ABSTRACT
This specification covers the design, construction, and weatherability of structural standing seam steel roof panel systems. It includes performance requirements for the following elements only: panels, concealed panel clips, panel/clip anchorage, and panel joint sealers. Panel material shall be a hot dip metallic coated product in accordance with one of the following commonly used materials: aluminum-, aluminum-zinc alloy-, zinc-, or zinc-5% aluminum alloy metallic-coated sheet steel. The roof system shall be designed for specified design loads and thermal effects without causing seam separation, permanent panel buckling, or weather-tightness loss. Deflection and serviceability shall be accounted for in the panel system for structural integrity. Static and uplift index tests shall be performed to determine the roof's load capacity. Standing seam roof panel systems shall be installed in accordance with the system design requirements.
SCOPE
1.1 This specification covers the design, construction, and weatherability of structural standing seam steel roof panel systems. It includes performance requirements for the following elements only: panels, concealed panel clips, panel/clip anchorage, and panel joint sealers.
Note 1: These systems are used on both low-slope and steep-slope roof applications. They also are used with or without an underlying deck or sheathing.  
1.2 The objective of this specification is to provide for the overall performance of the structural standing seam steel roof panel system as defined in 3.2.6 during its service life in order to provide weather protection, carry the specified design loads, and allow proper access over the roof surface in order to provide for periodic maintenance of equipment by the owner.  
1.3 In addition to structural, the specifier shall evaluate other characteristics beyond the scope of this specification that affect the final choice of roof construction. These include, but are not limited to, functional, legal, insurance, and economic considerations. See Appendix X1 for specifier's checklist.  
1.4 The specification is not intended to exclude products or systems not covered by the referenced documents.  
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.  
1.6 The text of this specification contains notes and footnotes that provide explanatory information and are not requirements of this specification.  
1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Technical specification
    5 pages
    English language

SIGNIFICANCE AND USE
5.1 This test method is a standard procedure for determining water leakage through metal roof panel system sideseams, endlaps, and roof plane penetrations when the roof system is subjected to a specified static water pressure head.
Note 2: In applying the results of tests by this method, note that the performance of a roof or its components or both, is in part a function of proper installation and adjustment. In service, the performance will also depend on the integrity of the supporting construction, roof slope, and on the resistance of components to deterioration by various causes: corrosive atmosphere, aging, ice, vibration, thermal cycling, etc. It is difficult to simulate the identical complex wetting, aging, and other variable conditions that can be encountered in service, including wind-blown ponded water; the effects of temperature and age on sealant performance; differential pressure across the joints due to wind, snow, and ice accumulation; densification and migration; and abrasions within the joint components which may occur during thermal cycling and other weather events. Some joint conditions are more sensitive than others to these factors.  
5.2 This test method will evaluate the resistance of roof panels, sideseams, endlaps, and roof plane penetrations to water submersion. It will not evaluate panel resistance to wind driven rain.
Note 3: See Test Method E1646 for a test which evaluates resistance to wind driven rain.  
5.3 This test method is not a structural adequacy test.  
5.4 This test method is applicable to single skin metal panels, the exterior skin of factory assembled composite panels, and the exterior skin of field assembled composite systems as long as means can be provided to distinguish leakage through the exterior panel sideseams/endlaps and perimeter leakage.
SCOPE
1.1 This laboratory test method covers the determination of the resistance to water penetration of exterior metal roof panel system sideseams, endlaps, and roof plane penetrations when a specified static water pressure head is applied to the outside face of the roof panel.
Note 1: This test method is intended to evaluate water-barrier (not water-shedding) roof system joints and details. These systems are also referred to as hydrostatic roof systems.  
1.2 This test method is limited to specimens in which the sideseams and attachments are clearly visible and in which the source of leakage is readily observable.  
1.3 This test method excludes performance at roof perimeter conditions.  
1.4 This test method is suitable for evaluating leakage at roof plane penetrations such as fasteners, curbs, pipes, and expansion joints under a static water pressure head.  
1.5 The proper use of this test method requires a knowledge of the principles of water pressure.  
1.6 The text of this standard includes notes and footnotes excluding tables and figures, which provide explanatory material. These notes and footnotes shall not be considered as requirements of the standard.  
1.7 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.  
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. For specific precautionary statements, see Section 7.  
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Standard
    4 pages
    English language

SIGNIFICANCE AND USE
5.1 This test method is a standard procedure for determining air leakage characteristics under specified air pressure differences.
Note 1: The air pressure differences acting across a building envelope vary greatly. The slope of the roof and other factors affecting air pressure differences and the implications of the resulting air leakage relative to the environment within buildings are discussed in the literature.4,5,6 These factors shall be considered fully when specifying the test pressure difference to be used.
Note 2: When applying the results of tests by this test method, note that the performance of a roof or its components, or both, may be a function of proper installation and adjustment. The performance in service will also depend on the rigidity of supporting construction, the presence of interior treatments, the roof slope, and the resistance of components to deterioration by various causes: corrosive atmospheres, aging, ice, vibration, thermal expansion, and contraction, etc. It is difficult to simulate the identical complex environmental conditions that can be encountered in service, including rapidly changing pressures due to wind gusting. Some designs are more sensitive than others to these environmental conditions.  
5.2 Rates of air leakage are sometimes used for comparison purposes. The comparisons are not always valid unless the components being tested and compared are of essentially the same size, configuration, and design.
Note 3: The specimen construction discussed in 1.2 and required in 8.1 isolates a source of leakage. The rate of air leakage measured during the test method has units of cubic feet per minute per square foot (litres per second per square metre). Openings and details such as end laps or roof curbs are excluded since leakage is measured more appropriately in cubic feet per minute per foot (litres per second per metre) at these conditions. The test specimen area is relatively small; the inclusion of details will give unrea...
SCOPE
1.1 This test method covers the determination of the resistance of exterior metal roof panel systems to air infiltration resulting from either positive or negative air pressure differences. The test method described is for tests with constant temperature and humidity across the specimen. This test method is a specialized adaption of Test Method E283.  
1.2 This test method is applicable to any roof area. This test method is intended to measure only the air leakage associated with the field of the roof, including the panel side laps and structural connections; it does not include leakage at the openings or perimeter or any other details.  
1.3 The proper use of this test method requires knowledge of the principles of air flow and pressure measurements.  
1.4 The text of this test method references notes and footnotes excluding tables and figures, which provide explanatory material. These notes and footnotes shall not be considered to be requirements of the test method.  
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.  
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. For specific precautionary statements, see Section 7.  
1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Standard
    7 pages
    English language

