ASTM C933-18
(Specification)Standard Specification for Welded Wire Lath
Standard Specification for Welded Wire Lath
ABSTRACT
This specification covers welded wire lath, flat or self-furring, with or without backing, designed for use as a base to receive Portland cement-based interior plaster and exterior stucco. Welded wire lath shall be fabricated from cold-drawn, galvanized steel wire, conforming to the referenced specification. The wire shall be zinc-coated and the backling shall be attached to the lath to prevent accidental removal during shipping, handling, or installation. The thickness of the embedment of the lath and plaster shall be measured from the back plane of the back wire, exclusive for furring, to the backing or surface of the substrate.
SCOPE
1.1 This specification covers welded wire lath, flat or self-furring, with or without backing, designed for use as a base to receive portland cement-based interior plaster and exterior stucco.
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.3 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
General Information
Relations
Buy Standard
Standards Content (Sample)
This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
Designation: C933 −18
Standard Specification for
1
Welded Wire Lath
This standard is issued under the fixed designation C933; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope* 4. Materials and Manufacture
4.1 Welded wire lath shall be fabricated from not less than
1.1 This specification covers welded wire lath, flat or
0.0625 in. (1.588 mm), cold-drawn, galvanized steel wire,
self-furring,withorwithoutbacking,designedforuseasabase
to receive portland cement-based interior plaster and exterior conforming to Specification A641/A641M.
4.1.1 Diameter tolerance for galvanized wire shall be in
stucco.
accordance with Specification A641/A641M.
1.2 The values stated in inch-pound units are to be regarded
4.1.2 The wire shall be zinc-coated (galvanized) in accor-
as standard. The values given in parentheses are mathematical
dance with Specification A641/A641M.
conversions to SI units that are provided for information only
4.1.3 The factory-attached water-resistive barrier shall con-
and are not considered standard.
form to Federal Specification UU-B-790 or ASTM Specifica-
1.3 This international standard was developed in accor-
tion E2556/E2556M. The water-resistive barrier shall be either
dance with internationally recognized principles on standard-
absorptive or water resistant. The water-resistive barrier shall
ization established in the Decision on Principles for the
have a bursting strength of not less than that required to
Development of International Standards, Guides and Recom-
maintain integrity under normal hand- or machine-application
mendations issued by the World Trade Organization Technical
pressures.
Barriers to Trade (TBT) Committee.
4.1.4 The factory-attached water-resistive barrier shall be
attached to the lath to prevent accidental removal during
2. Referenced Documents
shipping, handling or installation. Attachment of the water-
2
2.1 ASTM Standards:
resistive barrier shall allow lapping of wire-to-wire and water-
A641/A641M Specification for Zinc–Coated (Galvanized)
resistive barrier to water-resistive barrier of not less than one
Carbon Steel Wire
meshatendsandedgesandshallpermitfullembedment,innot
C11 Terminology Relating to Gypsum and Related Building
1
less than ⁄4 in. (6 mm) of plaster, of not less than one-half of
Materials and Systems
the total length and width of the wire.
E2556/E2556M Specification for Vapor Permeable Flexible
4.1.5 Thethicknessoftheembedmentofthelathandplaster
Sheet Water-Resistive Barriers Intended for Mechanical
shall be measured from the back plane of the back wire,
Attachment
exclusive of furring, to the water-resistive barrier or surface of
2.2 Federal Specifications:
the substrate.
UU-B-790 Building Paper, Vegetable Fiber: (Kraft,
3
5. Dimensions and Permissible Variations
Waterproofed, Water Repellent and Fire Resistant)
5.1 Openings and Stiffening:
3. Terminology
5.1.1 Lath shall be welded at all intersections of wire to
3.1 Definitions of terms used in this standard shall be in
form openings not more than 2 by 2 in. (51 by 51 mm).
accordance with Terminology C11.
5.1.2 Reinforced lath shall be permitted to be reinforced
continuously and parallel to the long dimension of the lath at
1
This specification is under the jurisdiction of ASTM Committee C11 on
intervals of not more than 6 in. (150 mm). Wires used for this
Gypsum and Related Building Materials and Systems and is the direct responsibility
purpose shall range from 0.072 to 0.1205 in. (1.9 to 3.1 mm).
of Subcommittee C11.02 on Specifications and Test Methods for Accessories and
Reduction of the size of the openings to less than 2 by 2 in. (51
Related Products.
