Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN 378-1:2008/oprA1:2008
01-oktober-2008
+ODGLOQLVLVWHPLLQWRSORWQHþUSDONH9DUQRVWQRWHKQLþQHLQRNROMHYDUVWYHQH]DKWHYH
GHO2VQRYQH]DKWHYHGHILQLFLMHUD]YUVWLWHYLQPHULOD]DL]ERU'RSROQLOR
Refrigerating systems and heat pumps - Safety and environmental requirements - Part 1:
Basic requirements, definitions, classification and selection criteria - Amendment 1
Systèmes de réfrigération et pompes à chaleur - Exigences de sécurité et
d'environnement - Partie 1 : Exigences de base, définitions, classification et critères de
choix - Amendement 1
Ta slovenski standard je istoveten z: EN 378-1:2008/prA1
ICS:
01.040.27 Prenos energije in toplote Energy and heat transfer
(Slovarji) engineering (Vocabularies)
27.080 7RSORWQHþUSDONH Heat pumps
27.200 Hladilna tehnologija Refrigerating technology
SIST EN 378-1:2008/oprA1:2008 en,fr
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
SIST EN 378-1:2008/oprA1:2008
SIST EN 378-1:2008/oprA1:2008
EUROPEAN STANDARD
DRAFT
EN 378-1:2008
NORME EUROPÉENNE
EUROPÄISCHE NORM
prA1
June 2008
ICS
English Version
Refrigerating systems and heat pumps - Safety and
environmental requirements - Part 1: Basic requirements,
definitions, classification and selection criteria - Amendment 1
Systèmes de réfrigération et pompes à chaleur - Exigences
de sécurité et d'environnement - Partie 1 : Exigences de
base, définitions, classification et critères de choix -
Amendement 1
This draft amendment is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 182.
This draft amendment A1, if approved, will modify the European Standard EN 378-1:2008. If this draft becomes an amendment, CEN
members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for inclusion of this amendment
into the relevant national standard without any alteration.
This draft amendment was established by CEN in three official versions (English, French, German). A version in any other language made
by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same
status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.
Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36 B-1050 Brussels
© 2008 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 378-1:2008/prA1:2008: E
worldwide for CEN national Members.
SIST EN 378-1:2008/oprA1:2008
EN 378-1:2008/prA1:2008 (E)
Contents Page
Foreword.3
1 Annex E.3
Annex E (normative) Safety classification and information about refrigerants .4
SIST EN 378-1:2008/oprA1:2008
EN 378-1:2008/prA1:2008 (E)
Foreword
This document (EN 378-1:2008/prA1:2008) has been prepared by Technical Committee CEN/TC 182
“Refrigerating systems, safety and environmental requirements”, the secretariat of which is held by DIN.
This document is currently submitted to the CEN Enquiry.
1 Annex E
Replace Annex E by the following table.