SIGNIFICANCE AND USE
5.1 This test method is a standard procedure for determining the resistance to water penetration under uniform positive static air pressure differences, and simulates wind driven rain imposed on sidelaps and rain that is free to drain while building a water head as it flows. The slope of the roof is significant. These factors shall be fully considered prior to specifying the test pressure difference.
Note 1: In applying the results of tests by this method, note that the performance of a roof or its components, or both, may be a function of proper installation and adjustment. In service, the performance also depends on the rigidity of supporting construction, roof slope, and on the resistance of components to deterioration by various causes: corrosive atmosphere, aging, ice, vibration, thermal expansion and contraction, etc. It is difficult to simulate the identical complex wetting conditions that can be encountered in service, including large wind-blown water drops, increasing water drop impact pressures with increasing wind velocity, and lateral or upward moving air and water. Some designs are more sensitive than others to this upward moving water.
Note 2: This is a test procedure. It is the responsibility of the specifying agency to determine the specimen construction, size, and test pressures after considering the method’s guidelines. Practical considerations suggest that every combination of panel thickness, span, and design load need not be tested in order to substantiate product performance.
Note 3: This test method shall not, by itself, be relied upon to form conclusions about overall water penetration through metal roofs. A roof contains many details. Although prescribed modifications are outside the scope of this test method, an experienced testing engineer is able to use the principles presented in this test method and generate significant data by isolating specific details and measuring leakage.
SCOPE
1.1 This test method covers the determination of the resistance of exterior metal roof panel systems to water penetration when water is applied to the outdoor face simultaneously with a static air pressure at the outdoor face higher than the pressure at the indoor face, that is, positive pressure. This test method is a specialized adaption of Test Method E331.  
1.2 This test method is applicable to any roof area and is intended to measure only the water penetration associated with the field of roof including panel side laps and structural connections. It does not include leakage at openings or perimeter or any other details.  
1.3 This test method is limited to specimens in which the side seams and attachments are clearly visible and in which the source of leakage is readily determined. Composite systems in which the source cannot be readily determined are outside the scope of this test method.  
1.4 The proper use of this test method requires a knowledge of the principles of pressure and flow measurement.  
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.  
1.6 The text of this test method references notes and footnotes excluding tables and figures, which provide explanatory material. These notes and footnotes shall not be considered as requirements of the test method.  
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. For specific hazard statements, see 7.1.  
1.8 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of Internati...

  • Standard
    6 pages
    English language

ABSTRACT
This specification covers the design, construction, and weatherability of structural standing seam aluminum roof panel systems. It includes performance requirements for the following elements only: panels, concealed panel clips, panel/clip anchorage, and panel joint sealers. Structural panels shall be designed in accordance with the required specifications for aluminum structures and in accordance with sound engineering methods and practices. The static load capacity and uplift index shall be tested to meet the requirements prescribed. Connections of panels to structural members shall be made with concealed panel clips compatible with the panel design. A fixing line is required to anchor roof panels in order to maintain end alignment and to resist in-plane gravity and thermal force components. Panel-to-panel sidelap connections and endlaps shall be weathertight. Panels of maximum practicable lengths shall be used to minimize endlaps.
SCOPE
1.1 This specification covers the design, construction, and weatherability of structural standing seam aluminum roof panel systems. It includes performance requirements for the following elements only: panels, concealed panel clips, panel/clip anchorage, and panel joint sealers.
Note 1: These systems are used on both low-slope and steep-slope roof applications. They also are used with or without an underlying deck or sheathing.  
1.2 The objective of this specification is to provide for the overall performance of the structural standing seam aluminum roof panel system as defined in 3.2.6 during its service life in order to provide weather protection, carry the specified design loads, and allow proper access over the roof surface in order to provide for periodic maintenance of the equipment by the building owner.  
1.3 In addition to structural characteristics, the specifier shall evaluate other characteristics beyond the scope of this specification that affect the final choice of roof construction. These include, but are not limited to, functional, legal, insurance, and economic considerations. See Appendix X1 for the specifier's checklist.  
1.4 This specification is not intended to exclude products or systems not covered by the referenced documents.  
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.  
1.6 The text of this specification contains notes and footnotes that provide explanatory information and are not requirements of this specification.  
1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Technical specification
    5 pages
    English language

SIGNIFICANCE AND USE
5.1 This test method provides a standard procedure to evaluate or confirm structural performance under uniform static air pressure difference. This procedure is intended to represent the effects of uniform loads on exterior building surface elements.  
5.2 It is also permissible to develop data for load-span tables by interpolating between the test results at different spans.
Note 1: When applying the results of tests to determine allowable design loads by application of a factor of safety, bear in mind that the performance of a wall or roof and its components, or both, can be a function of fabrication, installation, and adjustment. The specimen must represent the actual structure closely. In service, the performance can also depend on the rigidity of supporting construction and on the resistance of components to deterioration by various causes, to vibration, to thermal expansion and contraction, and so forth.
SCOPE
1.1 This test method covers the evaluation of the structural performance of sheet metal panels and anchor-to-panel attachments for roof or siding systems under uniform static air pressure differences using a test chamber or support surface.  
1.2 The provisions of this test method are applicable to standing seam, trapezoidal, ribbed, or corrugated metal panels in the range of thickness from 0.012 to 0.050-in. (0.3 to 1.3-mm) and apply to the evaluation of uniform pressure applied to single-skin construction or one sheet metal layer of multiple-skin construction. They do not cover requirements for the construction of a specimen to determine the load sharing that can occur with either composite or multiple-layer construction such as: (1) metal cladding over wood sheathing; or (2) field assemblies of insulation sandwiched between corrugated or formed metal panels.  
1.3 Proper use of this test method requires knowledge of the principles of pressure and deflection measurement.  
1.4 This test method describes optional apparatus and procedures for use in evaluating the structural performance of a given system for a range of support spacings or for confirming the structural performance of a specific installation.  
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.  
1.6 The text of this standard references notes and footnotes exclusive of those for tables and figures. These notes and footnotes provide explanatory material and shall not be considered as requirements of the standard.  
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. For specific precautionary statements, see Section 7.  
1.8 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Standard
    9 pages
    English language

