ASTM D3311-11(2016)
(Specification)Standard Specification for Drain, Waste, and Vent (DWV) Plastic Fittings Patterns
Standard Specification for Drain, Waste, and Vent (DWV) Plastic Fittings Patterns
ABSTRACT
This specification illustrates the standard fitting geometries and laying lengths of plastic fittings intended for use with outside diameter controlled pipes in drain, waste, and vent (DWV) applications.
SCOPE
1.1 This specification provides standard fitting geometries and laying lengths for plastic fittings intended for use in drain, waste, and vent applications. (See Specifications D2661 and D2665.)
1.2 Fittings meeting the requirements of this standard specification are designed for use with outside diameter controlled pipe. The inside diameter can vary significantly as the wall thickness and outside diameter varies and therefore is not suitable for use as a fitting socket.
1.3 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
General Information
Relations
Buy Standard
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:D3311 −11 (Reapproved 2016) An American National Standard
Standard Specification for
Drain, Waste, and Vent (DWV) Plastic Fittings Patterns
This standard is issued under the fixed designation D3311; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope D2665 Specification for Poly(Vinyl Chloride) (PVC) Plastic
Drain, Waste, and Vent Pipe and Fittings
1.1 This specification provides standard fitting geometries
F1498 Specification for Taper Pipe Threads 60° for Thermo-
and laying lengths for plastic fittings intended for use in drain,
plastic Pipe and Fittings
waste, and vent applications. (See Specifications D2661 and
D2665.)
3. Requirements
1.2 Fittings meeting the requirements of this standard speci-
3.1 Fittings shall conform to the geometries and laying
fication are designed for use with outside diameter controlled
lengths as shown in Tables 1-45 and Figs. 1-5.Tolerances shall
pipe. The inside diameter can vary significantly as the wall
be 6 ⁄16 in. unless otherwise specified.
thickness and outside diameter varies and therefore is not
3.2 Spigot and hub dimensions shall conform to the require-
suitable for use as a fitting socket.
ments of the referencing standard.
1.3 The values stated in inch-pound units are to be regarded
3.3 The exact outside shape of a fitting is not determined by
as standard. The values given in parentheses are mathematical
the outline drawings shown in this specification but rather by
conversions to SI units that are provided for information only
the socket dimensions, wall thickness requirements, waterway,
and are not considered standard.
laying lengths, and any other critical dimensions that may be
2. Referenced Documents
specified.
2.1 ASTM Standards:
3.4 The pitch of sockets for patterns with 90° angles (except
D2661 Specification for Acrylonitrile-Butadiene-Styrene
vent fittings) shall be ⁄4 in./ft or 1° 12 min.
(ABS) Schedule 40 Plastic Drain, Waste, and Vent Pipe
3.5 On double reducing sanitary tees, the G2 dimension on
and Fittings
branches will be calculated on the larger size and centerlines
shall remain the same for both branches.
This specification is under the jurisdiction ofASTM Committee F17 on Plastic
Piping Systems and is the direct responsibility of Subcommittee F17.63 on DWV.
3.6 All other dimensions, materials and property require-
Current edition approved Feb. 1, 2016. Published February 2016. Originally
ments shall be in conformance with the referencing standard.
approved in 1974. Last previous edition approved in 2011 as D3311 – 11. DOI:
10.1520/D3311-11R16.
For referenced ASTM standards, visit the ASTM website, www.astm.org, or 4. Keywords
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
4.1 DWV; fittings; plastic; Schedule 40; thermoplastic
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
D3311−11 (2016)
TABLE 1 Bends, in. (mm)
Long Sweep
1 1 1 1
⁄4 Bend ⁄8 Bend ⁄6 Bend ⁄16 Bend
⁄4 Bend
Nominal Pipe Size
GG G G G
1 9 1 7 7
1 ⁄4 1 ⁄16 (40) 2 ⁄4 (57) 1 (25) ⁄8 (22) ⁄16 (11)
1 3 3 1 1
1 ⁄2 1 ⁄4 (44) 2 ⁄4 (70) 1 ⁄8 (29) 1 (25) ⁄2 (13)
5 1 1 5 11
22 ⁄16 (59) 3 ⁄4 (83) 1 ⁄2 (38) 1 ⁄16 (33) ⁄16 (17)
1 1 3 11 13
33 ⁄16 (78) 4 ⁄16 (103) 1 ⁄4 (44) 1 ⁄16 (43) ⁄16 (21)
7 15 3 1
43 ⁄8 (98) 4 ⁄16 (125) 2 ⁄16 (56) 2 ⁄16 (52) 1 (25)
3 1
6 5 (min) (127) 9 (229) 2 (min) (51) 3 ⁄8 (86) 1 ⁄2 (38)
1 1
8 6 (152) . . . 2 ⁄16 (52) . . . 1 ⁄2 (38)
A A A
1 5 3
10 9 ⁄4 (235) . 2 ⁄8 (67) . 2 ⁄16 (56)
A A A
11 1 3
12 10 ⁄16 . 3 ⁄8 (79) . 2 ⁄8 (60)
A
10 in. and 12 in. fittings dimensions are minimum
TABLE 2 Bends with Inlets, in. (mm)
Long-Sweep ⁄4 Bend with Low Heel
1 1
⁄4 Bend with Low Heel Inlet Long-Sweep ⁄4 Bend with High Heel Inlet
Inlet
Nominal Pipe Size
GN G N G N GG
1 1 3 1 3
3by3by1 ⁄2 3 ⁄16 (78) 4 ⁄16 (106) 4 ⁄16 (103) 4 ⁄4 (121) . . . . . . . . .
1 7 1 15 1 5 1
3by3by2 3 ⁄16 (78) 4 ⁄16 (113) 4 ⁄16 (103) 4 ⁄16 (125) 4 ⁄16 (103) 5 ⁄8 (143) 2 ⁄4 (57)
7 7 15
4by4by2 3 ⁄8 (98) 5 ⁄16 (138) 4 ⁄16 (125) 6 (152) . . . . . . . . .
