ASTM C1290-06e1
(Specification)Standard Specification for Flexible Fibrous Glass Blanket Insulation Used to Externally Insulate HVAC Ducts
Standard Specification for Flexible Fibrous Glass Blanket Insulation Used to Externally Insulate HVAC Ducts
ABSTRACT
This specification covers the standard for composition, size, dimensions, and physical properties of flexible glass blanket, ductwrap intended for use to insulate HVAC ducts. The basic materials shall be fibers manufacture from glass processed from the molten state into fibrous form. Bonded fibers formed into flexible blank rolls shall consist the insulation. Materials shall conform to physical requirements such as thermal resistance, surface burning characteristics, hot surface performance, water vapor permeance, water vapor sorption, odor emission, corrosiveness, and fungi resistance.
SCOPE
1.1 This specification covers the composition, size, dimensions, and physical properties of flexible fiber glass blanket, ductwrap, used to externally insulate HVAC ducts used for the distribution of condition air with a temperature up to 250°F (121°C).
1.2 The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are for information only and may be approximate.
1.3 When the installation and use of thermal insulation materials, accessories, and systems may pose safety and health problems, the manufacturer shall provide the user appropriate current information regarding any known problems associated with the recommended use of the company's products, and shall also recommend protective measures to be employed in their safe utilization. The user shall establish appropriate safety and health practices and determine the applicability of regulatory requirements prior to use.
1.4 The following safety hazards caveat pertains only to the test methods, Section 13, in this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
General Information
Relations
Buy Standard
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
´1
Designation: C1290 – 06
Standard Specification for
Flexible Fibrous Glass Blanket Insulation Used to Externally
1
Insulate HVAC Ducts
This standard is issued under the fixed designation C1290; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1
´ NOTE—Sections 2.2 and 13.3 were editorially updated in June 2008.
1. Scope C177 Test Method for Steady-State Heat Flux Measure-
ments and Thermal Transmission Properties by Means of
1.1 This specification covers the composition, size, dimen-
the Guarded-Hot-Plate Apparatus
sions, and physical properties of flexible fiber glass blanket,
C390 Practice for Sampling and Acceptance of Thermal
ductwrap, used to externally insulate HVAC ducts used for the
Insulation Lots
distribution of condition air with a temperature up to 250°F
C411 Test Method for Hot-Surface Performance of High-
(121°C).
Temperature Thermal Insulation
1.2 The values stated in inch-pound units are to be regarded
C518 Test Method for Steady-State Thermal Transmission
as the standard. The values given in parentheses are for
Properties by Means of the Heat Flow Meter Apparatus
information only and may be approximate.
C665 Specification for Mineral-Fiber Blanket Thermal In-
1.3 When the installation and use of thermal insulation
sulation for Light Frame Construction and Manufactured
materials, accessories, and systems may pose safety and health
Housing
problems, the manufacturer shall provide the user appropriate
C1104/C1104M Test Method for Determining the Water
current information regarding any known problems associated
Vapor Sorption of Unfaced Mineral Fiber Insulation
with the recommended use of the company’s products, and
C1136 Specification for Flexible, Low Permeance Vapor
shall also recommend protective measures to be employed in
Retarders for Thermal Insulation
their safe utilization.The user shall establish appropriate safety
C1045 PracticeforCalculatingThermalTransmissionProp-
and health practices and determine the applicability of regula-
erties Under Steady-State Conditions
tory requirements prior to use.
E84 Test Method for Surface Burning Characteristics of
1.4 The following safety hazards caveat pertains only to the
Building Materials
test methods, Section 13, in this specification. This standard
E96/E96M Test Methods for Water Vapor Transmission of
does not purport to address all of the safety concerns, if any,
Materials
associated with its use. It is the responsibility of the user of this
E2231 Practice for Specimen Preparation and Mounting of
standard to establish appropriate safety and health practices
Pipe and Duct Insulation Materials to Assess Surface
and determine the applicability of regulatory limitations prior
Burning Characteristics
to use.
2.2 Other Documents:
2. Referenced Documents CAN/ULC-S102 Standard Method of Test for Surface
2
Burning Characteristics of Building Materials andAssem-
2.1 ASTM Standards:
3
blies
C167 TestMethodsforThicknessandDensityofBlanketor
Batt Thermal Insulations
3. Terminology
C168 Terminology Relating to Thermal Insulation
3.1 Definitions—For definitions of terms defined in this
specification, see Terminology C168.
1
This specification is under the jurisdiction of ASTM Committee C16 onTher-
mal Insulation and is under the direct responsibility of Subcommittee C16.23 . 4. Classification
Current edition approved March 1, 2006. Published March 2006.