ABSTRACT
This specification covers the design, construction, and weatherability of structural standing seam steel roof panel systems. It includes performance requirements for the following elements only: panels, concealed panel clips, panel/clip anchorage, and panel joint sealers. Panel material shall be a hot dip metallic coated product in accordance with one of the following commonly used materials: aluminum-, aluminum-zinc alloy-, zinc-, or zinc-5% aluminum alloy metallic-coated sheet steel. The roof system shall be designed for specified design loads and thermal effects without causing seam separation, permanent panel buckling, or weather-tightness loss. Deflection and serviceability shall be accounted for in the panel system for structural integrity. Static and uplift index tests shall be performed to determine the roof's load capacity. Standing seam roof panel systems shall be installed in accordance with the system design requirements.
SCOPE
1.1 This specification covers the design, construction, and weatherability of structural standing seam steel roof panel systems. It includes performance requirements for the following elements only: panels, concealed panel clips, panel/clip anchorage, and panel joint sealers.
Note 1: These systems are used on both low-slope and steep-slope roof applications. They also are used with or without an underlying deck or sheathing.  
1.2 The objective of this specification is to provide for the overall performance of the structural standing seam steel roof panel system as defined in 3.2.6 during its service life in order to provide weather protection, carry the specified design loads, and allow proper access over the roof surface in order to provide for periodic maintenance of equipment by the owner.  
1.3 In addition to structural, the specifier shall evaluate other characteristics beyond the scope of this specification that affect the final choice of roof construction. These include, but are not limited to, functional, legal, insurance, and economic considerations. See Appendix X1 for specifier's checklist.  
1.4 The specification is not intended to exclude products or systems not covered by the referenced documents.  
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.  
1.6 The text of this specification contains notes and footnotes that provide explanatory information and are not requirements of this specification.  
1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Technical specification
    5 pages
    English language
  • Technical specification
    5 pages
    English language
  • Technical specification
    5 pages
    English language

SIGNIFICANCE AND USE
5.1 This test method is a standard procedure for determining water leakage through metal roof panel system sideseams, endlaps, and roof plane penetrations when the roof system is subjected to a specified static water pressure head.
Note 2: In applying the results of tests by this method, note that the performance of a roof or its components or both, is in part a function of proper installation and adjustment. In service, the performance will also depend on the integrity of the supporting construction, roof slope, and on the resistance of components to deterioration by various causes: corrosive atmosphere, aging, ice, vibration, thermal cycling, etc. It is difficult to simulate the identical complex wetting, aging, and other variable conditions that can be encountered in service, including wind-blown ponded water; the effects of temperature and age on sealant performance; differential pressure across the joints due to wind, snow, and ice accumulation; densification and migration; and abrasions within the joint components which may occur during thermal cycling and other weather events. Some joint conditions are more sensitive than others to these factors.  
5.2 This test method will evaluate the resistance of roof panels, sideseams, endlaps, and roof plane penetrations to water submersion. It will not evaluate panel resistance to wind driven rain.
Note 3: See Test Method E1646 for a test which evaluates resistance to wind driven rain.  
5.3 This test method is not a structural adequacy test.  
5.4 This test method is applicable to single skin metal panels, the exterior skin of factory assembled composite panels, and the exterior skin of field assembled composite systems as long as means can be provided to distinguish leakage through the exterior panel sideseams/endlaps and perimeter leakage.
SCOPE
1.1 This laboratory test method covers the determination of the resistance to water penetration of exterior metal roof panel system sideseams, endlaps, and roof plane penetrations when a specified static water pressure head is applied to the outside face of the roof panel.
Note 1: This test method is intended to evaluate water-barrier (not water-shedding) roof system joints and details. These systems are also referred to as hydrostatic roof systems.  
1.2 This test method is limited to specimens in which the sideseams and attachments are clearly visible and in which the source of leakage is readily observable.  
1.3 This test method excludes performance at roof perimeter conditions.  
1.4 This test method is suitable for evaluating leakage at roof plane penetrations such as fasteners, curbs, pipes, and expansion joints under a static water pressure head.  
1.5 The proper use of this test method requires a knowledge of the principles of water pressure.  
1.6 The text of this standard includes notes and footnotes excluding tables and figures, which provide explanatory material. These notes and footnotes shall not be considered as requirements of the standard.  
1.7 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.  
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific precautionary statements, see Section 7.  
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Standard
    4 pages
    English language
  • Standard
    4 pages
    English language

SIGNIFICANCE AND USE
5.1 This test method is a standard procedure for determining air leakage characteristics under specified air pressure differences.
Note 1: The air pressure differences acting across a building envelope vary greatly. The slope of the roof and other factors affecting air pressure differences and the implications of the resulting air leakage relative to the environment within buildings are discussed in the literature.4,5,6 These factors shall be considered fully when specifying the test pressure difference to be used.
Note 2: When applying the results of tests by this test method, note that the performance of a roof or its components, or both, may be a function of proper installation and adjustment. The performance in service will also depend on the rigidity of supporting construction, the presence of interior treatments, the roof slope, and the resistance of components to deterioration by various causes: corrosive atmospheres, aging, ice, vibration, thermal expansion, and contraction, etc. It is difficult to simulate the identical complex environmental conditions that can be encountered in service, including rapidly changing pressures due to wind gusting. Some designs are more sensitive than others to these environmental conditions.  
5.2 Rates of air leakage are sometimes used for comparison purposes. The comparisons are not always valid unless the components being tested and compared are of essentially the same size, configuration, and design.
Note 3: The specimen construction discussed in 1.2 and required in 8.1 isolates a source of leakage. The rate of air leakage measured during the test method has units of cubic feet per minute per square foot (litres per second per square metre). Openings and details such as end laps or roof curbs are excluded since leakage is measured more appropriately in cubic feet per minute per foot (litres per second per metre) at these conditions. The test specimen area is relatively small; the inclusion of details will give unrea...
SCOPE
1.1 This test method covers the determination of the resistance of exterior metal roof panel systems to air infiltration resulting from either positive or negative air pressure differences. The test method described is for tests with constant temperature and humidity across the specimen. This test method is a specialized adaption of Test Method E283.  
1.2 This test method is applicable to any roof area. This test method is intended to measure only the air leakage associated with the field of the roof, including the panel side laps and structural connections; it does not include leakage at the openings or perimeter or any other details.  
1.3 The proper use of this test method requires knowledge of the principles of air flow and pressure measurements.  
1.4 The text of this test method references notes and footnotes excluding tables and figures, which provide explanatory material. These notes and footnotes shall not be considered to be requirements of the test method.  
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.  
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific precautionary statements, see Section 7.