SIST EN 378-1:2008/oprA1:2008
EN 378-1:2008/prA1:2008 (E)
Annex E
(normative)
Safety classification and information about refrigerants
Table E.1 — Refrigerant Designations
Auto-
PED ignition
i a, f a, g
Refrigerant Number Chemical Safety Practical Flammability Vapour Density Molecular Normal
ATEL/ODL ODP GWP
Fluid Tempe-
rature
25°C, Boiling
(100
b d e j, k a
Formula Group
Chemical Name Group Limit LFL Mass
a a
101.3 kPa Point yr ITH)
3 3 3 3
(kg/m) (kg/m) (kg/m) (kg/m) (°C) (°C)
Methane Series
11 Trichlorofluoromethane CCIF A1 2 0.3 0.3 — 5.824 137,4 23.8 1 3800 —
12 Dichlorodifluoromethane CCI F A1 2 0.5 0.5 — 5.039 120,9 – 29.0 1 10600 —
2 2
12B1 Bromochlorodifluoromethane CBrCIF 2 0.2 0.2 — N.D. 165,4 – 4.0 3 1300 —
13 Chlorotrifluoromethane CCIF A1 2 0.5 0.5 — 4.309 104,5 – 81.4 1 14000 —
13B1 Bromotrifluoromethane CBrF A1 2 0.6 0.6 — 6.169 148,9 – 58.0 10 5400 —
14 carbon tetrafluoride CF A1 2 N.D. N.D. — 3.611 88,0 – 128.0 0 6500 —
22 Chlorodifluoromethane CHCIF A1 2 0.3 0.3 — 3.587 86,5 – 40.8 0.055 1700 635
23 Trifluoromethane CHF A1 2 0.68 0.68 — 2.884 70,0 – 82,1 0 12000 765
30 Dichloromethane (methylene chloride) CH Cl B2 2 0.017 N.D. 0.417 N.D. 84,9 40.0 9 662
2 2
32 difluoromethane (methylene fluoride) CH F A2 1 0.061 0.085 0.306 2.153 52,0 – 51.7 0 550 648
2 2
50 Methane CH A3 1 0.006 N.D. 0.032 0.657 16,0 – 161.0 0 21 645
Ethane Series
113 1,1,2-trichloro-1,2,2-trifluoroethane CCl FCClF A1 2 0.4 0.4 — 3.467 187,4 47,6 0.8 4800 —
2 2
114 1,2-dichloro-1,1,2,2-tetrafluoroethane CClF CClF A1 2 0.7 0.7 — 7.207 170,9 3,8 1 9800 —
2 2
115 Chloropentafluoroethane CCIF CF A1 2 0.6 0.6 — 6.438 154,5 – 39.0 0.6 7200 —
2 3
116 Hexafluoroethane CF CF A1 2 0.55 0.55 — 5.696 138,0 – 79.0 0 11900 —
3 3
123 2,2-dichloro-1,1,1-trifluoroethane CHCI CF B1 2 0.1 0.1 — 5.872 153,0 27,9 0.02 120 730
2 3
124 2-chloro-1,1,1,2-tetrafluoroethane CHCIFCF A1 2 0.11 0.11 — 5.728 136,5 – 12,1 0.022 620 —
125 Pentafluoroethane CHF CF A1 2 0.39 0.39 — 4.982 120,0 – 48,1 0 3400 733
2 3
134a 1,1,1,2-tetrafluoroethane CH FCF A1 2 0.25 0.25 — 4.258 102,0 – 26,2 0 1300 743
2 3
141b 1,1-dichloro-1-fluoroethane CH CCIF A2 2 0.013 0.013 0.43 3.826 117,0 32.0 0.11 700 532
3 2
142b 1-chloro-1,1-difluoroethane CH CCIF A2 1 0.066 0.10 0.329 4.223 100,5 – 10.0 0.065 2400 750
3 2
143a 1,1,1-trifluoroethane CH CF A2 1 0.056 0.53 0.282 3.495 84,0 – 47,0 0 4300 750
3 3
152a 1,1-difluoroethane CH CHF A2 1 0.026 0.14 0.13 2.759 66,0 – 25.0 0 120 455
3 2
i
170 Ethane CH CH A3 1 0.008
3 3 0.01 0.038 1.239 30,0 – 89.0 0 515
i
1150 Ethene (ethylene) CH =CH A3 1 0.007
2 2 N.D. 0.036 1.153 28,1 – 104.0 0 3 —
SIST EN 378-1:2008/oprA1:2008
EN 378-1:2008/prA1:2008 (E)
Table E.1 (continued)
Auto-
PED ignition
i a, f a, h
Refrigerant Number Chemical Safety Practical Flammability Vapour Density Molecular Normal
ATEL/ODL ODP GWP
Fluid Tempe-