4.1 Fibrous glass flexible blanket HVAC duct external
Originally approved in 1995. Last previous edition approved in 2004 as
insulation consists of the following three types:
C1290–04. DOI: 10.1520/C1290-06E01.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
3
Standards volume information, refer to the standard’s Document Summary page on Available from Underwriters Laboratories of Canada, 7 Crouse Road, Scarbor-
the ASTM website. ough, Ontario, Canada M1R 3A9.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1
---------------------- Page: 1 ----------------------
´1
C1290 – 06
4.1.1 Type I—Blankets without membrane facing. 7.6 Odor Emission— A detectable odor of objectionable
4.1.2 Type II—Blankets faced with a vapor-retarder mem- nature recorded by more than two of the five panel members
brane having a water vapor permeance no higher than 1.30 shall constitute rejection of the product when tested in accor-
Perm. dance with 13.7.
4.1.3 Type III—Flexible blankets faced with a vapor- 7.7 Corrosiveness— When tested in accordance with 13.8,
reta
...
This document is not anASTM standard and is intended only to provide the user of anASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
e1
Designation:C1290–04 Designation: C 1290 – 06
Standard Specification for
Flexible Fibrous Glass Blanket Insulation Used to Externally
1
Insulate HVAC Ducts
This standard is issued under the fixed designation C 1290; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1
e NOTE—Sections 2.2 and 13.3 were editorially updated in June 2008.
1. Scope
1.1 Thisspecificationcoversthecomposition,size,dimensions,andphysicalpropertiesofflexiblefiberglassblanket,ductwrap,
used to externally insulate HVAC ducts used for the distribution of condition air with a temperature up to 250°F (121°C).
1.2 The values stated in inch-pound units are to be regarded as the standard.The values given in parentheses are for information
only and may be approximate.
1.3 Whentheinstallationanduseofthermalinsulationmaterials,accessories,andsystemsmayposesafetyandhealthproblems,
the manufacturer shall provide the user appropriate current information regarding any known problems associated with the
recommended use of the company’s products, and shall also recommend protective measures to be employed in their safe
utilization. The user shall establish appropriate safety and health practices and determine the applicability of regulatory
requirements prior to use.
1.4 The following safety hazards caveat pertains only to the test methods, Section 13, in this specification. This standard does
not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard
to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
2. Referenced Documents
2
2.1 ASTM Standards:
C 167 Test Methods for Thickness and Density of Blanket or Batt Thermal Insulations
C 168 Terminology Relating to Thermal Insulation
C 177 Test Method for Steady-State Heat Flux Measurements and Thermal Transmission Properties by Means of the
Guarded-Hot-Plate Apparatus
C 390 Practice for Sampling and Acceptance of Preformed Thermal Insulation Lots
C 411 Test Method for Hot-Surface Performance of High-Temperature Thermal Insulation
C 518 Test Method for Steady-State Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus
C 665 Specification for Mineral-Fiber Blanket Thermal Insulation for Light Frame Construction and Manufactured Housing
C1104/1104M 1104/C 1104M Test Method for Determining the Water Vapor Sorption of Unfaced Mineral Fiber Insulation
C 1136 Specification for Flexible, Low Permeance VaporsVapor Retarders for Thermal Insulation
C 1045 Practice for Calculating Thermal Transmission Properties Under Steady-State Conditions
E 84 Test Method for Surface Burning Characteristics of BuildingsBuilding Materials
E96Test Methods for Water Vapor Transmission of Materials
2.2 96/E 96M Test Methods for Water Vapor Transmission of Materials
E 2231 Practice for Specimen Preparation and Mounting of Pipe and Duct Insulation Materials to Assess Surface Burning
Characteristics
2.2 Other Documents:
CAN/UCL-S102–M88 CAN/ULC-S102 Standard Method of Test for Surface Burning Characteristics of Building Materials
3
and Assemblies
1
This specification is under the jurisdiction of ASTM Committee C16 onThermal Insulation and is under the direct responsibility of Subcommittee C16.23 on Blanket
and Loose Fill Insulation .
Current edition approved Sept.March 1, 2004.2006. Published September 2004.March 2006.
´1
Originally approved in 1995. Last previous edition approved in 2004 as C 1290–00 .1290–04.
2
For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
3
Available from Underwriters Laboratories of Canada, 7 Crouse Road, Scarborough, Ontario, Canada M1R 3A9.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1
---------------------- Page: 1 ----------------------
e1
C1290–06
3. Terminology
3.1 Definitions—For definitions of terms defined in this specification, see Terminology C 168.
4. Classification
4.1 Fibrous glass flexible blanket HVAC duct external insulation consists of the following three types:
4.1.1 Type I—Blankets without membr
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.