D3311−11 (2016)
TABLE 3 Sanitary Tees, 45° Wyes, Combination Wyes and ⁄8 Bends, in. (mm)
Combination Wye and ⁄8 Bend Single and
A
Sanitary Tee Single and Double 45° Wye, Single and Double
Double
Nominal Pipe Size
GN GJ GN GJ GN GJ
1 3 9 1 9 7 15
1 ⁄4 ⁄4 (19) 1 ⁄16 (40) 1 ⁄16 (27) 2 ⁄16 (65) ⁄16 (11) 2 ⁄16 (75)
1 3 1 7 1 3
1 ⁄2 1 (25) 1 ⁄4 (44) 1 ⁄8 (29) 2 ⁄8 (73) ⁄2 (13) 3 ⁄8 (86)
3 5 3 5 1
21 ⁄8 (35) 2 ⁄16 (59) 1 ⁄8 (35) 3 ⁄8 (92) 1 (25) 4 ⁄2 (114)
13 1 5 1 5
31 ⁄16 (46) 3 ⁄16 (78) 1 ⁄8 (41) 5 (127) 1 ⁄8 (29) 6 ⁄16 (160)
1 7 7 3 13 5
42 ⁄4 (57) 3 ⁄8 (98) 1 ⁄8 (48) 6 ⁄8 (162) 1 ⁄16 (46) 8 ⁄8 (219)
BB
1 3 7
63 ⁄2 (89) 5 (127) 1 ⁄4 (44) 8 ⁄16 (214)
BB
1 3 3
84 ⁄2 (114) 6 (152) 2 ⁄8 (60) 11 ⁄4 (298)
C C C CB B
1 11 7
10 5 ⁄2 (140) 9 ⁄16 (246) 2 ⁄16 (62) 13 (330)
C C C CB B
9 7 3
12 6 ⁄16 (167) 11 (279) 2 ⁄8 (73) 15 ⁄8 (391)
A
Non-reducing double sanitary tees are for vent use only.
B 1
Combination wye and ⁄8 bend is assembled from two standard fittings.
C
10 in. and 12 in. fittings dimensions are minimum.
D3311−11 (2016)
TABLE 4 Reducing Sanitary Tees, 45° Wyes, Combination Wyes, and ⁄8 Bends, in. (mm)
Combination Wye and ⁄8 Bend
A
Sanitary Tee, Reducing Single and Double 45° Wye, Reducing Single and Double
Reducing Single and Double
Nominal Pipe Size
G1 G2 G3 G4 G1 G2 G3 G1 G2 G3
B B B B
1 1 1 11 1 11 11
1 ⁄2 by 1 ⁄4 by 1 ⁄4 ⁄16 (17) 1 ⁄2 (38) 1 ⁄16 (43) 1 ⁄16 (43) — — — ———
1 1 1 3 3 3
1 ⁄2 by 1 ⁄4 by 1 ⁄2 1 (25) 1 ⁄4 (44) 1 ⁄4 (44) 1 ⁄4 (44) — — — — — —
1 1 1 13 11 13 13 1 1 3
1 ⁄2 by 1 ⁄2 by 1 ⁄4 ⁄16 (21) 1 ⁄16 (43) 1 ⁄16 (46) 1 ⁄16 (46) — — — ⁄2 (13) 3 ⁄4 (83) 3 ⁄16 (81)
1 1 3 15 3 3
2by1 ⁄4 by 1 ⁄2 1 ⁄16 (30) 1 ⁄16 (49) 2 ⁄16 (56) 2 ⁄16 (56) — — — — — —
B B B
1 1 3 15 3 3 3 13 15 9 11 5
2by1 ⁄2 by 1 ⁄2 1 ⁄16 (30) 1 ⁄16 (49) 2 ⁄16 (56) 2 ⁄16 (56) ⁄4 (19) 2 ⁄16 (71) 2 ⁄16 (75) ⁄16 (14) 3 ⁄16 (94) 3 ⁄8 (92)
B B B
1 3 5 5 5 1 3 1 1
2by1 ⁄2 by 2 1 ⁄8 (35) 2 ⁄16 (59) 2 ⁄16 (59) 2 ⁄16 (50) 1 (25) 3 ⁄2 (89) 3 ⁄8 (86) 1 (25) 4 ⁄2 (114) 4 ⁄2 (114)
1 3 15 3 3
2by2by1 ⁄4 1 ⁄16 (30) 1 ⁄16 (49) 2 ⁄16 (56) 2 ⁄16 (56) — — — — — —
1 3 15 3 3 1 5 7 9 11 5
2by2by1 ⁄2 1 ⁄16 (30) 1 ⁄16 (49) 2 ⁄16 (56) 2 ⁄16 (56) 1 ⁄16 (27) 3 ⁄16 (84) 3 ⁄16 (87) ⁄16 (14) 3 ⁄16 (170) 3 ⁄8 (92)
1 15 3 9 9 1 3 5 1 7 1
3by3by1 ⁄2 ⁄16 (24) 1 ⁄4 (44) 2 ⁄16 (65) 2 ⁄16 (65) ⁄2 (13) 3 ⁄4 (95) 4 ⁄16 (110) ⁄8 (3) 3 ⁄16 (87) 4 ⁄4 (108)
3 1 7 7 7 1 5 7 3 5
3by3by2 1 ⁄16 (30) 2 ⁄8 (54) 2 ⁄8 (73) 2 ⁄8 (73) ⁄8 (22) 4 ⁄8 (105) 4 ⁄8 (117) ⁄16 (11) 4 ⁄4 (121) 5 ⁄16 (135)
B B B B
1 15 1 7 1
3by3by2by1 ⁄2 ⁄16 (24) 2 ⁄16 (52) 2 ⁄16 (62) 2 ⁄2 (64) — — — ———
B B B B B B B
1 1 1 1 5 15
4by4by1 ⁄2 1 ⁄16 (27) 2 (51) 3 ⁄4 (83) 3 ⁄4 (83) 0(0) 3 ⁄16 (84) 3 ⁄16 (100) ———
1 1 5 5 3 11 9 5 3 7
4by4by2 1 ⁄8 (29) 2 ⁄16 (52) 3 ⁄16 (84) 3 ⁄16 (84) ⁄8 (10) 4 ⁄16 (119) 5 ⁄16 (141) ⁄16 (8) 4 ⁄4 (121) 5 ⁄8 (149)
3 9 9 1 9 1 3 7
4by4by3 1 ⁄4 (44) 3 (76) 3 ⁄16 (90) 3 ⁄16 (90) 1 ⁄16 (27) 5 ⁄16 (141) 6 (152) 1 ⁄16 (27) 6 ⁄8 (162) 6 ⁄8 (175)
B B B B B B
3 15 7 11 13 13
6by6by3 — — — — ⁄16 (5) 6 ⁄16 (176) 7 ⁄16 (189) ⁄16 (17) 7 ⁄16 (198) 8 ⁄16 (224)
B B B B B B B B B B
3 5 5 5 3 11 7 9 13 15
6by6by4 2 ⁄16 (56) 3 ⁄8 (92) 4 ⁄16 (110) 4 ⁄16 (110) ⁄16 (5) 6 ⁄16 (170) 7 ⁄16 (189) ⁄16 (14) 7 ⁄16 (198) 8 ⁄16 (227)
5 1 1 1 3 5 5 CCC
8by8by4 2 ⁄8 (67) 4 ⁄8 (105) 5 ⁄4 (133) 5 ⁄4 (133) ⁄8 (10) 7 ⁄8 (194) 8 ⁄8 (219)
CCC
9 13 1 1 1 13
8by8by6 3 ⁄16 (90) 4 ⁄16 (122) 5 ⁄2 (140) 5 ⁄2 (140) 1 (25) 9 ⁄2 (241) 9 ⁄16 (249)
B B B CCC
1 11 3
10 by 10 by 4 . . . . -1 ⁄2 (-38) 8 ⁄16 (221) 10 ⁄8 (264)
B B CCC
1 1
10 by 10 by 6 . . . . 0 10 ⁄8 (257) 11 ⁄4 (286)
B B B CCC
1 1 7
10 by 10 by 8 . . . . 1 ⁄4 (32) 11 ⁄2 (202) 12 ⁄16 (316)
B B B CCC
7 3 13
12 by 12 by 4 . . . . -2 ⁄16 (-62) 9 ⁄4 (248) 11 ⁄16 (284)
B B B CCC
3 3 11
12 by 12 by 6 . . . . - ⁄4 (-19) 11 ⁄16 (284) 11 ⁄16 (297)
1 B 9 B 7 B CCC
12 by 12 by 8 . . . . ⁄2 (13) 12 ⁄16 (319) 13 ⁄8 (352)
B B B CCC
1 15
12 by 12 by 10 . . . . 1 ⁄8 (29) 14 (356) 14 ⁄16 (379)
A
Non-reducing double sanitary tees are for vent use only.
