Abstract

This document is part of the EN 50708 series which applies to transformers in compliance with EN 60076 1.

Status
Not Published
Publication Date
21-Nov-2024
Technical Committee
CLC/TC 14 - Power transformers
Current Stage
4599 - Dispatch of FV draft to CMC - Finalization for Vote
Start Date
13-Aug-2026
Due Date
01-Jun-2022
Completion Date
01-Jun-2022

Buy Documents

Draft

prEN 50708-1-1:2023

English language (34 pages)
Preview
Preview
e-Library read for
×1 day

FprEN 50708-1-1:2026 is a draft European Standard from CLC for power transformers. It gives additional European requirements for the common part of the EN 50708 series, building on EN 60076-1 and setting rules for energy performance, material efficiency, technical documentation, rating plates, tolerances, tests and loss evaluation. It is written for manufacturers, purchasers, test laboratories and compliance teams that need to specify, verify or document transformer performance.

What does FprEN 50708-1-1:2026 specify?

FprEN 50708-1-1:2026 specifies the general requirements that apply across the EN 50708 series for transformers in compliance with EN 60076-1. It is the common part that later EN 50708 subparts build on, so the document is the reference point for shared rules on performance, documentation and verification.

The document is organized into clauses 1 to 11 and five annexes.

AnnexWhat it covers
Annex APeak efficiency calculation
Annex BCapitalization of losses
Annex CA-deviations
Annex DAdditional considerations related to energy performances
Annex ZZRelationship with the ecodesign requirements of Commission Regulation (EU) No 548/2014 and amendment No 2019/1783

FprEN 50708-1-1:2026 also identifies a defined set of special-purpose transformers that are outside the energy-performance requirements, including instrument transformers, rectifier-load transformers, furnace transformers, offshore and vessel transformers, emergency transformers, railway feeding transformers, earthing or grounding transformers, traction transformers, starting transformers, testing and welding transformers, explosion-proof and underground mining transformers, deep-water transformers, MV/MV interface transformers up to 5 MVA used for network voltage conversion, nuclear-safety transformers, and very small three-phase medium power transformers.

What are the key requirements of FprEN 50708-1-1:2026?

FprEN 50708-1-1:2026 focuses on how to rate, document, test and declare power transformers so their losses, efficiency and material-related information can be checked in practice.

Ratings and energy performance

Clause 5.1 says loss evaluation is based on the continuous rated power. Temporary overload capability for emergency use or refurbishment cannot be treated as rated power. Clause 5.2 sets the rated frequency as the network frequency, with 50 Hz as the default.

Clause 5.3.1 sets two energy-performance routes: maximum no-load and load losses for three-phase MPT, and PEI with its load factor for LPT. In practice, this means the document does not use one single efficiency rule for all transformers - it distinguishes between medium-power and large-power cases.

Clause 5.3.3 defines a reference temperature basis for energy-performance calculations. That matters because transformer losses depend on temperature, so the declared values and comparisons have to use the same thermal basis.

Material efficiency and sustainability

Clause 5.4 introduces material efficiency as a separate technical topic alongside energy performance. It covers durability and reliability, remanufacturing, repair, reuse, upgrade, recyclability and recoverability, reused major components, recycled content and critical raw materials.

In practice, this means the transformer is not assessed only by electrical losses. The manufacturer also has to think about how the design can be maintained, taken apart, reprocessed and documented over its life cycle.

Technical documentation

Clause 5.6 requires a technical file for each transformer. It includes the manufacturer identity, model identifier, rated and loss information, PEI data for large power transformers, dual-voltage data where relevant, major-component weights, the reason for any energy-performance exemption, and the rating-plate data.

This matters because the document links compliance to evidence. If declared values come from another model or from a type test, the technical documentation has to show how they were derived and include the supporting type-test report where relevant.

Clause 5.6.2 also requires a Disassembly Manual, and clause 5.6.5 requires data sheets and working points for key accessories and major components such as coolers, fans, bushings and tap changers. That gives users the information needed for maintenance, substitution and end-of-life handling.