Current edition approved Oct. 1, 2018. Published October 2018. Originally by 51 mm) shall also be permitted.
approved in 1980. Last previous edition approved in 2014 as C933 – 14. DOI:
5.1.3 Self-furring crimps on self-furring lath shall project
10.1520/C0933-18.
1
not less than ⁄4 in. (6 mm) from the plane of the back of the
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
lath.
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Standards volume information, refer to the standard’s Document Summary page on
1
5.2 Thickness—The nominal thickness shall be ⁄8 in.
the ASTM website.
3 (3.2 mm), exclusive of self-furring crimps, with a permissible
Available from Standardization Documents Order Desk, Bldg. 4 Section D, 700
1
Robbins Ave., Philadelphia,
...
This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: C933 − 14 C933 − 18
Standard Specification for
1
Welded Wire Lath
This standard is issued under the fixed designation C933; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope*
1.1 This specification covers welded wire lath, flat or self-furring, with or without backing, designed for use as a base to receive
portland cement-based interior plaster and exterior stucco.
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
1.3 This international standard was developed in accordance with internationally recognized principles on standardization
established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued
by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
2. Referenced Documents
2
2.1 ASTM Standards:
A641/A641M Specification for Zinc–Coated (Galvanized) Carbon Steel Wire
C11 Terminology Relating to Gypsum and Related Building Materials and Systems
E2556/E2556M Specification for Vapor Permeable Flexible Sheet Water-Resistive Barriers Intended for Mechanical Attachment
2.2 Federal Specifications:
3
UU-B-790 Building Paper, Vegetable Fiber: (Kraft, Waterproofed, Water Repellent and Fire Resistant)
3. Terminology
3.1 Definitions of terms used in this standard shall be in accordance with Terminology C11.
4. Materials and Manufacture
4.1 Welded wire lath shall be fabricated from not less than 0.0625 in. (1.588 mm), cold-drawn, galvanized steel wire,
conforming to Specification A641/A641M.
4.1.1 Diameter tolerance for galvanized wire shall be in accordance with Specification A641/A641M.
4.1.2 The wire shall be zinc-coated (galvanized) in accordance with Specification A641/A641M.
4.1.3 The backing factory-attached water-resistive barrier shall conform to Federal Specification UU-B-790. UU-B-790 or
ASTM Specification E2556/E2556M. The backing water-resistive barrier shall be either absorptive or water resistant. The backing
water-resistive barrier shall have a bursting strength of not less than that required to maintain integrity under normal hand- or
machine-application pressures.
4.1.4 The backing factory-attached water-resistive barrier shall be attached to the lath to prevent accidental removal during
shipping, handling or installation. Attachment of the backing water-resistive barrier shall allow lapping of wire-to-wire and
backing-to-backing water-resistive barrier to water-resistive barrier of not less than one mesh at ends and edges and shall permit
1
full embedment, in not less than ⁄4 in. (6 mm) of plaster, of not less than one-half of the total length and width of the wire.
4.1.5 The thickness of the embedment of the lath and plaster shall be measured from the back plane of the back wire, exclusive
of furring, to the backing water-resistive barrier or surface of the substrate.
1
This specification is under the jurisdiction of ASTM Committee C11 on Gypsum and Related Building Materials and Systems and is the direct responsibility of
Subcommittee C11.02 on Specifications and Test Methods for Accessories and Related Products.
Current edition approved Aug. 15, 2014Oct. 1, 2018. Published October 2014October 2018. Originally approved in 1980. Last previous edition approved in 20132014
as C933 – 13.C933 – 14. DOI: 10.1520/C0933-14.10.1520/C0933-18.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
3
Available from Standardization Documents Order Desk, Bldg. 4 Section D, 700 Robbins Ave., Philadelphia, PA 19111-5094, Attn: NPODS.
*A Summary of Changes section appears at the end of this standard
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1
---------------------- Page: 1 ----------------------
C933 − 18
5. Dimensions and Permissible Variations
5.1 Openings and Stiffening:
5.1.1 Lath shall be welded at all intersections of wire to form openings not more than 2 by 2 in. (51 mm) by 2 in. (51 mm).by
51 mm).
5.1.2 Reinfor
...
