Standard Test Method for Water Penetration of Exterior Metal Roof Panel Systems by Uniform Static Air Pressure Difference

SIGNIFICANCE AND USE
This test method is a standard procedure for determining the resistance to water penetration under uniform positive static air pressure differences, and simulates wind driven rain imposed on sidelaps and rain that is free to drain while building a water head as it flows. The slope of the roof is significant. These factors shall be fully considered prior to specifying the test pressure difference.
Note 1—In applying the results of tests by this method, note that the performance of a roof or its components, or both, may be a function of proper installation and adjustment. In service, the performance also depends on the rigidity of supporting construction, roof slope, and on the resistance of components to deterioration by various causes: corrosive atmosphere, aging, ice, vibration, thermal expansion and contraction, etc. It is difficult to simulate the identical complex wetting conditions that can be encountered in service, including large wind-blown water drops, increasing water drop impact pressures with increasing wind velocity, and lateral or upward moving air and water. Some designs are more sensitive than others to this upward moving water.
Note 2—This is a test procedure. It is the responsibility of the specifying agency to determine the specimen construction, size, and test pressures after considering the method's guidelines. Practical considerations suggest that every combination of panel thickness, span, and design load need not be tested in order to substantiate product performance.
Note 3—This test method shall not, by itself, be relied upon to form conclusions about overall water penetration through metal roofs. A roof contains many details. Although prescribed modifications are outside the scope of this test method, an experienced testing engineer is able to use the principles presented in this test method and generate significant data by isolating specific details and measuring leakage.
SCOPE
1.1 This test method covers the determination of the resistance of exterior metal roof panel systems to water penetration when water is applied to the outdoor face simultaneously with a static air pressure at the outdoor face higher than the pressure at the indoor face, that is, positive pressure. This test method is a specialized adaption of Test Method E331.
1.2 This test method is applicable to any roof area and is intended to measure only the water penetration associated with the field of roof including panel side laps and structural connections. It does not include leakage at openings or perimeter or any other details.
1.3 This test method is limited to specimens in which the side seams and attachments are clearly visible and in which the source of leakage is readily determined. Composite systems in which the source cannot be readily determined are outside the scope of this test method.
1.4 The proper use of this test method requires a knowledge of the principles of pressure and flow measurement.
1.5 The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are for information only and may be approximate.
1.6 The text of this test method references notes and footnotes excluding tables and figures, which provide explanatory material. These notes and footnotes shall not be considered as requirements of the test method.
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific hazard statements, see 7.1.

General Information

Status
Historical
Publication Date
28-Feb-2011
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM E1646-95(2011) - Standard Test Method for Water Penetration of Exterior Metal Roof Panel Systems by Uniform Static Air Pressure Difference
English language
6 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: E1646 − 95 (Reapproved 2011)
Standard Test Method for
Water Penetration of Exterior Metal Roof Panel Systems by
Uniform Static Air Pressure Difference
This standard is issued under the fixed designation E1646; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 2. Referenced Documents
1.1 This test method covers the determination of the resis- 2.1 ASTM Standards:
tance of exterior metal roof panel systems to water penetration
E331 Test Method for Water Penetration of Exterior
when water is applied to the outdoor face simultaneously with Windows, Skylights, Doors, and Curtain Walls by Uni-
a static air pressure at the outdoor face higher than the pressure
form Static Air Pressure Difference
at the indoor face, that is, positive pressure.This test method is
E631 Terminology of Building Constructions
a specialized adaption of Test Method E331.
E1680 Test Method for Rate of Air Leakage through Exte-
rior Metal Roof Panel Systems
1.2 This test method is applicable to any roof area and is
E1592 Test Method for Structural Performance of Sheet
intended to measure only the water penetration associated with
Metal Roof and Siding Systems by Uniform Static Air
the field of roof including panel side laps and structural
Pressure Difference
connections. It does not include leakage at openings or
perimeter or any other details. 2.2 Other Standards:
AAMA 501 Methods of Test for Metal Curtain Walls
1.3 This test method is limited to specimens in which the
side seams and attachments are clearly visible and in which the
3. Terminology
source of leakage is readily determined. Composite systems in
3.1 Definitions—For definitions of general terms relating to
which the source cannot be readily determined are outside the
buildingconstructionusedinthistestmethod,seeTerminology
scope of this test method.
E631.
1.4 The proper use of this test method requires a knowledge
3.2 Definitions of Terms Specific to This Standard:
of the principles of pressure and flow measurement.