Rating plate and tolerances

Clause 6 adds rating-plate information beyond EN 60076-1 and EN IEC 60076-11:2018. It includes loss-related values, cooling-power information, material masses, PEI data where applicable, and a visible statement for pole-mounted transformers. For dual-voltage transformers, the plate information has to refer to the highest rated voltage values.

Clause 7 distinguishes factory acceptance testing from market surveillance. For acceptance tests, measured no-load and load losses must meet the declared maximums without tolerance. For market surveillance, measured loss values and cooling-system power can be slightly above the declared values, within the clause limits. This distinction matters because factory verification and market checks are not treated the same way.

Tests and cooling consumption

Clause 8 allows cooling-system electrical power to be taken from type-test evidence or from the cooling-equipment manufacturer’s type test. If it is not already known, the clause requires a type test under specified electrical and installation conditions.

This is important because forced cooling affects energy performance. The document makes clear that fan and pump consumption is part of the performance picture, not an afterthought.

Loss capitalization and reprocessing

Clause 10 points users to loss capitalization as the economic method for comparing transformer designs. Clause 11 says medium and large power transformers have to be reassessed for conformity after overhaul if the core or complete windings are replaced. Reuse, however, is treated differently and does not trigger reassessment.

What terms does FprEN 50708-1-1:2026 define?

  • MPT (medium power transformer) - The medium-power transformer category used by the standard for its general requirements and energy-performance rules.
  • LPT (large power transformer) - The larger transformer category for which PEI-based requirements are used.
  • PEI (Peak Efficiency Index) - The highest efficiency ratio achieved at the optimum load factor.
  • EI (Efficiency Index) - The efficiency ratio at a given load factor, based on transmitted apparent power and losses.
  • Declared value - A value stated in the technical documentation and, where applicable, used for calculation and verification.
  • Load factor - The ratio of actual current to rated current.
  • Remanufacturing - An industrial process that produces a product from used products or parts with a change affecting safety, performance, purpose or type.
  • CRMs (critical raw materials) - Materials that the technical documentation has to declare when regulated or otherwise applicable.

Who uses FprEN 50708-1-1:2026?

FprEN 50708-1-1:2026 is used by transformer manufacturers and design engineers who need to set ratings, efficiency values, material declarations and rating-plate data. It is also used by test laboratories and factory acceptance teams that measure losses, cooling power and related declared values.

Purchasers, utilities and procurement teams use it when comparing bids with loss-capitalization methods and checking whether a transformer fits a required service and documentation profile. Compliance teams, conformity assessment bodies and market-surveillance authorities use it to verify declared values, tolerances and ecodesign-related evidence.

Maintenance, refurbishment and reprocessing teams use it for the disassembly manual, accessory data and the conformity questions raised by overhaul or reuse.

What changed in FprEN 50708-1-1:2026 from the previous edition?

The foreword states that this edition supersedes EN 50708-1-1:2020 and its amendments and corrigenda. It also states these significant technical changes compared with EN 50708-1-1:2020:

  • the EN 50708-1-1:2020/AC:2020 corrigendum has been included
  • comments received from national committees that were not allowed in the corrigendum have been taken into account
  • a new topic, material efficiency, has been added alongside energy performance within transformer sustainability

Which standards are used with FprEN 50708-1-1:2026?

  • EN 60076-1:2011 - the base power-transformer standard for service conditions, definitions and general transformer requirements
  • EN IEC 62474 - the material declaration standard used for critical raw materials and related declarations
  • EN 50708-2-1:2020 - the medium-power transformer part that provides the detailed requirements referenced by this common part
  • EN 50708-3-1:2020 - the large-power transformer part referenced for PEI-related requirements and benchmark values
  • EN 60076-22 series - the fittings standard series used for accessories and fittings data
  • EN IEC 60076-11:2018 - the standard cited for measurement methods linked to tests and rating-plate data

What does the FprEN 50708-1-1:2026 document contain?