  • Standard
    7 pages
    English language
  • Standard
    7 pages
    English language

SIGNIFICANCE AND USE
This test method provides a standard procedure to evaluate or confirm structural performance under uniform static air pressure difference. This procedure is intended to represent the effects of uniform loads on exterior building surface elements.  
It is also permissible to develop data for load-span tables by interpolating between the test results at different spans.  
Note 1—When applying the results of tests to determine allowable design loads by application of a factor of safety, bear in mind that the performance of a wall or roof and its components, or both, can be a function of fabrication, installation, and adjustment. The specimen must represent the actual structure closely. In service, the performance can also depend on the rigidity of supporting construction and on the resistance of components to deterioration by various causes, to vibration, to thermal expansion and contraction, and so forth.
SCOPE
1.1 This test method covers the evaluation of the structural performance of sheet metal panels and anchor-to-panel attachments for roof or siding systems under uniform static air pressure differences using a test chamber or support surface.  
1.2 The provisions of this test method are applicable to standing seam, trapezoidal, ribbed, or corrugated metal panels in the range of thickness from 0.012 to 0.050-in. (0.3 to 1.3-mm) and apply to the evaluation of uniform pressure applied to single-skin construction or one sheet metal layer of multiple-skin construction. They do not cover requirements for the construction of a specimen to determine the load sharing that can occur with either composite or multiple-layer construction such as: (1) metal cladding over wood sheathing; or (2) field assemblies of insulation sandwiched between corrugated or formed metal panels.  
1.3 Proper use of this test method requires knowledge of the principles of pressure and deflection measurement.  
1.4 This test method describes optional apparatus and procedures for use in evaluating the structural performance of a given system for a range of support spacings or for confirming the structural performance of a specific installation.  
1.5 The values stated in inch-pound units are to be regarded as the standard. The metric equivalents of inch-pound units are approximate.  
1.6 The text of this standard references notes and footnotes exclusive of those for tables and figures. These notes and footnotes provide explanatory material and shall not be considered as requirements of the standard.  
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific precautionary statements, see Section 7.

  • Standard
    8 pages
    English language

SIGNIFICANCE AND USE
This test method is a standard procedure for determining air leakage characteristics under specified air pressure differences.
Note 1—The air pressure differences acting across a building envelope vary greatly. The slope of the roof and other factors affecting air pressure differences and the implications of the resulting air leakage relative to the environment within buildings are discussed in the literature. , , These factors shall be considered fully when specifying the test pressure difference to be used.
Note 2—When applying the results of tests by this test method, note that the performance of a roof or its components, or both, may be a function of proper installation and adjustment. The performance in service will also depend on the rigidity of supporting construction, the presence of interior treatments, the roof slope, and the resistance of components to deterioration by various causes: corrosive atmospheres, aging, ice, vibration, thermal expansion, and contraction, etc. It is difficult to simulate the identical complex environmental conditions that can be encountered in service, including rapidly changing pressures due to wind gusting. Some designs are more sensitive than others to these environmental conditions.
Rates of air leakage are sometimes used for comparison purposes. The comparisons are not always valid unless the components being tested and compared are of essentially the same size, configuration, and design.
Note 3—The specimen construction discussed in 1.2 and required in 8.1 isolates a source of leakage. The rate of air leakage measured during the test method has units of cubic feet per minute per square foot (litres per second per square metre). Openings and details such as end laps or roof curbs are excluded since leakage is measured more appropriately in cubic feet per minute per foot (litres per second per metre) at these conditions. The test specimen area is relatively small; the inclusion of details will give unrealistic imp...
SCOPE
1.1 This test method covers the determination of the resistance of exterior metal roof panel systems to air infiltration resulting from either positive or negative air pressure differences. The test method described is for tests with constant temperature and humidity across the specimen. This test method is a specialized adaption of Test Method E283.
1.2 This test method is applicable to any roof area. This test method is intended to measure only the air leakage associated with the field of the roof, including the panel side laps and structural connections; it does not include leakage at the openings or perimeter or any other details.
1.3 The proper use of this test method requires knowledge of the principles of air flow and pressure measurements.
1.4 The text of this test method references notes and footnotes excluding tables and figures, which provide explanatory material. These notes and footnotes shall not be considered to be requirements of the test method.
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific precautionary statements, see Section 7.

  • Standard
    6 pages
    English language
  • Standard
    6 pages
    English language

ABSTRACT
This specification covers the design, construction, and weatherability of structural standing seam aluminum roof panel systems. It includes performance requirements for the following elements only: panels, concealed panel clips, panel/clip anchorage, and panel joint sealers. Structural panels shall be designed in accordance with the required specifications for aluminum structures and in accordance with sound engineering methods and practices. The static load capacity and uplift index shall be tested to meet the requirements prescribed. Connections of panels to structural members shall be made with concealed panel clips compatible with the panel design. A fixing line is required to anchor roof panels in order to maintain end alignment and to resist in-plane gravity and thermal force components. Panel-to-panel sidelap connections and endlaps shall be weathertight. Panels of maximum practicable lengths shall be used to minimize endlaps.
SCOPE
1.1 This specification covers the design, construction, and weatherability of structural standing seam aluminum roof panel systems. It includes performance requirements for the following elements only: panels, concealed panel clips, panel/clip anchorage, and panel joint sealers.  
Note 1—These systems are used on both low-slope and steep-slope roof applications. They also are used with or without an underlying deck or sheathing.  
1.2 The objective of this specification is to provide for the overall performance of the structural standing seam aluminum roof panel system as defined in 3.2.6 during its service life in order to provide weather protection, carry the specified design loads, and allow proper access over the roof surface in order to provide for periodic maintenance of the equipment by the building owner.  
1.3 In addition to structural characteristics, the specifier shall evaluate other characteristics beyond the scope of this specification that affect the final choice of roof construction. These include, but are not limited to, functional, legal, insurance, and economic considerations. See Appendix X1 for the specifier's checklist.  
1.4 This specification is not intended to exclude products or systems not covered by the referenced documents.  
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.6 The text of this specification contains notes and footnotes that provide explanatory information and are not requirements of this specification.

