: 10.1520/C0635_C0635M-13A.10.1520/C0635_C0635M-17.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
C635/C635M − 17
3.1.1.1 backing board—a flat sheet of gypsum board to which acoustical tile is attached using adhesive, screws, staples, or other
suitable means (Fig. 1c).
3.1.1.2 bow—the maximum component of deviation in the vertical plane of a main runner, cross runner, or wall molding where
the centroidal axis of these structu
...