ASTM D2729-03
(Specification)Standard Specification for Poly(Vinyl Chloride) (PVC) Sewer Pipe and Fittings
Standard Specification for Poly(Vinyl Chloride) (PVC) Sewer Pipe and Fittings
ABSTRACT
This specification covers requirements and test methods for materials, dimensions, workmanship, chemical resistance, and joint tightness of poly (vinyl chloride) (PVC) sewer and drain pipe and fittings. The pipe shall be made from virgin cell 12164 with a certain minimum tensile strength, 12454 or 12454 poly(vinyl chloride) compounds. The fittings shall be made from virgin poly(vinyl chloride) compounds of cell classification PVC 12454, PVC 12454, or PVC 13343. Compounds that have different cell classification because one or more properties are superior to those of the specified compounds are also acceptable. In order to determine the overall performance of the pipes and fittings, the following tests shall be done: flattening test, joint tightness test, and perforation test. The pipe and fittings shall be homogeneous throughout and free from visible cracks, holes, foreign inclusions, or other injurious defects. The pipe shall be as uniform as commercially practical in color, opacity, density, and other physical properties.
SCOPE
1.1 This specification covers requirements and test methods for materials, dimensions, workmanship, chemical resistance, and joint tightness of poly(vinyl chloride) (PVC) sewer and drain pipe and fittings. Four-inch perforated pipe is also covered; the joint tightness test is not applicable for this product. A form of marking to indicate compliance with this specification is also included.
1.2 The text of this specification references notes, footnotes, and appendixes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the specification.
1.3 The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are for information only.
1.4 The following precautionary caveat pertains only to the test methods portion, Section 6, of this specification: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
General Information
Relations
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
AnAmerican National Standard
Designation: D2729 – 03
Standard Specification for
1
Poly(Vinyl Chloride) (PVC) Sewer Pipe and Fittings
This standard is issued under the fixed designation D2729; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the Department of Defense.
1. Scope D2122 Test Method for Determining Dimensions of Ther-
moplastic Pipe and Fittings
1.1 This specification covers requirements and test methods
D2152 Test Method for Adequacy of Fusion of Extruded
for materials, dimensions, workmanship, chemical resistance,
Poly(Vinyl Chloride) (PVC) Pipe and Molded Fittings by
and joint tightness of poly(vinyl chloride) (PVC) sewer and
Acetone Immersion
drain pipe and fittings. Four-inch perforated pipe is also
D2321 Practice for Underground Installation of Thermo-
covered; the joint tightness test is not applicable for this
plastic Pipe for Sewers and Other Gravity-Flow Applica-
product. A form of marking to indicate compliance with this
tions
specification is also included.
D2412 Test Method for Determination of External Loading
1.2 Thetextofthisspecificationreferencesnotes,footnotes,
Characteristics of Plastic Pipe by Parallel-Plate Loading
and appendixes which provide explanatory material. These
D2444 Test Method for Determination of the Impact Resis-
notesandfootnotes(excludingthoseintablesandfigures)shall
tance of Thermoplastic Pipe and Fittings by Means of a
not be considered as requirements of the specification.
Tup (Falling Weight)
1.3 The values stated in inch-pound units are to be regarded
D2564 Specification for Solvent Cements for Poly(Vinyl
as the standard. The values given in parentheses are for
Chloride) (PVC) Plastic Piping Systems
information only.
F412 Terminology Relating to Plastic Piping Systems
1.4 The following precautionary caveat pertains only to the
2.2 Federal Standard:
test methods portion, Section 6, of this specification: This
3
Fed. Std. No. 123 Marking for Shipment (Civil Agencies)
standard does not purport to address all of the safety concerns,
2.3 Military Standard:
if any, associated with its use. It is the responsibility of the user
3
MIL-STD-129 Marking for Shipment and Storage
of this standard to establish appropriate safety and health
practices and determine the applicability of regulatory limita-
3. Terminology
tions prior to use.
3.1 Definitions—Definitions used are in accordance with
2. Referenced Documents Terminology F412, and abbreviations are in accordance with
2
Terminology D1600, unless otherwise specified.The abbrevia-
2.1 ASTM Standards:
tion for poly(vinyl chloride) is PVC.
D618 Practice for Conditioning Plastics for Testing
3.1.1 Pipe having perforations is called perforated pipe;
D1600 Terminology for Abbreviated Terms Relating to
without perforations it is called standard pipe.
Plastics
D1784 Specification for Rigid Poly(Vinyl Chloride) (PVC)
4. Materials
Compounds and Chlorinated Poly(Vinyl Chloride)
4.1 General—The pipe shall be made from virgin cell
(CPVC) Compounds
12164 with a minimum tensile strength of 4000 psi (28 MPa),
12454 or 12454 poly(vinyl chloride) compounds, as defined
1
This specification is under the jurisdiction ofASTM Committee F17 on Plastic
and described in Specification D1784. The fittings shall be
Piping Systems and is the direct responsibility of Subcommittee F17.62 on Sewer.
made from virgin poly(vinyl chloride) compounds of cell
Current edition approvedAug. 10, 2003. Published September 2003. Originally
classification PVC 12454, PVC 12454, or PVC 13343. Com-
approved in 1968. Last previous edition approved in 1996 as D2729–96a. DOI:
pounds that have different cell classification because one or
10.1520/D2729-03.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
3
Standards volume information, refer to the standard’s Document Summary page on AvailablefromStandardizationDocumentsOrderDesk,Bldg.4SectionD,700
the ASTM website. Robbins Ave., Philadelphia, PA 19111-5094, Attn: NPODS.
Copyright ©ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA19428-2959, United States.
1
---------------------- Page: 1 ----------------------
D2729 – 03
TABLE 2 Diameters and Tolerances for PVC Sewer and Drain
more properties are superior to those of the specified com-
Pipe
pounds are also acceptable.
Nominal
4.2 Rework Material—The manufacturer shall use only his
Average Outside
Pipe Size,
Diameter, mm (in.)
own clean pipe or fitting rework material; the pipe and fittings
in.
produc
...