B
This dimension is a minimum with no upper maximum limit.
C
Combination Wye and ⁄8 bend is assembled from two standard fittings.
TABLE 5 60° Wyes, Single, and Double, in. (mm) TABLE 6 Fixture Tees, in. (mm)
Nominal Pipe Size G1 G2 G3
1 9 3 1
1 ⁄2 1 ⁄16 (40) 1 ⁄16 (30) 1 ⁄4 (32)
1 1 7 3 1
2by1 ⁄2 by 1 ⁄2 1 ⁄16 (37) 1 ⁄16 (30) 1 ⁄4 (32)
1 7 5 1
2by2by1 ⁄2 1 ⁄16 (37) 1 ⁄16 (33) 1 ⁄4 (32)
Nominal Pipe
GN GJ
Size
1 1 7
1 ⁄2 1 ⁄8 (40) 2 ⁄8 (73)
3 5
21 ⁄8 (37) 3 ⁄8 (92)
31 ⁄8 (37) 5 (127)
D3311−11 (2016)
TABLE 7 Cleanout Tees, in. (mm) TABLE 10 Molded Nipples, in. (mm)
Nominal
Nominal Pipe
OD ID Length
GI
Pipe Size
Size
1 1
1 ⁄2 1.900 1.500 ⁄2-in. increments from
1 3 5
1 ⁄2 1 ⁄16 (30) ⁄8 (16)
2 2.375 1.939 close to 18 in. long
1 5
21 ⁄2 (38) ⁄8 (16)
3 3.500 2.900
7 3
31 ⁄8 (48) ⁄4 (19)
1 7
42 ⁄2 (64) ⁄8 (22)
A A
1 15
63 ⁄2 (89) ⁄16 (33)
A A
9 1
84 ⁄16 (102) 1 ⁄2 (38)
TABLE 11 Vent Tees and ⁄4 Bend Vents, in. (mm)
A
6 in. and 8 in. fittings dimensions are minimum.
TABLE 8 Reducing Cleanout Tees, in. (mm)
Nominal Pipe
Vent Tee ⁄4 Bend Vent
Size
1 ⁄4 1 (25) 1 (25)
1 3 3
1 ⁄2 1 ⁄16 (30) 1 ⁄16 (30)
1 1
21 ⁄2 (38) 1 ⁄2 (38)
7 7
31 ⁄8 (48) 1 ⁄8 (48)
Nominal Pipe
1 1
42 ⁄2 (64) 2 ⁄2 (64)
GN, min GJ, min I, min
Size
A A
1 1
63 ⁄2 (89) 3 ⁄2 (89)
3 1 3 A A
1 1
10 by 10 by 8 5 ⁄16 (132) 5 ⁄2 (140) 1 ⁄4 (44) 84 ⁄2 (114) 4 ⁄2 (89)
1 11 A A
13 13
12 by 12 by 8 6 (152) 5 ⁄2 1 ⁄16 (43)
10 5 ⁄16 (148) 5 ⁄16 (148)
A A
7 7
12 6 ⁄8 (175) 6 ⁄8 (175)
A
6 in., 8 in., 10 in., and 12 in. fitting dimensions are minimum.
TABLE 9 60° Reducing Wyes, Single and Double, in. (mm)
Nominal Pipe
G1 G2 G3
Size
1 1 7 7
2by2by1 ⁄2 1 ⁄16 (27) 3 ⁄16 (87) 3 ⁄16 (87)
1 1 3 5
3by3by1 ⁄2 ⁄2 (13) 3 ⁄4 (95) 4 ⁄16 (110)
7 1 5
3by3by2 ⁄8 (22) 4 ⁄8 (105) 4 ⁄8 (117)
D3311−11 (2016)
TABLE 12 Reducing Vent Tees, Single, and Double, in. (mm)
GJ, min
Nominal Pipe Size GN, min
1 1 3 1
2by1 ⁄2 by 1 ⁄2 1 ⁄16 (30) 1 ⁄2 (38)
1 3 1
2by2by1 ⁄2 1 ⁄16 (30) 1 ⁄2 (38)
1 3 7
3by3by1 ⁄2 1 ⁄16 (30) 1 ⁄8 (48)
1 7
3by3by2 1 ⁄2 (38) 1 ⁄8 (48)
1 7
6by6by4 2 ⁄2 (64) 3 ⁄16 (87)
1 1
8by8by4 2 ⁄2 (64) 4 ⁄2 (114)
5 1
8by8by6 3 ⁄8 (92) 4 ⁄2 (114)
5 7
10 by 10 by 4 3 ⁄16 (84) 5 ⁄8 (149)
15 7
10 by 10 by 6 3 ⁄16 (100) 5 ⁄8 (149)
1 7
10 by 10 by 8 3 ⁄2 (89) 5 ⁄8 (140)
1 15
12 by 12 by 4 3 ⁄2 (89) 6 ⁄16 (176)
1 15
12 by 12 by 6 4 ⁄2 (114) 6 ⁄16 (176)
7 15
12 by 12 by 8 4 ⁄8 (124) 6 ⁄16 (176)
1 1
12 by 12 by 10 6 ⁄2 (165) 7 ⁄2 (190)
TABLE 13 Pipe Increasers, in. (mm)
Nominal N,min
Pipe Size
1 1 13
1 ⁄4 by 1 ⁄2 ⁄32 (10)
1 17
1 ⁄2 by 2 ⁄32 (13)
1 3
1 ⁄2 by 3 1 ⁄32 (28)
2by3 ⁄8 (22)
2by4 1 ⁄8 (35)
3by4 ⁄16 (24)
3by6 1 ⁄16 (49)
4by6 1 ⁄16 (30)
4by8 1 ⁄8 (41)
4by10 2 ⁄16 (56)
6by8 ⁄4 (19)
6by10 1 ⁄16 (40)
6by12 2 ⁄8 (60)
8by10 1 ⁄16 (33)
8by12 1 ⁄16 (46)
10 by 12 1 ⁄4 (32)
D3311−11 (2016)
TABLE 14 Trap Adapters, in. (mm)
Without Stop With Stop
Nominal N,min A,min
Pipe Size
1 3
1 ⁄4 ⁄16 (5) 1.250 (32)
1 3
1 ⁄2 ⁄16 (5) 1.500 (38)
2 ⁄16 (5) 2.000 (51)
1 1 3