FprEN 50708-1-1:2026 contains the full framework for declaring and checking transformer energy performance, including the calculation method for PEI in Annex A and the economic loss-capitalization method in Annex B. It also contains the national A-deviations in Annex C and the extra technical context in Annex D.

Annex ZZ maps the standard to the ecodesign requirements of Commission Regulation (EU) No 548/2014 and its amendment. The body of the document includes the technical file, rating-plate, tolerance and test provisions that support design review, procurement, acceptance testing and market surveillance.

Relations

Effective Date
03-Feb-2026
Effective Date
15-Dec-2020
Effective Date
15-Dec-2020

Buy Documents

Draft

prEN 50708-1-1:2023

English language (34 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

IMQ S.p.A. (Certification)

Italian electrical product certification.

ACCREDIA Italy Verified

SLG Prüf- und Zertifizierungs GmbH

German testing and certification body.

DAKKS Germany Verified

UL Solutions

Global safety science company with testing, inspection and certification.

ANAB United States Verified

Sponsored listings

Frequently Asked Questions

FprEN 50708-1-1:2026 is a draft published by CLC. Its full title is "Power transformers - Additional European requirements - Part 1-1: Common part - General requirements". This standard covers: This document is part of the EN 50708 series which applies to transformers in compliance with EN 60076 1.

This document is part of the EN 50708 series which applies to transformers in compliance with EN 60076 1.

FprEN 50708-1-1:2026 is classified under the following ICS (International Classification for Standards) categories: 29.180 - Transformers. Reactors. The ICS classification helps identify the subject area and facilitates finding related standards.

FprEN 50708-1-1:2026 has the following relationships with other standards: It is inter standard links to EN IEC/IEEE 60076-57-1202:2025/A11:2025, EN 50708-1-1:2020, EN 50708-1-1:2020/AC:2020-12. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

FprEN 50708-1-1:2026 is associated with the following European legislation: EU Directives/Regulations: 548/2014; Standardization Mandates: M/495, M/495 Amd 2. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.

FprEN 50708-1-1:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • Introduction
  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 3.1 medium power transformer
  • 3.2 large power transformer
  • 3.3 medium power pole-mounted transformer
  • 3.4 load factor
  • 3.5 transmitted apparent power
  • 3.6 Efficiency Index
  • 3.7 Peak Efficiency Index
  • 3.8 load factor of Peak Efficiency Index
  • 3.9 declared value
  • 3.9.1 declared value of loss
  • 3.9.2 declared value of no-load loss
  • 3.9.3 declared value of load loss
  • 3.9.6 declared value of PEI
  • 3.10 dual voltage transformer
  • 3.11 acceptance test
  • 3.12 witnessed testing
  • 3.13 instrument transformer
  • 3.16 transformer specially designed for emergency installations
  • 3.18 earthing or grounding transformer
  • 3.19 traction transformer
  • 3.22 durability
  • 3.23 reliability
  • 3.24 limiting event
  • 3.25 limiting state
  • 3.26 remanufacturing
  • 3.27 reuse
  • 3.28 repair
  • 3.29 upgrade
  • 3.30 recovery
  • 3.31 material recovery
  • 3.32 energy recovery
  • 3.33 recycling
  • 3.34 waste
  • 3.35 component
  • 4 Service condition
  • 5 Ratings and general requirements
  • 5.1 Rated power
  • 5.2 Rated frequency
  • 5.3 Energy performance
  • 5.4 Material efficiency
  • 5.5 Sustainability
  • 5.6 Technical documentation
  • 6 Rating plate
  • 7 Tolerances
  • 7.1 Tolerance during acceptance tests
  • 7.2 Tolerances for market surveillance
  • 8 Tests
  • 8.1 General
  • 8.2 Measurement of cooling consumption
  • 9 Accessories and fittings
  • 10 Capitalization of losses
  • 11 Transformer reprocessing
  • Annex A
  • 2 P + P + Pk
  • Annex B
  • Annex C
  • 1 Czech Republic
  • Annex D
  • Annex ZZ
  • 21 May 2014 and its amendment

Introduction

The EN 50708 series, “Power transformers – Additional European requirements”, has been prepared by CENELEC TC 14 to address specific European requirements of power transformers related EU Regulations and local practices.

