Standard Specification for Precast Reinforced Concrete Monolithic Box Sections for Culverts, Storm Drains, and Sewers (Metric)

ABSTRACT
This specification deals with the standards for single-cell precast reinforced concrete box sections cast monolithically and proposed for use in the construction of culverts and for the conveyance of storm water industrial sewage. The reinforced concrete shall be composed of cementitious materials, mineral aggregates and water, in which steel has been embedded. The aggregates shall be sized, graded, and mixed to the proportion that will produce a homogeneous mixture. The box sections shall also undergo steam curing, water curing, and membrane curing.
SCOPE
1.1 This specification covers single-cell precast reinforced concrete box sections cast monolithically and intended to be used for the construction of culverts and for the conveyance of storm water industrial wastes and sewage.  
1.2 This specification is the SI companion to Specification C1433.Note 1—This specification is primarily a manufacturing and purchasing specification. However, standard designs are included and the criteria used to develop these designs are given in Appendix X1. The successful performance of this product depends upon the proper selection of the box section, bedding, backfill, and care that the installation conforms to the construction specifications. The purchaser of the precast reinforced concrete box sections specified herein is cautioned that he must properly correlate the loading conditions and the field requirements with the box section specified and provide for inspection at the construction site.

General Information

Status
Historical
Publication Date
30-Jun-2013
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM C1433M-13b - Standard Specification for Precast Reinforced Concrete Monolithic Box Sections for Culverts, Storm Drains, and Sewers (Metric)
English language
22 pages
sale 15% off
Preview
sale 15% off
Preview
Technical specification
REDLINE ASTM C1433M-13b - Standard Specification for Precast Reinforced Concrete Monolithic Box Sections for Culverts, Storm Drains, and Sewers (Metric)
English language
22 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:C1433M −13b
StandardSpecification for
Precast Reinforced Concrete Monolithic Box Sections for
1
Culverts, Storm Drains, and Sewers (Metric)
This standard is issued under the fixed designation C1433M; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope C595Specification for Blended Hydraulic Cements
C618Specification for Coal Fly Ash and Raw or Calcined
1.1 This specification covers single-cell precast reinforced
Natural Pozzolan for Use in Concrete
concrete box sections cast monolithically and intended to be
C822Terminology Relating to Concrete Pipe and Related
used for the construction of culverts and for the conveyance of
Products
storm water industrial wastes and sewage.
C989SpecificationforSlagCementforUseinConcreteand
1.2 This specification is the SI companion to Specification
Mortars
C1433.
C990Specification for Joints for Concrete Pipe, Manholes,
and Precast Box Sections Using Preformed Flexible Joint
NOTE 1—This specification is primarily a manufacturing and purchas-
ing specification. However, standard designs are included and the criteria Sealants
used to develop these designs are given in Appendix X1. The successful
C1619Specification for Elastomeric Seals for Joining Con-
performance of this product depends upon the proper selection of the box
crete Structures
section, bedding, backfill, and care that the installation conforms to the
C1677Specification for Joints for Concrete Box, Using
construction specifications. The purchaser of the precast reinforced
Rubber Gaskets
concrete box sections specified herein is cautioned that he must properly
3
correlate the loading conditions and the field requirements with the box
2.2 AASHTO Standards:
section specified and provide for inspection at the construction site.
Standard Specifications for Highway Bridges
2. Referenced Documents
3. Terminology
2
2.1 ASTM Standards:
3.1 Definitions—Fordefinitionsoftermsrelatingtoconcrete
A1064/A1064MSpecification for Carbon-Steel Wire and
pipe, see Terminology C822.
Welded Wire Reinforcement, Plain and Deformed, for
Concrete
4. Types
A615/A615MSpecificationforDeformedandPlainCarbon-
4.1 Precast reinforced concrete box sections manufactured
Steel Bars for Concrete Reinforcement
in accordance with this specification shall be one of two types
C31/C31MPractice for Making and Curing Concrete Test
identified in Tables 1 and 2, and shall be designated by type,
Specimens in the Field
span, rise, and design earth cover.
C33Specification for Concrete Aggregates
C39/C39MTest Method for Compressive Strength of Cylin-
5. Basis of Acceptance
drical Concrete Specimens
5.1 Acceptability of the box sections produced in accor-
C150Specification for Portland Cement
dance with Section 7 shall be determined by the results of the
C309Specification for Liquid Membrane-Forming Com-
concretecompressivestrengthtestsdescribedinSection10,by
pounds for Curing Concrete
the material requirements described in Section 6, and by
C497MTest Methods for Concrete Pipe, Manhole Sections,
inspection of the finished box sections.
or Tile (Metric)
5.2 Box sections shall be considered ready for acceptance