1 ⁄4 by 1 ⁄2 ⁄16 (5) 1.250 (32)
TABLE 15 Hubs, in. (mm)
Nominal
AC N AJ CJ N
Pipe Size
3 3
2 . . . 2.94(74.7) 2 ⁄8 (60) ⁄8 (10)
11 5 5 7
3 3.448 (87.58) 1 ⁄16 (43) ⁄16 (8) 3.94 (100.1) 2 ⁄8 (67) ⁄16 (11)
15 11 7 1
4 4.493 (114.12) 1 ⁄16 (49) ⁄32 (9) 4.94 (125.5) 2 ⁄8 (73) ⁄2 (13)
15 5 7 7
Reducing 4 by 3 4.493 (114.12) 1 ⁄16 (49) ⁄16 (8) 4.94 (125.5) 2 ⁄8 (73) ⁄16 (11)
D3311−11 (2016)
TABLE 16 Spigots, in. (mm)
M
Nominal
L2,min L1,min L3,min AN
Pipe Size
max min
1 5 3
23 ⁄2 (89) 4 ⁄8 (117) ⁄8 (10) 2.75 (69.9) 2.63 (66.8) 2.00 (50.8)
3 5 3
33 ⁄4 (95) 5 ⁄8 (143) ⁄8 (10) 3.88 (98.6) 3.63 (92.2) 3.00 (76.2)
1 3
4 4 (102) 6 ⁄8 (156) ⁄8 (10) 4.88 (124.0) 4.63 (117.6) 4.00 (101.6)
TABLE 17 Reducing Spigots, in. (mm)
M
Nominal
L2 min L1 min L3 min AJ
min
Pipe Size
max
1 1 1 3
2by1 ⁄2 3 ⁄2 (89) 4 ⁄4 (108) ⁄8 (10) 2.75 (69.9) 2.63 (66.8) 2.00 (50.8)
1 3 1 3
3by1 ⁄2 3 ⁄4 (95) 4 ⁄2 (114) ⁄8 (10) 3.88 (98.6) 3.63 (92.2) 3.00 (76.2)
3 5 3
3by2 3 ⁄4 (95) 4 ⁄8 (117) ⁄8 (10) 3.88 (98.6) 3.63 (92.2) 3.00 (76.2)
7 3
4 by 2 4 (102) 4 ⁄8 (124) ⁄8 (10) 4.88 (124.0) 4.63 (117.6) 4.00 (101.6)
1 3
4 by 3 4 (102) 5 ⁄2 (140) ⁄8 (10) 4.88 (124.0) 4.63 (117.6) 4.00 (101.6)
D3311−11 (2016)
TABLE 18 P Traps, in. (mm)
Nominal
min GJ min GGJ min GGN min GN min R
Pipe Size
1 1 3 3 5
1 ⁄4 4 ⁄8 (105) 3 ⁄8 (86) 3 (76) 1 ⁄8 (35) 1 ⁄8 (41)
1 7 5 3 5
1 ⁄2 4 ⁄32 (107) 3 ⁄8 (92) 3 (76) 1 ⁄8 (35) 1 ⁄8 (41)
1 1 1 1
27 ⁄4 (184) 4 ⁄16 (103) 5 (127) 2 ⁄4 (57) 2 ⁄2 (64)
7 5 1 5 1
38 ⁄16 (214) 6 ⁄16 (160) 6 ⁄4 (159) 2 ⁄8 (67) 3 ⁄8 (79)
13 7 1 7 1
410 ⁄16 (275) 7 ⁄8 (200) 8 ⁄16 (205) 3 ⁄16 (87) 4 ⁄16 (103)
3 3 3 3 3
617 ⁄4 (451) 12 ⁄4 (324) 11 ⁄4 (298) 4 ⁄4 (121) 6 ⁄8 (162)
TABLE 19 Double Fixture Fitting, in. (mm)
Nominal Pipe Size G1 G2 G3 G4
1 3 9 7 7
1 ⁄2 ⁄8 (10) 3 ⁄16 (90) 2 ⁄16 (62) 2 ⁄16 (62)
3 9 1 1
2 ⁄8 (10) 4 ⁄16 (116) 3 ⁄16 (78) 3 ⁄16 (78)
1 3 1 1
3 ⁄2 (13) 6 ⁄4 (171) 4 ⁄2 (114) 4 ⁄2 (114)
Reducing:
1 1 1 3 9 7 7
2by1 ⁄2 by 1 ⁄2 by 1 ⁄2 ⁄8 (10) 3 ⁄16 (90) 2 ⁄16 (62) 2 ⁄16 (62)
1 3 9 1 1
2by1 ⁄2by2by2 ⁄8 (10) 4 ⁄16 (116) 3 ⁄16 (78) 3 ⁄16 (78)
1 1 3 9 1 1
2by1 ⁄2by2by1 ⁄2 ⁄8 (10) 4 ⁄16 (116) 3 ⁄16 (78) 3 ⁄16 (78)
D3311−11 (2016)
TABLE 20 Double Fixture Fitting, in. (mm)
Interchanges with Double Fixture Fittings
Double Fixture Fitting
Nominal
Pipe Size
G1 G2 G3 G4 R1 R2
1 3 1 11 11 5 5
1 ⁄2 ⁄8 (10) 3 ⁄8 (79) 2 ⁄16 (68) 2 ⁄16 (68) 3 ⁄8 (92) 3 ⁄8 (92)
3 1 1 1 1 1
2 ⁄8 (10) 4 ⁄4 (108) 3 ⁄2 (89) 3 ⁄2 (89) 4 ⁄2 (114) 4 ⁄2 (114)
1 1 15 15 5 5
3 ⁄2 (13) 6 ⁄4 (159) 4 ⁄16 (125) 4 ⁄16 (125) 6 ⁄8 (168) 6 ⁄8 (168)
Reducing
1 1 3 1 7 7 5 5
2by1 ⁄2 by 1 ⁄2 by ⁄8 (10) 3 ⁄8 (79) 2 ⁄8 (73) 2 ⁄8 (73) 3 ⁄8 (92) 3 ⁄8 (92)
1 ⁄2
1 1 3 1 7 1 5 1
2by1 ⁄2 by 1 ⁄2 by 2 ⁄8 (10) 4 ⁄4 (108) 2 ⁄8 (73) 3 ⁄2 (69) 3 ⁄8 (92) 4 ⁄2 (114)
1 3 1 1 1 1 1
2by1 ⁄2by2by2 ⁄8 (10) 4 ⁄4 (108) 3 ⁄2 (89) 3 ⁄2 (89) 4 ⁄2 (114) 4 ⁄2 (114)
1 1 15 15 5 5
3by2by3by3 ⁄2 (13) 6 ⁄4 (159) 4 ⁄16 (125) 4 ⁄16 (125) 6 ⁄8 (168) 6 ⁄8 (168)
TABLE 21 Single and Double Long Turn Tee, in. (mm)
...
