Standard Practice for Installation and Use of Reflective Insulation in Building Constructions

SCOPE
1.1 This practice has been prepared for use by the designer, specifier, and installer of reflective insulation for use in building construction. The scope is limited to recommendations relative to the use and installation of thermal insulation consisting of one or more surfaces, having an emittance of 0.1 or less such as metallic foil or metallic deposits unmounted or mounted on substrates and facing enclosed air spaces. The reflective insulation covered by this practice must meet the requirements of Specification C 1224.
1.2 This practice covers the installation process from pre-installation inspection through post-installation procedure. It does not cover the production of the insulation materials.
1.3 This practice is not intended to replace the manufacturer's installation instructions, but shall be used in conjunction with such instructions. This practice is not intended to supercede local, state, or federal codes.
1.4 This practice assumes that the installer possesses a good working knowledge of the applicable codes and regulations, safety practices, tools, equipment, and methods necessary for the installation of thermal insulation materials. It also assumes that the installer understands the fundamentals of construction that affect the installation of insulation.
1.5 The values given in inch-pound units are to be regarded as standard. The SI units in parentheses are for information only.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
09-Oct-2001
Technical Committee
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM C727-90(1996)e1 - Standard Practice for Installation and Use of Reflective Insulation in Building Constructions
English language
3 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


NOTICE: This standard has either been superseded and replaced by a new version or discontinued.
Contact ASTM International (www.astm.org) for the latest information.
e1
Designation: C 727 – 90 (Reapproved 1996)
Standard Practice for
Installation and Use of Reflective Insulation in Building
Constructions
This standard is issued under the fixed designation C 727; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
e NOTE—Keywords were added editorially in March 1996.
1. Scope 2.2 NFPA Standards:
NFPA 31 Standard for the Installation of Oil Burning
1.1 This practice has been prepared for use by the designer,
Equipment
specifier, and installer of reflective insulation for use in
NFPA 54 National Fuel Gas Code
building construction. The scope is limited to recommenda-
NFPA 211 Standard for Chimneys, Fireplaces, and Vents
tions relative to the use and installation of thermal insulation
2.3 Code of Federal Regulations:
consisting of one or more surfaces, having an emittance of 0.1
16 CFR 460 Federal Trade Commission Trade Regulation
or less such as metallic foil or metallic deposits unmounted or
Rule: Labeling and Advertising of Home Insulation
mounted on substrates and facing enclosed air spaces.
1.2 This practice covers the installation process from pre-
3. Terminology
installation inspection through post-installation procedure. It
3.1 Definitions—For definitions of terms used in this prac-
does not cover the production of the insulation materials.
tice refer to Terminology C 168
1.3 This practice is not intended to replace the manufactur-
3.2 Descriptions of Terms Specific to This Standard:
er’s installation instructions, but shall be used in conjunction
3.2.1 applicator—the person or persons who apply thermal
with such instructions. This practice is not intended to super-
insulation materials in buildings whether or not such person or
cede local, state, or federal codes.
persons have contracted with the owner to perform the work.
1.4 This practice assumes that the installer possesses a good
3.2.2 conditioned space—any space in a building that is
working knowledge of the applicable codes and regulations,
served by a heating or cooling system.
safety practices, tools, equipment, and methods necessary for
3.2.3 owner—the person, partnership, corporation, agency,
the installation of thermal insulation materials. It also assumes
or other entity owning the building to be insulated whether
that the installer understands the fundamentals of construction
such ownership is by virtue of deed, contract, or any other
that affect the installation of insulation.
instrument for acquiring legal title under the laws of the state
1.5 The values given in inch-pound units are to be regarded
in which the building is located.
as standard. The SI units in parentheses are for information
3.2.4 reflective insulation system—thermal insulation con-
only.
sisting of one or more low emittance surfaces, bounding one or
1.6 This standard does not purport to address all of the
more enclosed air spaces.
safety concerns, if any, associated with its use. It is the
3.2.5 vapor retarder—any material (membrane or paint)
responsibility of the user of this standard to establish appro-
that has a water vapor permeance (perm) rating of 57 ng/
priate safety and health practices and determine the applica-
(Pa·s·m ) (1 perm) or less as defined in Practice C 755.
bility of regulatory limitations prior to use.
4. Significance and Use
2. Referenced Documents
4.1 This practice recognizes that effectiveness, safety, and
2.1 ASTM Standards:
durability of reflective insulation depends not only on the
C 168 Terminology Relating to Thermal Insulating Materi-
2 quality of the insulating materials, but also on their proper
als
installation.
C 755 Practice for Selection of Vapor Retarders for Thermal
2 4.2 Improper installation of insulation can reduce its ther-
Insulations
mal effectiveness, cause fire risks and other unsafe conditions,
and promote deterioration of the structure in which it is
This practice is under the jurisdiction of ASTM Committee C-16 on Thermal
Insulationand is the direct responsibility of Subcommittee C16.21 on Reflective
Insulation. Available from National Fire Protection Association, Batterymarch Park,
Current edition approved Oct. 26, 1990. Published December 1990. Originally Quincy, MA 02269.
published as C 727 – 72. Last previous edition C 727 – 72 (1978). Federal Register, Vol 45, No. 160, Aug. 15, 1980. Available from Department
Annual Book of ASTM Standards, Vol 04.06. of Housing and Urban Development, 451 7th St. N.W., Washington, D.C. 20410.
Copyright © ASTM, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959, United States.
C 727
installed. Specific hazards that can result from improper least as high as the height of the finished insulation and in a
installation include fires caused by (1) heat build-up in recessed manner that ensures all devices that require maintenance or
lighting fixtures, (2) deterioration or failure of electrical wiring servicing remain accessible after the insulation is installed.
components, and heat build-up resulting from overcurrent 6.4.2 Install blocking to provide a minimum three inch (76
protection devices incorrectly matched to wiring; or (3) dete- mm) clearance around all sides of recessed lighting fixtures,
rioration in wood structures and paint failure due to moisture unless such fixtures are approved for installation in direct
accumulation. contact with insulation, including fixture wiring compartments
4.3 This practice provides recommendations for the instal- and ballasts and other heat-producing devices not covered with
lation of reflective insulation in a safe and effective manner. thermal insulation.
Actual conditions in existing buildings may vary greatly and in 6.4.3 The open area above heat producing devices must not
some cases additional care should be taken to ensure safe and be covered, unless they are specifically approved devices for
effective installation. operation when covered with thermal insulation.
4.4 This practice presents requirements that are general in 6.4.4 Install blocking around gas-fired appliances to provide
nature and considered practical. They are not intended as th
...