Technical requirements set by the EN 50708 series supplement, modify or replace certain requirements of the other EN standards derived from equivalent IEC international standards. This series contains general requirements on energy performance, accessories, fittings, tests, mechanical requirements etc. structured as follows:

  • Part 1 series - Common requirements;
  • Part 2 series - Medium power transformers;
  • Part 3 series - Large power transformers.

The EN 50708-X parts with X greater than 1 contain particular requirements for a different category of transformers or transformer applications which are based on the requirements of the general parts of EN 50708-1-1.

The EN 50708-X parts should be considered in conjunction with the requirements of the general part. The particular requirements of these subparts of EN 50708 supplement, modify or replace certain requirements of the general parts of EN 50708-1-1 and/or EN 50708-1-X being valid at the time of publication of this part. The absence of references to the exclusion of a part or a clause of a general part means that the corresponding clauses of the general part are applicable (undated reference). Requirements of other -X parts with X greater than 1 being eventually relevant for cases covered by this part also apply. This part therefore possibly supplements, modifies or replaces certain of these requirements valid at the time of publication of this document. The main clause numbering of each subpart follows the pattern and corresponding references of EN 50708-1-1. The numbers following the particular number of this part are those of the corresponding parts, or clauses of the other parts of the EN 50708 series, valid at the time of publication of this part, as indicated in the normative references of this document (dated reference). In the case where new or amended general parts with modified numbering were published after the subpart was issued, the clause numbers referring to a general part in subparts might no longer align with the latest edition of the general part. Dated references should be observed. It is acknowledged that environmental requirements including energy in the use phase are a significant aspect that can be addressed through product design. As the material content increases to improve energy performance, it is advisable to make a proper life cycle assessment including recycling of the extra raw material and the overall energy used to produce and transport transformers. Some guidelines are given in EN 60076-1.

oSIST prEN 50708-1-1:2023 prEN 50708-1-1:2023 (E)

1 Scope

This document is part of the EN 50708 series which applies to transformers in compliance with EN 60076-1.

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 60076-1:2011, Power transformers - Part 1: General EN IEC 62474, Material declaration for products of and for the electrotechnical industry EN 50708-2-1:2020, Power transformers - Additional European requirements: Part 2-1 Medium power transformer - General requirements EN 60076-1:2011, Power transformers - Part 1: General EN 60076-22 series, Power transformers - Part 22: Power transformer and reactor fittings

3 Terms and definitions

For the purposes of this document, the terms and definitions given in EN 60076-1:2011 and the following apply.

ISO and IEC maintain terminology databases for use in standardization at the following addresses:

  • ISO Online browsing platform: available at https://www.iso.org/obp/
  • IEC Electropedia: available at https://www.electropedia.org/

3.1 medium power transformer

MPT power transformer with all windings having a rated power lower than or equal to 3 150 kVA, and highest voltage for equipment greater than 1,1 kV and lower than or equal to 36 kV Note 1 to entry: The definitions of power transformer and winding are given in EN 60076-1. Note 2 to entry: The national practice of the Czech Republic could require the use of the highest voltages for equipment in AC three-phase systems of 38,5 kV instead of 36 kV and 25 kV instead of 24 kV. These units have a rated power lower than or equal to 3 150 kVA:

  • with U = 38,5 kV are considered as U = 36 kV (ref. to EN 50708-2-1:2020); m m
  • with U = 25 kV are considered as U = 24 kV (ref. to EN 50708-2-1:2020). m m

3.2 large power transformer

LPT power transformer with at least one winding having either a rated power greater than 3 150 kVA or highest voltage for equipment greater than 36 kV Note 1 to entry: The definitions of power transformer and winding is given in EN 60076-1.