  • Technical specification
    5 pages
    English language

ABSTRACT
This specification covers the design, construction, and weatherability of structural standing seam steel roof panel systems. It includes performance requirements for the following elements only: panels, concealed panel clips, panel/clip anchorage, and panel joint sealers. Panel material shall be a hot dip metallic coated product in accordance with one of the following commonly used materials: aluminum-, aluminum-zinc alloy-, zinc-, or zinc-5% aluminum alloy metallic-coated sheet steel. The roof system shall be designed for specified design loads and thermal effects without causing seam separation, permanent panel buckling, or weather-tightness loss. Deflection and serviceability shall be accounted for in the panel system for structural integrity. Static and uplift index tests shall be performed to determine the roof's load capacity. Standing seam roof panel systems shall be installed in accordance with the system design requirements.
SCOPE
1.1 This specification covers the design, construction, and weatherability of structural standing seam steel roof panel systems. It includes performance requirements for the following elements only: panels, concealed panel clips, panel/clip anchorage, and panel joint sealers.  
Note 1—These systems are used on both low-slope and steep-slope roof applications. They also are used with or without an underlying deck or sheathing.  
1.2 The objective of this specification is to provide for the overall performance of the structural standing seam steel roof panel system as defined in 3.2.6 during its service life in order to provide weather protection, carry the specified design loads, and allow proper access over the roof surface in order to provide for periodic maintenance of equipment by the owner.  
1.3 In addition to structural, the specifier shall evaluate other characteristics beyond the scope of this specification that affect the final choice of roof construction. These include, but are not limited to, functional, legal, insurance, and economic considerations. See Appendix X1 for specifier's checklist.  
1.4 The specification is not intended to exclude products or systems not covered by the referenced documents.  
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.6 The text of this specification contains notes and footnotes that provide explanatory information and are not requirements of this specification.

  • Technical specification
    5 pages
    English language

SIGNIFICANCE AND USE
This test method is a standard procedure for determining the resistance to water penetration under uniform positive static air pressure differences, and simulates wind driven rain imposed on sidelaps and rain that is free to drain while building a water head as it flows. The slope of the roof is significant. These factors shall be fully considered prior to specifying the test pressure difference.
Note 1—In applying the results of tests by this method, note that the performance of a roof or its components, or both, may be a function of proper installation and adjustment. In service, the performance also depends on the rigidity of supporting construction, roof slope, and on the resistance of components to deterioration by various causes: corrosive atmosphere, aging, ice, vibration, thermal expansion and contraction, etc. It is difficult to simulate the identical complex wetting conditions that can be encountered in service, including large wind-blown water drops, increasing water drop impact pressures with increasing wind velocity, and lateral or upward moving air and water. Some designs are more sensitive than others to this upward moving water.
Note 2—This is a test procedure. It is the responsibility of the specifying agency to determine the specimen construction, size, and test pressures after considering the method's guidelines. Practical considerations suggest that every combination of panel thickness, span, and design load need not be tested in order to substantiate product performance.
Note 3—This test method shall not, by itself, be relied upon to form conclusions about overall water penetration through metal roofs. A roof contains many details. Although prescribed modifications are outside the scope of this test method, an experienced testing engineer is able to use the principles presented in this test method and generate significant data by isolating specific details and measuring leakage.
SCOPE
1.1 This test method covers the determination of the resistance of exterior metal roof panel systems to water penetration when water is applied to the outdoor face simultaneously with a static air pressure at the outdoor face higher than the pressure at the indoor face, that is, positive pressure. This test method is a specialized adaption of Test Method E331.
1.2 This test method is applicable to any roof area and is intended to measure only the water penetration associated with the field of roof including panel side laps and structural connections. It does not include leakage at openings or perimeter or any other details.
1.3 This test method is limited to specimens in which the side seams and attachments are clearly visible and in which the source of leakage is readily determined. Composite systems in which the source cannot be readily determined are outside the scope of this test method.
1.4 The proper use of this test method requires a knowledge of the principles of pressure and flow measurement.
1.5 The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are for information only and may be approximate.
1.6 The text of this test method references notes and footnotes excluding tables and figures, which provide explanatory material. These notes and footnotes shall not be considered as requirements of the test method.
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific hazard statements, see 7.1.

  • Standard
    6 pages
    English language

SIGNIFICANCE AND USE
This test method is a standard procedure for determining water leakage through metal roof panel system sideseams, endlaps, and roof plane penetrations when the roof system is subjected to a specified static water pressure head.
Note 2—In applying the results of tests by this method, note that the performance of a roof or its components or both, is in part a function of proper installation and adjustment. In service, the performance will also depend on the integrity of the supporting construction, roof slope, and on the resistance of components to deterioration by various causes: corrosive atmosphere, aging, ice, vibration, thermal cycling, etc. It is difficult to simulate the identical complex wetting, aging, and other variable conditions that can be encountered in service, including wind-blown ponded water; the effects of temperature and age on sealant performance; differential pressure across the joints due to wind, snow, and ice accumulation; densification and migration; and abrasions within the joint components which may occur during thermal cycling and other weather events. Some joint conditions are more sensitive than others to these factors.
This test method will evaluate the resistance of roof panels, sideseams, endlaps, and roof plane penetrations to water submersion. It will not evaluate panel resistance to wind driven rain.
Note 3—See Test Method E1646 for a test which evaluates resistance to wind driven rain.
This test method is not a structural adequacy test.
This test method is applicable to single skin metal panels, the exterior skin of factory assembled composite panels, and the exterior skin of field assembled composite systems as long as means can be provided to distinguish leakage through the exterior panel sideseams/endlaps and perimeter leakage.
SCOPE
1.1 This laboratory test method covers the determination of the resistance to water penetration of exterior metal roof panel system sideseams, endlaps, and roof plane penetrations when a specified static water pressure head is applied to the outside face of the roof panel.
Note 1—This test method is intended to evaluate water-barrier (not water-shedding) roof system joints and details. These systems are also referred to as hydrostatic roof systems.
1.2 This test method is limited to specimens in which the sideseams and attachments are clearly visible and in which the source of leakage is readily observable.
1.3 This test method excludes performance at roof perimeter conditions.
1.4 This test method is suitable for evaluating leakage at roof plane penetrations such as fasteners, curbs, pipes, and expansion joints under a static water pressure head.
1.5 The proper use of this test method requires a knowledge of the principles of water pressure.  
1.6 The text of this standard includes notes and footnotes excluding tables and figures, which provide explanatory material. These notes and footnotes shall not be considered as requirements of the standard.
1.7 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific precautionary statements, see Section 7.