rature
25°C, Boiling
(100
b d e j, k a
Formula Group
Chemical Name Group Limit LFL Mass
a a
yr ITH)
101.3 kPa Point
3 3 3 3
(kg/m) (kg/m) (kg/m) (kg/m) (°C) (°C)
Propane Series
218 Octafluoropropane CF CF CF A1 2 0.44 0.44 — 7.853 188.0 – 37 0 8600 —
3 2 3
227ea 1,1,1,2,3,3,3-heptafluoropropane CF CHFCF A1 2 0.49 0.49 — 7.137 170.0 – 15.6 0 3500 —
3 3
236fa 1,1,1,3,3,3-hexafluoropropane CF CH CF A1 2 0.59 0.59 — 6.418 152.0 – 1.4 0 9400 —
3 2 3
245fa 1,1,1,3,3-pentafluoropropane CF CH2CHF B1 2 0.19 0.19 — 5.689 134.0 14.9 0 950 —
3 2
h
290 Propane CH CH CH A3
3 2 3 1 0.008 0.09 0.038 1.832 44.0 – 42 0 470
h
1270 Propene (propylene) CH CH=CH A3
3 2 1 0.008 0.010 0.040 1.745 42,1 – 48 0 3 455
Butane (and higher) Series
365mfc 1,1,1,3,3-pentafluorobutane CF CH CF CH ND N.D. N.D. N.D. N.D. N.D. 148.0 40.1 0 890 —
3 2 2 3
43-10mee 1,1,1,2,2,3,4,5,5,5-decafluoropentane CF3CF2CHFCHF A1
2 N.D. N.D. — N.D. 252.0 54.6 0 1500 —
CF
Cyclic Organic Compounds
C318 Octafluorocyclobutane C F A1 2 0.81 0.81 — 8.429 200,0 – 6 0 10000 —
4 8
Hydrocarbons
h
600 Butane CH CH CH CH A3
3 2 2 3 1 0.0086 0.19 0.043 2.450 58.1 0 0 365
h
600a 2-methyl propane (isobutane) CH(CH ) A3 1 0.0086 0.06 0.043 2.440 58.1 – 12 0 3 460
3 3
601 Pentane CH CH CH CH A3
3 2 2 2
h
1 0.008 N/A 0.041 2.058 72.1 36.1 0
3 —
CH
601a 2methyl butane (isopentane) (CH ) CHCH CH A3
3 2 2
h
1 0.008 N/A 0.041 2,786 72.1 27.8 0 —
Other Organic Compounds
E170 Dimethyl Ether (CH )O A3 1 0.013 0.08 0.064 1.914 46 – 24.8 0 235
3 2
SIST EN 378-1:2008/oprA1:2008
EN 378-1:2008/prA1:2008 (E)
Table E.1 (continued)
Auto-
PED ignition
i a, f a, h
Refrigerant Number Chemical Safety Practical Flammability Vapour Density Molecular Normal
ATEL/ODL ODP GWP
Fluid Tempe-
rature
25°C, Boiling
(100
b d e j, k a
Formula Group
Chemical Name Group Limit LFL Mass
a a
yr ITH)
101.3 kPa Point
3 3 3 3
(kg/m) (kg/m) (kg/m) (kg/m) (°C) (°C)
Inorganic Compounds
717 Ammonia NH B2 1 0.00035 0.00035 0.104 0.704 17,0 – 33 0 0 630
c
744 Carbon dioxide CO A1
2 2 0.07 0.07 - 1.808 44,0 0 1 —
– 78
See Tables E.2 and E.3 for R-400 and R-500 blends.
N.D Signifies Not Determined
a
The vapour density, molecular mass, normal boiling point, ODP and GWP are not part of this standard and are provided for information purposes only.
b
The preferred chemical name is followed by the popular name in parentheses.
c
Sublimes. Triple Point is -56.6°C at 5.2 bar.
d
See Annex G. Unclassified refrigerants indicate either insufficient data to classify or no formal request for classification.
e
See Annex G.
f
Adopted under the Montreal Protocol.
g
IPCC, Third Assessment Report 2001. Values used in EC Regulation 842/2006 (F Gas Regulation)
h
1998 Ozone Assessment Report.
i
Acute-Toxicity Exposure Limit or Oxygen Deprivation Limit, whichever is l
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.