oSIST prEN 50708-1-1:2023 prEN 50708-1-1:2023 (E) Note 2 to entry: The national practice of Czech Republic requires the use of the highest voltages for equipment in AC three-phase systems of 38,5 kV instead of 36 kV and 25 kV instead of 24 kV. These units have a rated power greater than 3 150 kVA:

  • with U = 38,5 kV are considered as U = 36 kV (ref. to EN 50708-3-1:2020) m m
  • with U = 25 kV are considered as U = 24 kV (ref. to EN 50708-3-1:2020). m m

3.3 medium power pole-mounted transformer

medium power transformer with a rated power of up to 400 kVA suitable for outdoor service and specifically designed to be mounted on the support structures of overhead power lines Note 1 to entry: The definitions of power transformer and winding are given in EN 60076-1. Note 2 to entry: For definitions of pole see IEV [466–07–01].

3.4 load factor

k ratio of actual current over the rated current of transformer Note 1 to entry: Normally the ratio is 0 ≤ k ≤ 1.

3.5 transmitted apparent power

kSr product of the load factor and rated power

3.6 Efficiency Index

EI ratio of the transmitted apparent power of a transformer minus electrical losses to the transmitted apparent power of the transformer

3.7 Peak Efficiency Index

PEI maximum value of the ratio of the transmitted apparent power of a transformer minus the electrical losses to the transmitted apparent power of the transformer Note 1 to entry: PEI is the maximum value of EI that can be achieved at the optimum value of load factor.

3.8 load factor of Peak Efficiency Index

k PEI load factor at which Peak Efficiency Index occurs Note 1 to entry: Alternative cooling modes can require an iterative calculation of the k . In any case, the k is PEI PEI defined at the point where the highest PEI occurs.

3.9 declared value

value given in the technical documentation and where applicable, the value used to calculate this value Note 1 to entry: The values given are pursuant to point 2 of Directive 2009/125/EC, Annex IV.

oSIST prEN 50708-1-1:2023 prEN 50708-1-1:2023 (E)

3.9.1 declared value of loss

loss measured by the manufacturer and written in the test report part of technical documentation and on the rating plate Note 1 to entry: This definition applies both to no-load loss and to load loss. Note 2 to entry: Declared values and guaranteed values according to EN 60076-1 are two different concepts. Guaranteed values are related to contract, whereas declared values are related to compliance verifications with Commision Regulation (EU) No 548/2014.

Note 3 to entry: This definition complies with item g) of point 2 of Directive 2009/125/EC, Annex IV.

3.9.2 declared value of no-load loss

P

no-load loss measured by the manufacturer and written in the test report part of technical documentation and on the rating plate Note 1 to entry: For definition of no-load loss, see EN 60076-1.

3.9.3 declared value of load loss

P k load loss measured by the manufacturer and written in the test report part of technical documentation and on the rating plate Note 1 to entry: For definition of load loss, see EN 60076-1.

3.9.4 declared value of electrical power required by the cooling system for no-load operation P c0 electrical power required by fan and liquid pump motors for no-load operation as derived from the transformer type test certificates Note 1 to entry: The electrical power required by the cooling system for no-load operation is not measured all the time because this is a type test according to EN 60076-1.

3.9.5 declared value of additional electrical power required by the cooling system for the load factor of k P (k) ck additional electrical power required (in addition to P ) by the cooling system for continuous operation c0 at k times the rated load ensuring the compliance with the temperature rise derived from the transformer type test measurements of the power taken by the fan and liquid pump motors Note 1 to entry: The electrical power required by the cooling system for k times the rated load operation is not measured all the time, because this is a type test according to EN 60076-1. It can be extrapolated from the temperature rise test.