3.2.1 specimen—the entire assembled unit submitted for test
1.5 The values stated in inch-pound units are to be regarded
as described in Section 8.
as the standard. The values given in parentheses are for
3.2.2 test pressure difference—the specified difference in
information only and may be approximate.
static air pressure across the assembled and fixed specimen
1.6 The text of this test method references notes and
expressed as pounds-force per square foot (newtons per square
footnotes excluding tables and figures, which provide explana-
metre (pascals)).
tory material. These notes and footnotes shall not be consid-
3.2.3 water leakage—penetration of water onto the exposed
ered as requirements of the test method.
inside surface of the test specimen under specified conditions
1.7 This standard does not purport to address all of the
of air pressure difference across the specimen during a 15-min
safety concerns, if any, associated with its use. It is the
test period. Water penetration at or around end dams or side
responsibility of the user of this standard to establish appro-
rails is not leakage; end dams and side rails are installed to
priate safety and health practices and determine the applica-
cause and control ponding over the panels and to support the
bility of regulatory limitations prior to use. For specific hazard
panels. They are not part of the roof.
statements, see 7.1.
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
This test method is under the jurisdiction of ASTM Committee E06 on contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Performance of Buildings and is the direct responsibility of Subcommittee E06.57 Standards volume information, refer to the standard’s Document Summary page on
on Performance of Metal Roof Systems. the ASTM website.
Current edition approved March 1, 2011. Published March 2011. Originally Available from Architectural Aluminum Manufacturers Association (AAMA),
approved in 1995. Last previous edition approved in 2003 as E1646 – 95 (2003). 1827 Walden Office Square, Suite 550, Schaumburg, IL 60173, http://
DOI: 10.1520/E1646-95R11. www.aamanet.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
E1646 − 95 (2011)
devices described in 8.3 are required to control ponding. Chamber run-off
4. Summary of Test Method
that drains onto the specimen is not allowed so that the accuracy and
4.1 This test method consists of sealing and fixing the test
uniformityofthemeteredflowratedescribedin 6.2.4isnotcompromised.
specimen into or against one face of a test chamber, supplying
6.2.2 Air System—A controllable blower, compressed air
air to or exhausting air from the chamber at the rate required to
supply, exhaust system, or reversible blower designed to
maintainthetestpressuredifferenceacrossthespecimen,while
provide the required maximum air-pressure difference across
spraying water onto the outdoor face of the specimen at the
the specimen. The system must provide essentially constant
required rate and observing any water leakage.
airflow at a fixed pressure for the required test period and be
capable of maintaining positive and negative pressures.
5. Significance and Use
6.2.3 Pressure-Measuring Apparatus—A device to measure
5.1 Thistestmethodisastandardprocedurefordetermining
the test pressure difference within a tolerance of 62 %. The
theresistancetowaterpenetrationunderuniformpositivestatic
device must measure positive and negative pressures.
air pressure differences, and simulates wind driven rain im-
6.2.4 Water-Spray System—The water-spray system shall
posed on sidelaps and rain that is free to drain while building
deliver water uniformly against the exterior surface of the test
a water head as it flows. The slope of the roof is significant. 2
specimen at a minimum rate of 5.0 U.S. gal/ft per h or 8 in./h
These factors shall be fully considered prior to specifying the 2
(3.4 L/m per min).
test pressure difference.
6.2.4.1 The water-spray system shall have nozzles spaced
on a uniform grid, located at a uniform distance approximately
NOTE 1—In applying the results of tests by this method, note that the
performance of a roof or its components, or both, may be a function of
12 in. (0.3 m) above the test specimen, and be adjustable to
proper installation and adjustment. In service, the performance also
provide the specified quantity of water in such a manner as to
depends on the rigidity of supporting construction, roof slope, and on the
wet the test specimen uniformly and to wet those areas
resistance of components to deterioration by various causes: corrosive
vulnerable to water leakage. The spray must be directed at all
atmosphere, aging, ice, vibration, thermal expansion and contraction, etc.
It is difficult to simulate the identical complex wetting conditions that can overlapping side seams with the stream centerline approxi-
be encountered in service, including large wind-blown water drops,
mately 20° off vertical (see Fig. 1). If additional nozzles are
increasing water drop impact pressures with increasing wind velocity, and
required to provide uniformity of water spray at the edge of the
lateral or upward moving air and water. Some designs are more sensitive
test specimen, they shall be equally spaced around the entire
than others to this upward moving water.
spray grid.
NOTE 2—This is a test procedure. It is the responsibility of the
specifying agency to determine the specimen construction, size, and test
7. Hazards
pressures after considering the method’s guidelines. Practical consider-
ations suggest that every combination of panel thickness, span, and design
7.1 Warning—Glass breakage and specimen failure do not
load need not be tested in order to substantiate product performance.
normally occur at the small pressure differences applied in this
NOTE 3—This test method shall not, by itself, be relied upon to form
test. Larger or excessive pressure differences occur during
conclusions about overall water penetration through metal roofs. A roof
preload or due to error in operation or when the apparatus is
contains many details. Although prescribed modifications are outside the
scopeofthistestmethod,anexperiencedtestingengineerisabletousethe
used for other purposes such as structural testing; therefore,
principles presented in this test method and generate significant data by
exercise adequate precautions to protect personnel.
isolating specific details and measuring leakage.
