Standard Specification for Faced Rigid Cellular Polyisocyanurate Thermal Insulation Board

SCOPE
1.1 This specification covers the general requirements for faced thermal insulation boards composed of rigid cellular polyisocyanurate surfaced with other materials. The insulation boards are intended for use at temperatures between -40 and 200°F (-40 and 93°C). This specification does not cover cryogenic applications. Consult the manufacturer for specific recommendations and properties in cryogenic conditions. For specific applications, the actual temperature limits shall be agreed upon by the manufacturer and the purchaser.
1.2 This standard is intended to apply to rigid cellular polyurethane-modified polyisocyanurate thermal insulation board products that are commercially acceptable as non-structural panels useful in building construction. The term polyisocyanurate encompasses the term polyurethane. For engineering and design purposes, users should follow specific product information provided by board manufacturers regarding physical properties, system design considerations and installation recommendations.
1.3 The use of thermal insulation materials covered by this specification may be regulated by building codes, or other agencies that address fire performance, or both. The fire performance of the material should be addressed through standard fire test methods established by the appropriate governing documents.
1.4 The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are for information only and may be approximate. For conversion to metric units other than those contained in this standard, refer to IEEE/ASTM SI 10.
1.5 The following safety hazards caveat pertains only to the test methods, Section 11, in this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
30-Nov-2003
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM C1289-03 - Standard Specification for Faced Rigid Cellular Polyisocyanurate Thermal Insulation Board
English language
9 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: C 1289 – 03
Standard Specification for
Faced Rigid Cellular Polyisocyanurate Thermal Insulation
1
Board
This standard is issued under the fixed designation C1289; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
1. Scope 2. Referenced Documents
1.1 This specification covers the general requirements for 2.1 The following documents, of the issue in effect on the
faced thermal insulation boards composed of rigid cellular date of material purchase, form a part of this specification to
polyisocyanurate surfaced with other materials. The insulation the extent specified herein:
2
boards are intended for use at temperatures between−40 and 2.2 ASTM Standards:
200°F (−40 and 93°C). This specification does not cover C168 Terminology Relating to Thermal Insulating Materi-
cryogenic applications. Consult the manufacturer for specific als
recommendations and properties in cryogenic conditions. For C177 Test Method for Steady-State Heat Flux Measure-
specific applications, the actual temperature limits shall be ments and Thermal Transmission Properties by Means of
agreed upon by the manufacturer and the purchaser. the Guarded-Hot-Plate Apparatus
1.2 This standard is intended to apply to rigid cellular C203 Test Methods for Breaking Load and Flexural Prop-
polyurethane-modified polyisocyanurate thermal insulation erties of Block Type Thermal Insulation
board products that are commercially acceptable as non- C208 Specification for Cellulosic Fiber Insulating Board
structural panels useful in building construction. The term C209 Test Methods for Cellulosic Fiber Insulating Board
polyisocyanurate encompasses the term polyurethane. For C303 Test Method for Density of Preformed Block-Type
engineering and design purposes, users should follow specific Thermal Insulation
product information provided by board manufacturers regard- C390 Criteria for Sampling and Acceptance of Preformed
ing physical properties, system design considerations and Thermal Insulation Lots
installation recommendations. C518 Test Method for Steady-State Heat Flux Measure-
1.3 The use of thermal insulation materials covered by this ments and Thermal Transmission Properties by Means of
specification may be regulated by building codes, or other the Heat Flow Meter Apparatus
agencies that address fire performance, or both. The fire C550 Test Method for MeasuringTrueness and Squareness
performance of the material should be addressed through of Rigid Block Thermal Insulation
standard fire test methods established by the appropriate C728 Specification for Perlite Thermal Insulation Board
governing documents. C 1045 Practice for Calculating Thermal Transmission
1.4 Thevaluesstatedininch-poundunitsaretoberegarded Properties from Steady-State Heat Flux Measurements
as the standard. The values given in parentheses are for C1058 Practice for Selecting Temperatures for Evaluating
information only and may be approximate. For conversion to and Reporting Thermal Properties of Thermal Insulation
metricunitsotherthanthosecontainedinthisstandard,referto C1114 TestMethodforSteady-StateThermalTransmission
IEEE/ASTM SI 10. Properties by Means of the Thin-Heater Apparatus
1.5 The following safety hazards caveat pertains only to the C1303 Test Method for Estimating the Long-Term Change
test methods, Section 11, in this specification. This standard in the Thermal Resistance of Unfaced Rigid Closed Cell
does not purport to address all of the safety concerns, if any, Plastic Foams by Slicing and Scaling Under Controlled
associated with its use. It is the responsibility of the user of this Laboratory Conditions
standard to establish appropriate safety and health practices C1363 Test Method for Thermal Performance of Building
and determine the applicability of regulatory limitations prior Assemblies by Means of a Hot Box Apparatus
to use. D226 Specification for Asphalt-Saturated Organic Felt
Used in Roofing and Waterproofing
1
This specification is under the jurisdiction of ASTM Committee C16 on
Thermal Insulation and is the direct responsibility of Subcommittee C16.22 on 2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Organic and Nonhomogeneous Inorganic Thermal Insulations.
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Current edition approved Dec. 1, 2003. Published January 2004. Originally
Standards volume information, refer to the standard’s Document Summary page on
approved in 1995. Last previous edition approved in 2002 as C1289–02.
the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Cons
...