Standard Practice for Joint Acceptance Testing of Installed Precast Concrete Pipe Sewer Lines (Metric)

SCOPE
1.1 This practice covers procedures for testing the joints of installed precast concrete pipe sewer lines, when using either air or water under low pressure to demonstrate the integrity of the joint and the construction procedures. This practice is used for testing 675-mm and larger diameter precast concrete sewer lines utilizing rubber gasket sealed joints.
1.2 This practice is the metric companion of Practice C 1103.
Note 1—The owner shall specify the following: who will conduct, observe, and furnish labor, material, and measuring devices and pay for the tests; who is responsible for determining local ground conditions; and whether an air or water test is to be used.
Note 2—The user of this practice is advised that test criteria presented in this practice are similar to those in general use. Pipe 600-mm diameter and smaller shall be accepted by infiltration or exfiltration testing utilizing Practice C 969M or by low pressure air testing utilizing Practice C 924M. Pipe greater than 600-mm diameter shall be accepted by infiltration or exfiltration testing utilizing C 969M.
Note 3—The user is advised that no correlation has been found between air loss and water leakage.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. Specific safety precautions are given in Section 6.

General Information

Status
Historical
Publication Date
09-Aug-2002
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM C1103M-02 - Standard Practice for Joint Acceptance Testing of Installed Precast Concrete Pipe Sewer Lines (Metric)
English language
2 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superceded and replaced by a new version or discontinued.
Contact ASTM International (www.astm.org) for the latest information.
Designation: C 1103M – 02
METRIC
Standard Practice for
Joint Acceptance Testing of Installed Precast Concrete Pipe
1
Sewer Lines [Metric]
This standard is issued under the fixed designation C 1103M; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
1. Scope C 969M Practice for Infiltration and Exfiltration Acceptance
Testing of Installed Precast Concrete Pipe Sewer Lines
1.1 This practice covers procedures for testing the joints of
2
[Metric]
installed precast concrete pipe sewer lines, when using either
air or water under low pressure to demonstrate the integrity of
3. Terminology
the joint and the construction procedures. This practice is used
3.1 Definitions—For definitions of terms relating to con-
for testing 675-mm and larger diameter precast concrete sewer
crete pipe, see Terminology C 822.
lines utilizing rubber gasket sealed joints.
1.2 This practice is the metric companion of Practice
4. Summary of Practice
C 1103.
4.1 The joint in the sewer line to be tested is covered on the
NOTE 1—The owner shall specify the following: who will conduct,
inside of the pipe by a ring with two end element sealing tubes.
observe, and furnish labor, material, and measuring devices and pay for
Air or water, at low pressure, is introduced through a connec-
the tests; who is responsible for determining local ground conditions; and
tion on the ring into the annular space between the ring and
whether an air or water test is to be used.
joint. The amount of air, or water, loss is used to determine the
NOTE 2—The user of this practice is advised that test criteria presented
acceptability of the installed sewer line.
in this practice are similar to those in general use. Pipe 600-mm diameter
and smaller shall be accepted by infiltration or exfiltration testing utilizing
5. Significance and Use
Practice C 969M or by low pressure air testing utilizing Practice C 924M.
Pipe greater than 600-mm diameter shall be accepted by infiltration or
5.1 This is not a routine test. The values recorded are
exfiltration testing utilizing C 969M.
applicable only to the sewer being tested and at the time of
NOTE 3—The user is advised that no correlation has been found
testing.
between air loss and water leakage.
1.3 This standard does not purport to address all of the 6. Safety Precautions
safety concerns, if any, associated with its use. It is the
6.1 The use of compressed air is dangerous if a sewer line is
responsibility of the user of this standard to establish appro-
not prepared properly and proper procedures are not followed.
priate safety and health practices and determine the applica-
6.2 It is imperative that all pressures be relieved completely
bility of regulatory limitations prior to use. Specific safety
before the test apparatus is loosened for removal.
precautions are given in Section 6.
6.3 Pressurizing lines for the two end element sealing tubes
shall be separate from the lines for pressurizing the void
2. Referenced Documents
volume created by the joint test apparatus. The pressures
2.1 ASTM Standards:
required to seal the end element tubes shall be as specified by
C 822 Terminology Relating to Concrete Pipe and Related
the apparatus manufacturer, and are greater than the pressure
2
Products
required to test the joint. The line for pressurizing the void
C 924M Practice for Testing Concrete Pipe Sewer Lines by
volume shall include a 42 kPa pressure relief device to reduce
2
Low-Pressure Air Test Method [Metric]
hazards and avoid overpressurization.
7. Preparation of the Sewer Joint
1
This practice is under the jurisdiction of ASTM Committee C13 on Concrete
7.1 Check the size of access openings to ensure that the test
Pipe and is the direct responsibility of Subcommittee C13.09 on Methods of Test.
Current edition approved August 10, 2002. Published October 2002. Originally apparatus will fit in the sewer line.
published as C 1103M–89. Last previous edition C 1103–94(2002).
2
Annual Book of ASTM Standards, Vol 04.05.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
NOTICE: This standard has either been superceded and replaced by a new version or discontinued.
Contact ASTM International (www.astm.org) for the latest information.
C1103M–02
continuous pumping of air or water is not required, and any variances in
7.2 Clean the joint and interior joint surfaces to eliminate
test equipment and joint space will be negated. The reservoir shall have a
debris prior to wetting and testing.