  • Standard
    4 pages
    English language

SIGNIFICANCE AND USE
This test method provides a standard procedure to evaluate or confirm structural performance under uniform static air pressure difference. This procedure is intended to represent the effects of uniform loads on exterior building surface elements.  
It is also permissible to develop data for load-span tables by interpolating between the test results at different spans.  
Note 1—When applying the results of tests to determine allowable design loads by application of a factor of safety, bear in mind that the performance of a wall or roof and its components, or both, can be a function of fabrication, installation, and adjustment. The specimen must represent the actual structure closely. In service, the performance can also depend on the rigidity of supporting construction and on the resistance of components to deterioration by various causes, to vibration, to thermal expansion and contraction, and so forth.
SCOPE
1.1 This test method covers the evaluation of the structural performance of sheet metal panels and anchor-to-panel attachments for roof or siding systems under uniform static air pressure differences using a test chamber or support surface.
1.2 The provisions of this test method are applicable to standing seam, trapezoidal, ribbed, or corrugated metal panels in the range of thickness from 0.012 to 0.050-in. (0.3 to 1.3-mm) and apply to the evaluation of uniform pressure applied to single-skin construction or one sheet metal layer of multiple-skin construction. They do not cover requirements for the construction of a specimen to determine the load sharing that can occur with either composite or multiple-layer construction such as: (1) metal cladding over wood sheathing; or (2) field assemblies of insulation sandwiched between corrugated or formed metal panels.
1.3 Proper use of this test method requires knowledge of the principles of pressure and deflection measurement.
1.4 This test method describes optional apparatus and procedures for use in evaluating the structural performance of a given system for a range of support spacings or for confirming the structural performance of a specific installation.
1.5 The values stated in inch-pound units are to be regarded as the standard. The metric equivalents of inch-pound units are approximate.
1.6 The text of this standard references notes and footnotes exclusive of those for tables and figures. These notes and footnotes provide explanatory material and shall not be considered as requirements of the standard.
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific precautionary statements, see Section 7.

  • Standard
    8 pages
    English language
  • Standard
    8 pages
    English language

ABSTRACT
This specification covers the design, construction, and weatherability of structural standing seam aluminum roof panel systems. It includes performance requirements for the following elements only: panels, concealed panel clips, panel/clip anchorage, and panel joint sealers. Structural panels shall be designed in accordance with the required specifications for aluminum structures and in accordance with sound engineering methods and practices. The static load capacity and uplift index shall be tested to meet the requirements prescribed. Connections of panels to structural members shall be made with concealed panel clips compatible with the panel design. A fixing line is required to anchor roof panels in order to maintain end alignment and to resist in-plane gravity and thermal force components. Panel-to-panel sidelap connections and endlaps shall be weathertight. Panels of maximum practicable lengths shall be used to minimize endlaps.
SCOPE
1.1 This specification covers the design, construction, and weatherability of structural standing seam aluminum roof panel systems. It includes performance requirements for the following elements only: panels, concealed panel clips, panel/clip anchorage, and panel joint sealers.
Note 1—These systems are used on both low-slope and steep-slope roof applications. They also are used with or without an underlying deck or sheathing.
1.2 The objective of this specification is to provide for the overall performance of the structural standing seam aluminum roof panel system as defined in during its service life in order to provide weather protection, carry the specified design loads, and allow proper access over the roof surface in order to provide for periodic maintenance of the equipment by the building owner.
1.3 In addition to structural characteristics, the specifier shall evaluate other characteristics beyond the scope of this specification that affect the final choice of roof construction. These include, but are not limited to, functional, legal, insurance, and economic considerations. See for the specifier's checklist.
1.4 This specification is not intended to exclude products or systems not covered by the referenced documents.
1.5 The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are for information only.
1.6 The text of this specification contains notes and footnotes that provide explanatory information and are not requirements of this specification.

  • Technical specification
    5 pages
    English language

ABSTRACT
This specification covers the design, construction, and weatherability of structural standing seam steel roof panel systems. It includes performance requirements for the following elements only: panels, concealed panel clips, panel/clip anchorage, and panel joint sealers. Panel material shall be a hot dip metallic coated product in accordance with one of the following commonly used materials: aluminum-, aluminum-zinc alloy-, zinc-, or zinc-5% aluminum alloy metallic-coated sheet steel. The roof system shall be designed for specified design loads and thermal effects without causing seam separation, permanent panel buckling, or weather-tightness loss. Deflection and serviceability shall be accounted for in the panel system for structural integrity. Static and uplift index tests shall be performed to determine the roof's load capacity. Standing seam roof panel systems shall be installed in accordance with the system design requirements.
SCOPE
1.1 This specification covers the design, construction, and weatherability of structural standing seam steel roof panel systems. It includes performance requirements for the following elements only: panels, concealed panel clips, panel/clip anchorage, and panel joint sealers.
Note 1—These systems are used on both low-slope and steep-slope roof applications. They also are used with or without an underlying deck or sheathing.
1.2 The objective of this specification is to provide for the overall performance of the structural standing seam steel roof panel system as defined in during its service life in order to provide weather protection, carry the specified design loads, and allow proper access over the roof surface in order to provide for periodic maintenance of equipment by the owner.
1.3 In addition to structural, the specifier shall evaluate other characteristics beyond the scope of this specification that affect the final choice of roof construction. These include, but are not limited to, functional, legal, insurance, and economic considerations. See Appendix X1 for specifier's checklist.
1.4 The specification is not intended to exclude products or systems not covered by the referenced documents.
1.5 The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are for information only.
1.6 The text of this specification contains notes and footnotes that provide explanatory information and are not requirements of this specification.