This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: D3311 − 11 D3311 − 11 (Reapproved 2016) An American National Standard
Standard Specification for
Drain, Waste, and Vent (DWV) Plastic Fittings Patterns
This standard is issued under the fixed designation D3311; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This specification provides standard fitting geometries and laying lengths for plastic fittings intended for use in drain, waste,
and vent applications. (See Specifications D2661 and D2665.)
1.2 Fittings meeting the requirements of this standard specification are designed for use with outside diameter controlled pipe.
The inside diameter can vary significantly as the wall thickness and outside diameter varies and therefore is not suitable for use
as a fitting socket.
1.3 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
2. Referenced Documents
2.1 ASTM Standards:
D2661 Specification for Acrylonitrile-Butadiene-Styrene (ABS) Schedule 40 Plastic Drain, Waste, and Vent Pipe and Fittings
D2665 Specification for Poly(Vinyl Chloride) (PVC) Plastic Drain, Waste, and Vent Pipe and Fittings
F1498 Specification for Taper Pipe Threads 60° for Thermoplastic Pipe and Fittings
3. Requirements
3.1 Fittings shall conform to the geometries and laying lengths as shown in Tables 1-45 and Figs. 1-5. Tolerances shall be 6 ⁄16
in. unless otherwise specified.
3.2 Spigot and hub dimensions shall conform to the requirements of the referencing standard.
3.3 The exact outside shape of a fitting is not determined by the outline drawings shown in this specification but rather by the
socket dimensions, wall thickness requirements, waterway, laying lengths, and any other critical dimensions that may be specified.
3.4 The pitch of sockets for patterns with 90° angles (except vent fittings) shall be ⁄4 in./ft or 1° 12 min.
3.5 On double reducing sanitary tees, the G2 dimension on branches will be calculated on the larger size and centerlines shall
remain the same for both branches.
3.6 All other dimensions, materials and property requirements shall be in conformance with the referencing standard.
4. Keywords
4.1 DWV; fittings; plastic; Schedule 40; thermoplastic
This specification is under the jurisdiction of ASTM Committee F17 on Plastic Piping Systems and is the direct responsibility of Subcommittee F17.63 on DWV.
Current edition approved Aug. 1, 2011Feb. 1, 2016. Published August 2011February 2016. Originally approved in 1974. Last previous edition approved in 20092011 as
D3311 – 09a.D3311 – 11. DOI: 10.1520/D3311-11.10.1520/D3311-11R16.
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
D3311 − 11 (2016)
TABLE 1 Bends, in. (mm)
Long Sweep
1 1 1 1
⁄4 Bend ⁄8 Bend ⁄6 Bend ⁄16 Bend
⁄4 Bend
Nominal Pipe Size
G G G G G
1 9 1 7 7
1 ⁄4 1 ⁄16 (40) 2 ⁄4 (57) 1 (25) ⁄8 (22) ⁄16 (11)
1 3 3 1 1
1 ⁄2 1 ⁄4 (44) 2 ⁄4 (70) 1 ⁄8 (29) 1 (25) ⁄2 (13)
5 1 1 5 11
2 2 ⁄16 (59) 3 ⁄4 (83) 1 ⁄2 (38) 1 ⁄16 (33) ⁄16 (17)
1 1 3 11 13
3 3 ⁄16 (78) 4 ⁄16 (103) 1 ⁄4 (44) 1 ⁄16 (43) ⁄16 (21)
7 15 3 1
4 3 ⁄8 (98) 4 ⁄16 (125) 2 ⁄16 (56) 2 ⁄16 (52) 1 (25)
3 1
6 5 (min) (127) 9 (229) 2 (min) (51) 3 ⁄8 (86) 1 ⁄2 (38)
1 1
8 6 (152) . . . 2 ⁄16 (52) . . . 1 ⁄2 (38)
A A A
1 5 3
10 9 ⁄4 (235) . . . 2 ⁄8 (67) . . . 2 ⁄16 (56)
A A A
11 1 3
12 10 ⁄16 . . . 3 ⁄8 (79) . . . 2 ⁄8 (60)
A
10 in. and 12 in. fittings dimensions are minimum
TABLE 2 Bends with Inlets, in. (mm)
Long-Sweep ⁄4 Bend with Low Heel
1 1
⁄4 Bend with Low Heel Inlet Long-Sweep ⁄4 Bend with High Heel Inlet
Inlet
Nominal Pipe Size
G N G N G N GG
1 1 3 1 3
3 by 3 by 1 ⁄2 3 ⁄16 (78) 4 ⁄16 (106) 4 ⁄16 (103) 4 ⁄4 (121) . . . . . . . . .
1 7 1 15 1 5 1
3 by 3 by 2 3 ⁄16 (78) 4 ⁄16 (113) 4 ⁄16 (103) 4 ⁄16 (125) 4 ⁄16 (103) 5 ⁄8 (143) 2 ⁄4 (57)
7 7 15
4 by 4 by 2 3 ⁄8 (98) 5 ⁄16 (138) 4 ⁄16 (125) 6 (152) . . . . . . . . .