3.9.6 declared value of PEI

PEI calculated from the declared values of no-load loss, load loss and power required by the cooling system for load operation at k according to the above definitions PEI

oSIST prEN 50708-1-1:2023 prEN 50708-1-1:2023 (E)

3.10 dual voltage transformer

transformer with one or more windings with two voltages available in order to be able to operate and supply rated power at either of two different voltage values

3.11 acceptance test

contractual test to prove to the customer that the item meets certain conditions of its specification Note 1 to entry: The test may be witnessed by the purchaser or/and a third party. Note 2 to entry: The common IEC acceptance tests do not require witnesses. Routine tests are performed on every transformer; for this reason, the factory acceptance test shall be agreed between purchaser and supplier at the order stage.

[SOURCE: IEV ref 151-16-23]

3.12 witnessed testing

active observance of the physical testing of the product under investigation by another party, to draw conclusions on the validity of the test and the test results and which may include conclusions on the compliance of testing and calculations methods used with applicable standards and legislation

3.13 instrument transformer

transformer intended to transmit an information signal to measuring instruments, meters and protective or control devices or similar apparatus even if it supplies energy for the operation of connected equipment Note 1 to entry: The difference between the definition in Commission Regulation (EU) No. 548/2014 and the CENELEC one is in the use of the word ‘supply’ rather than ‘transmit an information signal’. [SOURCE: EN 61869-1:2009, 3.1.1, modified] 3.14 transformer specifically designed and intended to provide a DC power supply to electronic or rectifier loads transformer specifically designed and intended to supply power electronic or rectifier loads specified according to EN 61378-1:2011 Note 1 to entry: This definition covers transformers designed for use with rectifiers to provide a DC supply in certain applications.

Note 2 to entry: This definition does not include:

  • transformers which are intended to provide AC from DC sources such as transformers for wind turbine and photo voltaic applications;
  • transformers designed for DC transmission and distribution applications. Therefore, they are part of the scope of this document and are expected to comply with Commission Regulation (EU) No. 548/2014.

3.15 transformer specifically designed for offshore applications and floating offshore applications transformer to be installed on fixed or floating offshore platforms, offshore wind turbines or on board ships and all kinds of vessels

oSIST prEN 50708-1-1:2023 prEN 50708-1-1:2023 (E)

3.16 transformer specially designed for emergency installations

transformer designed to only provide cover for a specific time limited situation when the normal power supply is interrupted either due to an unplanned occurrence such as failure or a station refurbishment, but not to permanently upgrade an existing substation Note 1 to entry: Such transformer could have some specific features that make it suitable for emergency or temporary use as opposed to normal use. Example of some specific features:

  • multiple windings making it suitable for use at several locations;
  • special low weight or dimensions for easy transport, or special capability to be disassembled into smaller units for transport;
  • increased overload capability achieved by the use of special material;
  • permanent mounting on a transporter arrangement.

3.17 transformer and auto-transformer specifically designed for railway feeding systems traction transformer Note 1 to entry: The definition of traction transformer given by EN 50329 is a transformer (with separate or autoconnected windings) connected to an a.c. or d.c. contact line, directly or through a converter, used in fixed installations of railway applications.

3.18 earthing or grounding transformer

three-phase transformer or reactor connected in a power system to provide a neutral connection for earthing either directly or via an impedance [SOURCE: EN 60076-6:2008, 3.1.10, modified]

3.19 traction transformer

transformer installed on board of rolling stock inserted in the traction and auxiliary circuits of rolling stock and in the scope of EN 60310:2016 3.20 starting transformer specifically designed for starting three-phase induction motors so as to eliminate supply voltage dips transformer that is de-energized during normal operation, and used for the purpose of starting a rotating machine 3.21 Medium Voltage (MV) to Medium Voltage (MV) interface transformer up to 5 MVA transformer used in network voltage conversion program and placed at the junction between two voltage levels of two MV networks and which needs to be able to cope with emergency overloads Note 1 to entry: Such units might or might not be part of a packaged compact substation including also MV Reclosers and protection equipment.

3.22 durability

<of a part or a product> ability to funtion as required, under defined condition of use, maintenance and repair, until a limiting state is reached Note 1 to entry: The degree to which maintenance and repair are within the scope of durability will vary by product or product-group.

oSIST prEN 50708-1-1:2023 prEN 50708-1-1:2023 (E) Note 2 to entry: The user of this document shall define the criteria for the transition from limiting state to end-of-life (EoL).