  • Technical specification
    5 pages
    English language

SIGNIFICANCE AND USE
This test method is a standard procedure for determining the resistance to water penetration under uniform positive static air pressure differences, and simulates wind driven rain imposed on sidelaps and rain that is free to drain while building a water head as it flows. The slope of the roof is significant. These factors shall be fully considered prior to specifying the test pressure difference.
Note 1—In applying the results of tests by this method, note that the performance of a roof or its components, or both, may be a function of proper installation and adjustment. In service, the performance also depends on the rigidity of supporting construction, roof slope, and on the resistance of components to deterioration by various causes: corrosive atmosphere, aging, ice, vibration, thermal expansion and contraction, etc. It is difficult to simulate the identical complex wetting conditions that can be encountered in service, including large wind-blown water drops, increasing water drop impact pressures with increasing wind velocity, and lateral or upward moving air and water. Some designs are more sensitive than others to this upward moving water.
Note 2—This is a test procedure. It is the responsibility of the specifying agency to determine the specimen construction, size, and test pressures after considering the method’guidelines. Practical considerations suggest that every combination of panel thickness, span, and design load need not be tested in order to substantiate product performance.
Note 3—This test method shall not, by itself, be relied upon to form conclusions about overall water penetration through metal roofs. A roof contains many details. Although prescribed modifications are outside the scope of this test method, an experienced testing engineer is able to use the principles presented in this test method and generate significant data by isolating specific details and measuring leakage.
SCOPE
1.1 This test method covers the determination of the resistance of exterior metal roof panel systems to water penetration when water is applied to the outdoor face simultaneously with a static air pressure at the outdoor face higher than the pressure at the indoor face, that is, positive pressure. This test method is a specialized adaption of Test Method E 331.
1.2 This test method is applicable to any roof area and is intended to measure only the water penetration associated with the field of roof including panel side laps and structural connections. It does not include leakage at openings or perimeter or any other details.
1.3 This test method is limited to specimens in which the side seams and attachments are clearly visible and in which the source of leakage is readily determined. Composite systems in which the source cannot be readily determined are outside the scope of this test method.
1.4 The proper use of this test method requires a knowledge of the principles of pressure and flow measurement.
1.5 The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are for information only and may be approximate.
1.6 The text of this test method references notes and footnotes excluding tables and figures, which provide explanatory material. These notes and footnotes shall not be considered as requirements of the test method.
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific hazard statements, see 7.1.

  • Standard
    6 pages
    English language

SCOPE
1.1 This test method covers the determination of the resistance of exterior metal roof panel systems to air infiltration resulting from either positive or negative air pressure differences. The test method described is for tests with constant temperature and humidity across the specimen. This test method is a specialized adaption of Test Method E 283.
1.2 This test method is applicable to any roof area. This test method is intended to measure only the air leakage associated with the field of the roof, including the panel side laps and structural connections; it does not include leakage at the openings or perimeter or any other details.
1.3 The proper use of this test method requires knowledge of the principles of air flow and pressure measurements.
1.4 The text of this test method references notes and footnotes excluding tables and figures, which provide explanatory material. These notes and footnotes shall not be considered to be requirements of the test method.
1.5 The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are for information only.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific precautionary statements, see Section 7.

  • Standard
    6 pages
    English language

SCOPE
1.1 This test method covers the evaluation of the structural performance of sheet metal panels and anchor-to-panel attachments for roof or siding systems under uniform static air pressure differences using a test chamber or support surface.
1.2 The provisions of this test method are applicable to standing seam, trapezoidal, ribbed, or corrugated metal panels in the range of thickness from 0.012 to 0.050-in. (0.3 to 1.3-mm) and apply to the evaluation of uniform pressure applied to single-skin construction or one sheet metal layer of multiple-skin construction. They do not cover requirements for the construction of a specimen to determine the load sharing that can occur with either composite or multiple-layer construction such as: 1) metal cladding over wood sheathing; or 2) field assemblies of insulation sandwiched between corrugated or formed metal panels.
1.3 Proper use of this test method requires knowledge of the principles of pressure and deflection measurement.
1.4 This test method describes optional apparatus and procedures for use in evaluating the structural performance of a given system for a range of support spacings or for confirming the structural performance of a specific installation.
1.5 The values stated in inch-pound units are to be regarded as the standard. The metric equivalents of inch-pound units are approximate.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific precautionary statements, see Section 7.
1.7 The text of this standard references notes and footnotes exclusive of those for tables and figures. These notes and footnotes provide explanatory material and shall not be considered as requirements of the standard.

  • Standard
    8 pages
    English language

SIGNIFICANCE AND USE
This test method is a standard procedure for determining water leakage through metal roof panel system sideseams, endlaps, and roof plane penetrations when the roof system is subjected to a specified static water pressure head.
Note 2—In applying the results of tests by this method, note that the performance of a roof or its components or both, is in part a function of proper installation and adjustment. In service, the performance will also depend on the integrity of the supporting construction, roof slope, and on the resistance of components to deterioration by various causes: corrosive atmosphere, aging, ice, vibration, thermal cycling, etc. It is difficult to simulate the identical complex wetting, aging and other variable conditions that can be encountered in service, including wind-blown ponded water, the effects of temperature and age on sealant performance, differential pressure across the joints due to wind, snow and ice accumulation, densification and migration, and abrasions within the joint components which may occur during thermal cycling and other weather events. Some joint conditions are more sensitive than others to these factors.
This test method will evaluate the resistance of roof panels, sideseams, endlaps, and roof plane penetrations to water submersion. It will not evaluate panel resistance to wind driven rain.
Note 3—See E 1646 for a test which evaluates resistance to wind driven rain.
This test method is not a structural adequacy test.
This test method is applicable to single skin metal panels, the exterior skin of factory assembled composite panels, and the exterior skin of field assembled composite systems as long as means can be provided to distinguish leakage through the exterior panel sideseams/endlaps and perimeter leakage.
SCOPE
1.1 This Laboratory test method covers the determination of the resistance to water penetration of exterior metal roof panel system sideseams, endlaps, and roof plane penetrations when a specified static water pressure head is applied to the outside face of the roof panel.Note 1
This test method is intended to evaluate water-barrier (not water-shedding) roof system joints and details. These systems are also referred to as hydrostatic roof systems.
1.2 This test method is limited to specimens in which the sideseams and attachments are clearly visible and in which the source of leakage is readily observable.
1.3 This test method excludes performance at roof perimeter conditions.
1.4 This test method is suitable for evaluating leakage at roof plane penetrations such as fasteners, curbs, pipes and expansion joints under a static water pressure head.
1.5 The proper use of this test method requires a knowledge of the principles of water pressure.
1.6 The values stated in inch-pound units are to be regarded as the standard. The SI equivalents of inch-pound units are approximate.
1.7 The text of this standard includes notes and footnotes excluding tables and figures, which provide explanatory material. These notes and footnotes shall not be considered as requirements of the standard.
This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific precautionary statements, see Section .