D3311 − 11 (2016)
TABLE 3 Sanitary Tees, 45° Wyes, Combination Wyes and ⁄8 Bends, in. (mm)
Combination Wye and ⁄8 Bend Single and
A
Sanitary Tee Single and Double 45° Wye, Single and Double
Double
Nominal Pipe Size
GN GJ GN GJ GN GJ
1 3 9 1 9 7 15
1 ⁄4 ⁄4 (19) 1 ⁄16 (40) 1 ⁄16 (27) 2 ⁄16 (65) ⁄16 (11) 2 ⁄16 (75)
1 3 1 7 1 3
1 ⁄2 1 (25) 1 ⁄4 (44) 1 ⁄8 (29) 2 ⁄8 (73) ⁄2 (13) 3 ⁄8 (86)
3 5 3 5 1
2 1 ⁄8 (35) 2 ⁄16 (59) 1 ⁄8 (35) 3 ⁄8 (92) 1 (25) 4 ⁄2 (114)
13 1 5 1 5
3 1 ⁄16 (46) 3 ⁄16 (78) 1 ⁄8 (41) 5 (127) 1 ⁄8 (29) 6 ⁄16 (160)
1 7 7 3 13 5
4 2 ⁄4 (57) 3 ⁄8 (98) 1 ⁄8 (48) 6 ⁄8 (162) 1 ⁄16 (46) 8 ⁄8 (219)
B B
1 3 7
6 3 ⁄2 (89) 5 (127) 1 ⁄4 (44) 8 ⁄16 (214)
B B
1 3 3
8 4 ⁄2 (114) 6 (152) 2 ⁄8 (60) 11 ⁄4 (298)
C C C C B B
1 11 7
10 5 ⁄2 (140) 9 ⁄16 (246) 2 ⁄16 (62) 13 (330)
C C C C B B
9 7 3
12 6 ⁄16 (167) 11 (279) 2 ⁄8 (73) 15 ⁄8 (391)
A
Non-reducing double sanitary tees are for vent use only.
B
Combination wye and ⁄8 bend is assembled from two standard fittings.
C
10 in. and 12 in. fittings dimensions are minimum.
D3311 − 11 (2016)
TABLE 4 Reducing Sanitary Tees, 45° Wyes, Combination Wyes, and ⁄8 Bends, in. (mm)
Combination Wye and ⁄8 Bend
A
Sanitary Tee, Reducing Single and Double 45° Wye, Reducing Single and Double
Reducing Single and Double
Nominal Pipe Size
G1 G2 G3 G4 G1 G2 G3 G1 G2 G3
B B B B
1 1 1 11 1 11 11
1 ⁄2 by 1 ⁄4 by 1 ⁄4 ⁄16 (17) 1 ⁄2 (38) 1 ⁄16 (43) 1 ⁄16 (43) — — — — — —
1 1 1 3 3 3
1 ⁄2 by 1 ⁄4 by 1 ⁄2 1 (25) 1 ⁄4 (44) 1 ⁄4 (44) 1 ⁄4 (44) — — — — — —
1 1 1 13 11 13 13 1 1 3
1 ⁄2 by 1 ⁄2 by 1 ⁄4 ⁄16 (21) 1 ⁄16 (43) 1 ⁄16 (46) 1 ⁄16 (46) — — — ⁄2 (13) 3 ⁄4 (83) 3 ⁄16 (81)
1 1 3 15 3 3
2 by 1 ⁄4 by 1 ⁄2 1 ⁄16 (30) 1 ⁄16 (49) 2 ⁄16 (56) 2 ⁄16 (56) — — — — — —
B B B
1 1 3 15 3 3 3 13 15 9 11 5
2 by 1 ⁄2 by 1 ⁄2 1 ⁄16 (30) 1 ⁄16 (49) 2 ⁄16 (56) 2 ⁄16 (56) ⁄4 (19) 2 ⁄16 (71) 2 ⁄16 (75) ⁄16 (14) 3 ⁄16 (94) 3 ⁄8 (92)
1 3 5 5 5 B 1 B 3 B 1 1
2 by 1 ⁄2 by 2 1 ⁄8 (35) 2 ⁄16 (59) 2 ⁄16 (59) 2 ⁄16 (50) 1 (25) 3 ⁄2 (89) 3 ⁄8 (86) 1 (25) 4 ⁄2 (114) 4 ⁄2 (114)
1 3 15 3 3
2 by 2 by 1 ⁄4 1 ⁄16 (30) 1 ⁄16 (49) 2 ⁄16 (56) 2 ⁄16 (56) — — — — — —
1 3 15 3 3 1 5 7 9 11 5
2 by 2 by 1 ⁄2 1 ⁄16 (30) 1 ⁄16 (49) 2 ⁄16 (56) 2 ⁄16 (56) 1 ⁄16 (27) 3 ⁄16 (84) 3 ⁄16 (87) ⁄16 (14) 3 ⁄16 (170) 3 ⁄8 (92)
1 15 3 9 9 1 3 5 1 7 1
3 by 3 by 1 ⁄2 ⁄16 (24) 1 ⁄4 (44) 2 ⁄16 (65) 2 ⁄16 (65) ⁄2 (13) 3 ⁄4 (95) 4 ⁄16 (110) ⁄8 (3) 3 ⁄16 (87) 4 ⁄4 (108)
3 1 7 7 7 1 5 7 3 5
3 by 3 by 2 1 ⁄16 (30) 2 ⁄8 (54) 2 ⁄8 (73) 2 ⁄8 (73) ⁄8 (22) 4 ⁄8 (105) 4 ⁄8 (117) ⁄16 (11) 4 ⁄4 (121) 5 ⁄16 (135)
B B B B
1 15 1 7 1
3 by 3 by 2 by 1 ⁄2 ⁄16 (24) 2 ⁄16 (52) 2 ⁄16 (62) 2 ⁄2 (64) — — — — — —
B B B B B B B
1 1 1 1 5 15
4 by 4 by 1 ⁄2 1 ⁄16 (27) 2 (51) 3 ⁄4 (83) 3 ⁄4 (83) 0 (0) 3 ⁄16 (84) 3 ⁄16 (100) — — —
1 1 5 5 3 11 9 5 3 7
4 by 4 by 2 1 ⁄8 (29) 2 ⁄16 (52) 3 ⁄16 (84) 3 ⁄16 (84) ⁄8 (10) 4 ⁄16 (119) 5 ⁄16 (141) ⁄16 (8) 4 ⁄4 (121) 5 ⁄8 (149)
3 9 9 1 9 1 3 7
4 by 4 by 3 1 ⁄4 (44) 3 (76) 3 ⁄16 (90) 3 ⁄16 (90) 1 ⁄16 (27) 5 ⁄16 (141) 6 (152) 1 ⁄16 (27) 6 ⁄8 (162) 6 ⁄8 (175)
3 B 15 B 7 B 11 B 13 B 13 B
6 by 6 by 3 — — — — ⁄16 (5) 6 ⁄16 (176) 7 ⁄16 (189) ⁄16 (17) 7 ⁄16 (198) 8 ⁄16 (224)
B B B B B B B B B B
3 5 5 5 3 11 7 9 13 15
6 by 6 by 4 2 ⁄16 (56) 3 ⁄8 (92) 4 ⁄16 (110) 4 ⁄16 (110) ⁄16 (5) 6 ⁄16 (170) 7 ⁄16 (189) ⁄16 (14) 7 ⁄16 (198) 8 ⁄16 (227)
C C C
5 1 1 1 3 5 5
8 by 8 by 4 2 ⁄8 (67) 4 ⁄8 (105) 5 ⁄4 (133) 5 ⁄4 (133) ⁄8 (10) 7 ⁄8 (194) 8 ⁄8 (219)
C C C
9 13 1 1 1 13
8 by 8 by 6 3 ⁄16 (90) 4 ⁄16 (122) 5 ⁄2 (140) 5 ⁄2 (140) 1 (25) 9 ⁄2 (241) 9 ⁄16 (249)
B B B C C C
1 11 3
10 by 10 by 4 . . . . -1 ⁄2 (-38) 8 ⁄16 (221) 10 ⁄8 (264)
B B C C C
1 1
10 by 10 by 6 . . . . 0 10 ⁄8 (257) 11 ⁄4 (286)
B B B C C C
1 1 7
10 by 10 by 8 . . . . 1 ⁄4 (32) 11 ⁄2 (202) 12 ⁄16 (316)
7 B 3 B 13 B C C C
12 by 12 by 4 . . . . -2 ⁄16 (-62) 9 ⁄4 (248) 11 ⁄16 (284)
B B B C C C
3 3 11
12 by 12 by 6 . . . . - ⁄4 (-19) 11 ⁄16 (284) 11 ⁄16 (297)
B B B C C C
1 9 7
12 by 12 by 8 . . . . ⁄2 (13) 12 ⁄16 (319) 13 ⁄8 (352)
B B B C C C
1 15
12 by 12 by 10 . . . . 1 ⁄8 (29) 14 (356) 14 ⁄16 (379)
A
Non-reducing double sanitary tees are for vent use only.