when they conform to the requirements of this specification.
1
This specification is under the jurisdiction of ASTM Committee C13 on
Concrete Pipeand is the direct responsibility of Subcommittee C13.07 on Accep-
6. Material
tance Specifications and Precast Concrete Box Sections.
CurrenteditionapprovedJuly1,2013.PublishedJuly2013.Originallyapproved
6.1 Reinforced Concrete—The reinforced concrete shall
in 1999. Last previous edition approved in 2013 as C1433M–13a. DOI: 10.1520/
consist of cementitious materials, mineral aggregates and
C1433M-13B.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
3
Standards volume information, refer to the standard’s Document Summary page on Available from American Association of State Highway and Transportation
the ASTM website. Officials (AASHTO), 444 N. Capitol St., NW, Suite 249, Washington, DC 20001.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
C1433M−13b
water,inwhichsteelhasbeenembeddedinsuchamannerthat wire reinforcement are to be submitted for the owner’s
the steel and concrete act together. approval. Longitudinal distribution reinforcement shall be
allowed to consist of welded wire reinforcement or deformed
6.2 Cementitious Materials:
billet-steel bars conforming to Specification A615/A615M,
6.2.1 Ceme
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: C1433M − 13a C1433M − 13b
Standard Specification for
Precast Reinforced Concrete Monolithic Box Sections for
1
Culverts, Storm Drains, and Sewers (Metric)
This standard is issued under the fixed designation C1433M; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This specification covers single-cell precast reinforced concrete box sections cast monolithically and intended to be used for
the construction of culverts and for the conveyance of storm water industrial wastes and sewage.
1.2 This specification is the SI companion to Specification C1433.
NOTE 1—This specification is primarily a manufacturing and purchasing specification. However, standard designs are included and the criteria used
to develop these designs are given in Appendix X1. The successful performance of this product depends upon the proper selection of the box section,
bedding, backfill, and care that the installation conforms to the construction specifications. The purchaser of the precast reinforced concrete box sections
specified herein is cautioned that he must properly correlate the loading conditions and the field requirements with the box section specified and provide
for inspection at the construction site.
2. Referenced Documents
2
2.1 ASTM Standards:
A82/A82MA1064/A1064M Specification for Steel Wire, Plain, for Concrete ReinforcementCarbon-Steel Wire and Welded Wire
Reinforcement, Plain and Deformed, for Concrete
A185/A185M Specification for Steel Welded Wire Reinforcement, Plain, for Concrete
A496/A496M Specification for Steel Wire, Deformed, for Concrete Reinforcement
A497/A497M Specification for Steel Welded Wire Reinforcement, Deformed, for Concrete
A615/A615M Specification for Deformed and Plain Carbon-Steel Bars for Concrete Reinforcement
C31/C31M Practice for Making and Curing Concrete Test Specimens in the Field
C33 Specification for Concrete Aggregates
C39/C39M Test Method for Compressive Strength of Cylindrical Concrete Specimens
C150 Specification for Portland Cement
C309 Specification for Liquid Membrane-Forming Compounds for Curing Concrete
C497M Test Methods for Concrete Pipe, Manhole Sections, or Tile (Metric)
C595 Specification for Blended Hydraulic Cements
C618 Specification for Coal Fly Ash and Raw or Calcined Natural Pozzolan for Use in Concrete
C822 Terminology Relating to Concrete Pipe and Related Products
C989 Specification for Slag Cement for Use in Concrete and Mortars
C990 Specification for Joints for Concrete Pipe, Manholes, and Precast Box Sections Using Preformed Flexible Joint Sealants
C1619 Specification for Elastomeric Seals for Joining Concrete Structures
C1677 Specification for Joints for Concrete Box, Using Rubber Gaskets
3
2.2 AASHTO Standards:
Standard Specifications for Highway Bridges
3. Terminology
3.1 Definitions—For definitions of terms relating to concrete pipe, see Terminology C822.
1
This specification is under the jurisdiction of ASTM Committee C13 on Concrete Pipeand is the direct responsibility of Subcommittee C13.07 on Acceptance
Specifications and Precast Concrete Box Sections.
Current edition approved April 1, 2013July 1, 2013. Published April 2013July 2013. Originally approved in 1999. Last previous edition approved in 2013 as
C1433M – 13.C1433M – 13a. DOI: 10.1520/C1433M-13A.10.1520/C1433M-13B.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
3
Available from American Association of State Highway and Transportation Officials (AASHTO), 444 N. Capitol St., NW, Suite 249, Washington, DC 20001.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
C1433M − 13b
4. Types
4.1 Precast reinforced concrete box sections manufactured in accordance with this specification shall be one of two types
identified in Tables 1 and 2, and shall be designated by type, span, rise, and design earth cover.
5. Basis of Acceptance
5.1 Acceptability of the box sections produced in accordance with Section 7 shall be determined by the results of the concrete
compressive strength tests described in Section 10, by the mat
...