  • Standard
    4 pages
    English language

SCOPE
1.1 This test method covers the evaluation of the structural performance of sheet metal panels and anchor-to-panel attachments for roof or siding systems under uniform static air pressure differences using a test chamber or support surface.
1.2 The provisions of this test method are applicable to standing seam, trapezoidal, ribbed, or corrugated metal panels in the range of thickness from 0.012 to 0.050-in. (0.3 to 1.3-mm) and apply to the evaluation of uniform pressure applied to single-skin construction or one sheet metal layer of multiple-skin construction. They do not cover requirements for the construction of a specimen to determine the load sharing that can occur with either composite or multiple-layer construction such as: 1) metal cladding over wood sheathing; or 2) field assemblies of insulation sandwiched between corrugated or formed metal panels.
1.3 Proper use of this test method requires knowledge of the principles of pressure and deflection measurement.
1.4 This test method describes optional apparatus and procedures for use in evaluating the structural performance of a given system for a range of support spacings or for confirming the structural performance of a specific installation.
1.5 The values stated in inch-pound units are to be regarded as the standard. The metric equivalents of inch-pound units are approximate.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific precautionary statements, see Section 7.
1.7 The text of this standard references notes and footnotes exclusive of those for tables and figures. These notes and footnotes provide explanatory material and shall not be considered as requirements of the standard.

  • Standard
    8 pages
    English language

SCOPE
1.1 This specification covers the design, construction, and weatherability of structural standing seam steel roof panel systems that can resist all superimposed design loads without the benefit of a supporting deck or sheathing. It includes performance requirements for the following elements only: panels, concealed panel clips, panel/clip anchorage, and panel joint sealers. Many of these systems are used on low-sloped roofs when installed in accordance with the manufacturer's recommendations.
1.2 The objective is to provide for the performance of the standing seam steel roof panel system as defined in 1.1 during its service life in order to provide weather protection, carry the specified design loads, and allow proper access over the roof surface in order to provide periodic maintenance of equipment by the owner.
1.3 In addition to structural, the specifier shall evaluate other characteristics beyond the scope of this specification, that affect the final choice of roof construction. These include, but are not limited to, functional, legal, insurance, and economic considerations. See Appendix X1 for designer's checklist.
1.4 The specification is not intended to exclude products or systems not covered by the referenced documents.

  • Technical specification
    5 pages
    English language

SCOPE
1.1 This specification covers the design, construction, and weatherability of structural standing seam aluminum roof panel systems that resist all superimposed design loads without the benefit of supporting deck or sheathing. It includes performance requirements for the following elements only: panels, concealed panel clips, panel/clip anchorage, and panel joint sealers.
1.2 The objective of this specification is to provide for the overall performance of the standing seam aluminum roof panel system in accordance with 1.1 during its service life in order to provide weather protection, carry the specified design loads, and allow proper access over the roof surface in order to provide periodic maintenance of the equipment by the building owner.
1.3 In addition to structural characteristics, the specifier shall evaluate other characteristics beyond the scope of this specification that affect the final choice of roof construction. These include, but are not limited to, functional, legal, insurance, and economic considerations. See Appendix X1 for the designer's checklist.
1.4 This specification is not intended to exclude products or systems not covered by the referenced documents.
1.5 The values stated in SI units are to be regarded as the standard. The values given in parentheses are for information only.

  • Technical specification
    5 pages
    English language

SCOPE
1.1 This test method covers the determination of the resistance of exterior metal roof panel systems to water penetration when water is applied to the outdoor face simultaneously with a static air pressure at the outdoor face higher than the pressure at the indoor face, that is, positive pressure. This test method is a specialized adaption of Test Method E331.
1.2 This test method is applicable to any roof area and is intended to measure only the water penetration associated with the field of roof including panel side laps and structural connections. It does not include leakage at openings or perimeter or any other details.
1.3 This test method is limited to specimens in which the side seams and attachments are clearly visible and in which the source of leakage is readily determined. Composite systems in which the source cannot be readily determined are outside the scope of this test method.
1.4 The proper use of this test method requires a knowledge of the principles of pressure and flow measurement.
1.5 The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are for information only and may be approximate.
1.6 The text of this test method references notes and footnotes excluding tables and figures, which provide explanatory material. These notes and footnotes shall not be considered as requirements of the test method.
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific hazard statements, see 8.1.

  • Standard
    6 pages
    English language

SCOPE
1.1 This test method covers the determination of the resistance of exterior metal roof panel systems to air infiltration resulting from either positive or negative air pressure differences. The test method described is for tests with constant temperature and humidity across the specimen. This test method is a specialized adaption of Test Method E283.  
1.2 This test method is applicable to any roof area. This test method is intended to measure only the air leakage associated with the field of the roof, including the panel side laps and structural connections; it does not include leakage at the openings or perimeter or any other details.  
1.3 The proper use of this test method requires knowledge of the principles of air flow and pressure measurements.  
1.4 The text of this test method references notes and footnotes excluding tables and figures, which provide explanatory material. These notes and footnotes shall not be considered to be requirements of the test method.  
1.5 The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are for information only.  
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific precautionary statements, see Section 7.

  • Standard
    6 pages
    English language

Frequently Asked Questions

E06.57 is a Technical Committee within ASTM International. It is named "Performance of Metal Roof Systems". This committee has published 27 standards.

E06.57 develops ASTM standards in the area of Information technology. Currently, there are 27 published standards from this technical committee.

ASTM is a standardization organization that develops and publishes standards to support industry, commerce, and regulatory requirements.

A Technical Committee (TC) in ASTM is a group of experts responsible for developing international standards in a specific technical area. TCs are composed of national member body delegates and work through consensus to create standards that meet global industry needs. Each TC may have subcommittees (SCs) and working groups (WGs) for specialized topics.

Loading...