8. Test Specimen
6. Apparatus
8.1 Roof test specimens shall be of sufficient size to
6.1 The description of apparatus in this section is general in
determine the performance of all typical parts of the roof
nature, and any arrangement of equipment capable of perform-
system. For roofs constructed with prefabricated or preformed
ing the test procedure within the allowable tolerances is
units or panels, the specimen width shall be equivalent to or
permitted.
greater than the width of three typical units plus the side rail
6.2 Major Components (see Fig. 1): supporting elements at each edge. The specimen shall contain
at least three assembled side lap seams; this allows partial
6.2.1 Test Chamber—A test chamber or box with either an
opening, a removable mounting panel, or one open face in width units. The specimen width shall be sufficient to provide
loading on at least one typical unit (see Fig. 1). The specimen
which or against which the specimen is installed and sealed.
The specimen shall be installed horizontally. Chamber design shall be of sufficient length to develop a multispan condition
unless the panel is used only in single span applications. If two
shall not allow run-off from the test chamber to drain onto the
test specimen.At least one static pressure tap shall be provided spans are used, they shall be unequal, with the shorter being
75 % of the longer. One panel end lap is optional but shall not
to measure the chamber pressure and shall be so located that
the reading is unaffected by the velocity of the air supply to or be used if the test will be run in tandem with Test Method
E1680. However, one end lap is allowed if the specifying
from the chamber. The air supply opening into the chamber
shall be arranged so that the air does not impinge directly on authority adopts the option at Test Method E1680.
the test specimen with any significant velocity. When required,
NOTE 5—The unbalanced span criterion more closely simulates multi-
a means of access shall be provided into the chamber to
span panel deflection curvature. This works the panel sidelap while
facilitate adjustments and observations after the specimen has minimizing specimen length.
been installed.
8.1.1 All parts of the roof test specimen shall be full size,
using the same materials, details, and methods of construction
NOTE 4—Uniform ponding is essential to this test method—refer to 5.1.
For this reason the specimen slope must be horizontal, and the overflow and anchorage as used on actual buildings.
E1646 − 95 (2011)
FIG. 1 General Arrangement of Water Leakage Apparatus Positive Chamber System
E1646 − 95 (2011)
8.1.2 Condition of structural support shall be simulated as shall be captured separately. A spray that provides at least 20
accurately as possible. If the roof system accommodates gal/h (1.26 L/min) total for the four areas and not less than 4
thermal expansion parallel to the panel, this detail must be gal/h (0.25 L/min) nor more than 10 gal/h (0.63 L/min) in any
included in the test specimen, and the interior support must be one square shall be acceptable.
able to slide parallel to the panel or its attachment or both. 9.1.1 The water-spray system shall be calibrated at all
corners and, if no overlapping occurs, at the quarter and
8.2 If insulation is an optional component of the roof
mid-points of the horizontal center line (of the spray system).
system, it shall not be included in the test specimen.
Ifanumberofidentical,contiguous,modularspraysystemsare
8.2.1 If only one specimen is to be tested, the specifying
used, only one module is required to be calibrated. The system
authority determines the selection.
shall be calibrated with the catch boxes at a distance within 62
NOTE 6—It should be recognized that performance is likely to be a
in. (50 mm) of the required test specimen location relative to
function of size, geometry, and stiffness. Therefore, select specimens
the nozzle. Recalibration shall be at intervals necessary in the
covering the range of sizes to be used in a building. In general, the largest
judgment of the testing agency but not longer than 6 months.
size and least stiff of a particular design, type, construction, and configu-
ration should be tested (see Note 2 for related commentary).
10. Information Required
8.3 Overflow devices shall be provided to ensure that water
1 3
ponds at least ⁄2 in. (13 mm) but no more than ⁄4 in. (20 mm)
10.1 The test-pressure difference or differences at which
above the panel bottom between each major flute while the water penetration is to be determined, unless otherwise
specimen is subjected to the specified flow.
specified, shall be 2.86 lbf/ft (137 Pa) for roof applications
less than or equal to 30° from horizontal. Unless otherwise
9. Calibration
specified, this test-pressure shall be 20 % of the positive design
wind pressure but not less than 6.24 lbf/ft (300 Pa) for roof
9.1 The ability of the test apparatus to meet the require-
ments of 6.2.4.1 shall be checked by using a catch box, the applications steeper than 30° from horizontal.The test pressure
shall not exceed 12 lbf/ft (575 Pa).
open face of which shall be located at the position of the face
ofthetestspecimen.ThecalibrationdeviceisillustratedinFig.
NOTE 7—This commentary is included to assist the specifier in the
2. The catch box shall be designed to receive only water
selection of test pressures. This test method is consistent with the default
impingingontheplaneofthetestspecimenfaceandtoexclude
test-pressure in Test Method E331 and the recommendations in AAMA
Methods 501.Thistestmethodconsidersthatalthoughneitheristolerable,
all run-off water from above.The box shall be 24 in. (610 mm)
water penetration at roofs is generally even less acceptable than at walls.
squareanddividedintofourareaseach12in.(305mm)square.
However, for shallow roofs, the test pressure requirement
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.