Note 3 to entry: Durability can be expressed in units appropriate to the part or product concerned, e.g. calendar time, operating cycles, distance run, etc. The units should always be clearly stated.

3.23 reliability

probability that a product functions as required under given conditions, including maintenance, for a given duration without limiting event Note 1 to entry: The intended funtion(s) and given conditions are described in the information for use provided with the product.

Note 2 to entry: Duration can be expressed in units appropriate to the part or product concerned, e.g. calendar time, operating cycles, distance run, etc. The units should always be clearly stated.

3.24 limiting event

occurrence which results in a primary or secondary function no longer being delivered EXAMPLES failures, wear-out failure or deviation of any analougue signal

3.25 limiting state

condition after one or more limiting event(s) Note 1 to entry: A limiting state can be changed to a functional state by maintenance or repair of ErP. Note 2 to entry: A limiting state can change to EoL-status if maintenance or repair is no longher viable due to socioeconomic or technical reasons.

3.26 remanufacturing

industrial process which produces a product from used products or used parts where at least one change is made which influences the safety, original performance, purpose or type of product Note 1 to entry: The product created by the remanufacturing process may be considered a new product when placing on the market. Refer to the EU Blue Guide for additional information. Note 2 to entry: Refurbishing is a similar concept to remanufacturing except that it does not involve changes influencing safety, original performance, purpose or type of the product.

3.27 reuse

process by which a product or its parts, having reached the end of their first use, are used for the same purpose for which they were conceived Note 1 to entry: Reuse after a second or subsequential usage is also considered as reuse, but normal, regular or sporadic use is not considered a reuse.

3.28 repair

process returning a faulty product to a condition where it can fulfil its intended use

3.29 upgrade

process of enhancing the functionality, performance, capacity or aesthetics of a product Note 1 to entry: An update to a product can involve changes to its software, firmware and/or hardware.

oSIST prEN 50708-1-1:2023 prEN 50708-1-1:2023 (E) Note 2 to entry: Refer to the “Blue Guide” for conditions under with a product is considered as a new product when placing it on the market after upgrading it.

3.30 recovery

operation of any kind, the principal result of which is waste serving a useful purpose by replacing other materials which would otherwise have been used to fulfil a particular function, or waste being prepared to fulfil that function, in the plant or in the wider economy Note 1 to entry: Annex II of the Waste Framework Directive (2008/98/EC) sets out a non-exhaustive list of recovery operations.

3.31 material recovery

recovery operation of any kind, other than energy recovery and reprocessing into materials that are to be use as fuels or other means to generate energy Note 1 to entry: Material recovery includes, inter alia, preparing for reuse, recycling and backfilling.

3.32 energy recovery

production of useful energy through direct and controlled combustion or other processing of waste

3.33 recycling

recovery operation of any kind, by which waste materials are reprocessed into products, materials or substances whether for the original or other purposes excluding energy recovery Note 1 to entry: Recycling includes the reprocessing of organic material but does not include energy recovery and the reprocessing into materials that are to be used as fuels or for backfilling operations.

3.34 waste

substance or object of any kind, which the holder discards or intends or is required to discard

3.35 component

hardware constituent of a product that cannot be taken apart without destruction or impairment of its intended use Note 1 to entry: A component which is used again with or without alteration is considered a reused component.

4 Service condition

See EN 60076-1.

5 Ratings and general requirements

5.1 Rated power

The reference rated power for any losses evaluation is the continuous rated power as stated in EN 60076-1.

If additional cooling systems such as fans or pumps are to provide additional power for a situation limited in time when the normal power supply is interrupted due to either an unplanned occurrence (such as a power failure) or a station refurbishment, but not to permanently upgrade an existing substation, then such overloading rating cannot be claimed to be the rated power.

oSIST prEN 50708-1-1:2023 prEN 50708-1-1:2023 (E)

...