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: C933 − 18
Standard Specification for
1
Welded Wire Lath
This standard is issued under the fixed designation C933; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope* 4. Materials and Manufacture
4.1 Welded wire lath shall be fabricated from not less than
1.1 This specification covers welded wire lath, flat or
self-furring, with or without backing, designed for use as a base 0.0625 in. (1.588 mm), cold-drawn, galvanized steel wire,
conforming to Specification A641/A641M.
to receive portland cement-based interior plaster and exterior
stucco. 4.1.1 Diameter tolerance for galvanized wire shall be in
accordance with Specification A641/A641M.
1.2 The values stated in inch-pound units are to be regarded
4.1.2 The wire shall be zinc-coated (galvanized) in accor-
as standard. The values given in parentheses are mathematical
dance with Specification A641/A641M.
conversions to SI units that are provided for information only
4.1.3 The factory-attached water-resistive barrier shall con-
and are not considered standard.
form to Federal Specification UU-B-790 or ASTM Specifica-
1.3 This international standard was developed in accor-
tion E2556/E2556M. The water-resistive barrier shall be either
dance with internationally recognized principles on standard-
absorptive or water resistant. The water-resistive barrier shall
ization established in the Decision on Principles for the
have a bursting strength of not less than that required to
Development of International Standards, Guides and Recom-
maintain integrity under normal hand- or machine-application
mendations issued by the World Trade Organization Technical
pressures.
Barriers to Trade (TBT) Committee.
4.1.4 The factory-attached water-resistive barrier shall be
attached to the lath to prevent accidental removal during
2. Referenced Documents
shipping, handling or installation. Attachment of the water-
2
2.1 ASTM Standards:
resistive barrier shall allow lapping of wire-to-wire and water-
A641/A641M Specification for Zinc–Coated (Galvanized)
resistive barrier to water-resistive barrier of not less than one
Carbon Steel Wire
mesh at ends and edges and shall permit full embedment, in not
C11 Terminology Relating to Gypsum and Related Building
1
less than ⁄4 in. (6 mm) of plaster, of not less than one-half of
Materials and Systems
the total length and width of the wire.
E2556/E2556M Specification for Vapor Permeable Flexible
4.1.5 The thickness of the embedment of the lath and plaster
Sheet Water-Resistive Barriers Intended for Mechanical
shall be measured from the back plane of the back wire,
Attachment
exclusive of furring, to the water-resistive barrier or surface of
2.2 Federal Specifications:
the substrate.
UU-B-790 Building Paper, Vegetable Fiber: (Kraft,
3
5. Dimensions and Permissible Variations
Waterproofed, Water Repellent and Fire Resistant)
5.1 Openings and Stiffening:
3. Terminology
5.1.1 Lath shall be welded at all intersections of wire to
3.1 Definitions of terms used in this standard shall be in
form openings not more than 2 by 2 in. (51 by 51 mm).
accordance with Terminology C11.
5.1.2 Reinforced lath shall be permitted to be reinforced
continuously and parallel to the long dimension of the lath at
1
This specification is under the jurisdiction of ASTM Committee C11 on
intervals of not more than 6 in. (150 mm). Wires used for this
Gypsum and Related Building Materials and Systems and is the direct responsibility
purpose shall range from 0.072 to 0.1205 in. (1.9 to 3.1 mm).
of Subcommittee C11.02 on Specifications and Test Methods for Accessories and
Reduction of the size of the openings to less than 2 by 2 in. (51
Related Products.
Current edition approved Oct. 1, 2018. Published October 2018. Originally by 51 mm) shall also be permitted.
approved in 1980. Last previous edition approved in 2014 as C933 – 14. DOI:
5.1.3 Self-furring crimps on self-furring lath shall project
10.1520/C0933-18.
1
not less than ⁄4 in. (6 mm) from the plane of the back of the
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
lath.
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Standards volume information, refer to the standard’s Document Summary page on
1
5.2 Thickness—The nominal thickness shall be ⁄8 in.
the ASTM website.
3 (3.2 mm), exclusive of self-furring crimps, with a permissible
Available from Standardization Documents Order Desk, Bldg. 4 Section D, 700
1
Robbins Ave., Philadelphia, PA 19111-5094, Attn: NPODS. variation of 6 ⁄32 in. (0.8 mm).
*A Summary of Changes section appears at the end
...