B
This dimension is a minimum with no upper maximum limit.
C
Combination Wye and ⁄8 bend is assembled from two standard fittings.
TABLE 5 60° Wyes, Single, and Double, in. (mm) TABLE 6 Fixture Tees, in. (mm)
Nominal Pipe Size G1 G2 G3
1 9 3 1
1 ⁄2 1 ⁄16 (40) 1 ⁄16 (30) 1 ⁄4 (32)
1 1 7 3 1
2 by 1 ⁄2 by 1 ⁄2 1 ⁄16 (37) 1 ⁄16 (30) 1 ⁄4 (32)
1 7 5 1
2 by 2 by 1 ⁄2 1 ⁄16 (37) 1 ⁄16 (33) 1 ⁄4 (32)
Nominal Pipe
GN GJ
Size
1 1 7
1 ⁄2 1 ⁄8 (40) 2 ⁄8 (73)
3 5
2 1 ⁄8 (37) 3 ⁄8 (92)
3 1 ⁄8 (37) 5 (127)
D3311 − 11 (2016)
TABLE 7 Cleanout Tees, in. (mm) TABLE 10 Molded Nipples, in. (mm)
Nominal
Nominal Pipe
OD ID Length
G I
Pipe Size
Size
1 1
1 ⁄2 1.900 1.500 ⁄2-in. increments from
1 3 5
1 ⁄2 1 ⁄16 (30) ⁄8 (16)
2 2.375 1.939 close to 18 in. long
1 5
2 1 ⁄2 (38) ⁄8 (16)
3 3.500 2.900
7 3
3 1 ⁄8 (48) ⁄4 (19)
1 7
4 2 ⁄2 (64) ⁄8 (22)
1 A 15 A
6 3 ⁄2 (89) ⁄16 (33)
A A
9 1
8 4 ⁄16 (102) 1 ⁄2 (38)
TABLE 11 Vent Tees and ⁄4 Bend Vents, in. (mm)
A
6 in. and 8 in. fittings dimensions are minimum.
TABLE 8 Reducing Cleanout Tees, in. (mm)
Nominal Pipe
Vent Tee ⁄4 Bend Vent
Size
1 ⁄4 1 (25) 1 (25)
1 3 3
1 ⁄2 1 ⁄16 (30) 1 ⁄16 (30)
1 1
2 1 ⁄2 (38) 1 ⁄2 (38)
7 7
3 1 ⁄8 (48) 1 ⁄8 (48)
Nominal Pipe
1 1
4 2 ⁄2 (64) 2 ⁄2 (64)
GN, min GJ, min I, min
Size
A A
1 1
6 3 ⁄2 (89) 3 ⁄2 (89)
3 1 3 A A
1 1
10 by 10 by 8 5 ⁄16 (132) 5 ⁄2 (140) 1 ⁄4 (44)
8 4 ⁄2 (114) 4 ⁄2 (89)
1 11 A A
13 13
12 by 12 by 8 6 (152) 5 ⁄2 1 ⁄16 (43)
10 5 ⁄16 (148) 5 ⁄16 (148)
A A
7 7
12 6 ⁄8 (175) 6 ⁄8 (175)
A
6 in., 8 in., 10 in., and 12 in. fitting dimensions are minimum.
TABLE 9 60° Reducing Wyes, Single and Double, in. (mm)
Nominal Pipe
G1 G2 G3
Size
1 1 7 7
2 by 2 by 1 ⁄2 1 ⁄16 (27) 3 ⁄16 (87) 3 ⁄16 (87)
1 1 3 5
3 by 3 by 1 ⁄2 ⁄2 (13) 3 ⁄4 (95) 4 ⁄16 (110)
7 1 5
3 by 3 by 2 ⁄8 (22) 4 ⁄8 (105) 4 ⁄8 (117)
D3311 − 11 (2016)
TABLE 12 Reducing Vent Tees, Single, and Double, in. (mm)
GJ, min
Nominal Pipe Size GN, min
1 1 3 1
2 by 1 ⁄2 by 1 ⁄2 1 ⁄16 (30) 1 ⁄2 (38)
1 3 1
2 by 2 by 1 ⁄2 1 ⁄16 (30) 1 ⁄2 (38)
1 3 7
3 by 3 by 1 ⁄2 1 ⁄16 (30) 1 ⁄8 (48)
1 7
3 by 3 by 2 1 ⁄2 (38) 1 ⁄8 (48)
1 7
6 by 6 by 4 2 ⁄2 (64) 3 ⁄16 (87)
1 1
8 by 8 by 4 2 ⁄2 (64) 4 ⁄2 (114)
5 1
8 by 8 by 6 3 ⁄8 (92) 4 ⁄2 (114)
5 7
10 by 10 by 4 3 ⁄16 (84) 5 ⁄8 (149)
15 7
10 by 10 by 6 3 ⁄16 (100) 5 ⁄8 (149)
1 7
10 by 10 by 8 3 ⁄2 (89) 5 ⁄8 (140)
1 15
12 by 12 by 4 3 ⁄2 (89) 6 ⁄16 (176)
1 15
12 by 12 by 6 4 ⁄2 (114) 6 ⁄16 (176)
7 15
12 by 12 by 8 4 ⁄8 (124) 6 ⁄16 (176)
1 1
12 by 12 by 10 6 ⁄2 (165) 7 ⁄2 (190)
TABLE 13 Pipe Increasers, in. (mm)
Nominal N, min
Pipe Size
1 1 13
1 ⁄4 by 1 ⁄2 ⁄32 (10)
1 17
1 ⁄2 by 2 ⁄32 (13)
1 3
1 ⁄2 by 3 1 ⁄32 (28)
2 by 3 ⁄8 (22)
2 by 4 1 ⁄8 (35)
3 by 4 ⁄16 (24)
3 by 6 1 ⁄16 (49)
4 by 6 1 ⁄16 (30)
4 by 8 1 ⁄8 (41)
4 by 10 2 ⁄16 (56)
6 by 8 ⁄4 (19)
6 by 10 1 ⁄16 (40)
6 by 12 2 ⁄8 (60)
8 by 10 1 ⁄16 (33)
8 by 12 1 ⁄16 (46)
10 by 12 1 ⁄4 (32)
D3311 − 11 (2016)
TABLE 14 Trap Adapters, in. (mm)
Without stopStop With Stop
Nominal N, min A, min
Pipe Size
1 3
1 ⁄4 ⁄16 (5) 1.250 (32)
1 3
1 ⁄2 ⁄16 (5) 1.500 (38)
2 ⁄16 (5) 2.000 (51)
1 1 3
1 ⁄4 by 1 ⁄2 ⁄16 (5) 1.250 (32)
TABLE 15 Hubs, in. (mm)
Nominal
A C N AJ CJ N
Pipe Size
3 3
2 . . . . . . . . . 2.94 (74.7) 2 ⁄8 (60) ⁄8 (10)
11 5 5 7
3 3.448 (87.58) 1 ⁄16 (43) ⁄16 (8) 3.94 (100.1) 2 ⁄8 (67) ⁄16 (11)
15 11 7 1
4 4.493 (114.12) 1 ⁄16 (49) ⁄32 (9) 4.94 (125.5) 2 ⁄8 (73) ⁄2 (13)
15 5 7 7
Reducing 4 by 3 4.493 (114.12) 1 ⁄16 (49) ⁄16 (8) 4.94 (125.5) 2 ⁄8 (73) ⁄16 (11)
D3311 − 11 (2016)
TABLE 16 Spigots, in. (mm)
M
Nominal
L2, min L1, min L3, min AN
Pipe Size
max min
1 5 3
2 3 ⁄2 (89) 4 ⁄8 (117) ⁄8 (10) 2.75 (69.9) 2.63 (66.8) 2.00 (50.8)
3 5 3
3 3 ⁄4 (95) 5 ⁄8 (143) ⁄8 (10) 3.88 (98.6) 3.63 (92.2) 3.00 (76.2)
1 3
4 4 (102) 6 ⁄8 (156) ⁄8 (10) 4.88 (124.0) 4.63 (117.6) 4.00 (101.6)
TABLE 17 Reducing Spigots, in. (mm)
M
Nominal
L2 min L1 min L3 min AJ
min
Pipe Size
max
1 1 1 3
2 by 1 ⁄2 3 ⁄2 (89) 4 ⁄4 (108) ⁄8 (10) 2.75 (69.9) 2.63 (66.8) 2.00 (50.8)
1 3 1 3
3 by 1 ⁄2 3 ⁄4 (95) 4 ⁄2 (114) ⁄8 (10) 3.88 (98.6) 3.63 (92.2) 3.00 (76.2)
3 5 3
3 by 2 3 ⁄4 (95) 4 ⁄8 (117) ⁄8 (10) 3.88 (98.6) 3.63 (92.2) 3.00 (76.2)
7 3
4 by 2 4 (102) 4 ⁄8 (124) ⁄8 (10) 4.88 (124.0) 4.63 (117.6) 4.00 (101.6)
1 3
4 by 3 4 (102) 5 ⁄2 (140) ⁄8 (10) 4.88 (124.0) 4.63 (117.6) 4.00 (101.6)
D3311 − 11 (2016)
TABLE 18 P Traps, in. (mm)
Nominal
min GJ min GGJ min GGN min GN min R
Pipe Size
1 1 3 3 5
1 ⁄4 4 ⁄8 (105) 3 ⁄8 (86) 3 (76) 1 ⁄8 (35) 1 ⁄8 (41)
1 7 5 3 5
1 ⁄2 4 ⁄32 (107) 3 ⁄8 (92) 3 (76) 1 ⁄8 (35) 1 ⁄8 (41)
1 1 1 1
2 7 ⁄4 (184) 4 ⁄16 (103) 5 (127) 2 ⁄4 (57) 2 ⁄2 (64)
7 5 1 5 1
3 8 ⁄16 (214) 6 ⁄16 (160) 6 ⁄4 (159) 2 ⁄8 (67) 3 ⁄8 (79)
13 7 1 7 1
4 10 ⁄16 (275) 7 ⁄8 (200) 8 ⁄16 (205) 3 ⁄16 (87) 4 ⁄16 (103)
3 3 3 3 3
6 17 ⁄4 (451) 12 ⁄4 (324) 11 ⁄4 (298) 4 ⁄4 (121) 6 ⁄8 (162)
TABLE 19 Double Fixture Fitting, in. (mm)
Nominal Pipe Size G1 G2 G3 G4
1 3 9 7 7
1 ⁄2 ⁄8 (10) 3 ⁄16 (90) 2 ⁄16 (62) 2 ⁄16 (62)
3 9 1 1
2 ⁄8 (10) 4 ⁄16 (116) 3 ⁄16 (78) 3 ⁄16 (78)
1 3 1 1
3 ⁄2 (13) 6 ⁄4 (171) 4 ⁄2 (114) 4 ⁄2 (114)
Reducing:
1 1 1 3 9 7 7
2 by 1 ⁄2 by 1 ⁄2 by 1 ⁄2 ⁄8 (10) 3 ⁄16 (90) 2 ⁄16 (62) 2 ⁄16 (62)
1 3 9 1 1
2 by 1 ⁄2 by 2 by 2 ⁄8 (10) 4 ⁄16 (116) 3 ⁄16 (78) 3 ⁄16 (78)
1 1 3 9 1 1
2 by 1 ⁄2 by 2 by 1 ⁄2 ⁄8 (10) 4 ⁄16 (116) 3 ⁄16 (78) 3 ⁄16 (78)
D3311 − 11 (2016)
TABLE 20 Double Fixture Fitting, in. (mm)
Interchanges with Double Fixture Fittings
Double Fixture Fitting
Nominal
Pipe Size
G1 G2 G3 G4 R1 R2
1 3 1 11 11 5 5
1 ⁄2 ⁄8 (10) 3 ⁄8 (79) 2 ⁄16 (68) 2 ⁄16 (68) 3 ⁄8 (92) 3
...