High-voltage switchgear and controlgear - Gas-filled compartments of AC switchgear and controlgear with rated voltages above 1 kV up to and including 52 kV

This document applies to pressurized compartments (gas-filled compartments with maximum allowable pressure above 50 kPa relative) of AC switchgear and controlgear with rated voltages above 1 kV up to and including 52 kV for indoor or outdoor installations. All gases stable and non-corrosive in the conditions that prevail inside the compartment are covered e.g. gases such as SF6, compressed air, natural-origin gases, alternative fluorinated compounds used alone or in gas mixtures with natural origin gases. The gas or gas mixture being used principally for its dielectric and/or arc-quenching properties.

Hochspannungs-Schaltgeräte und -Schaltanlagen – Gasgefullte Schottraume für Wechselstrom-Schaltgerate und -Schaltanlagen mit Nennspannungen über 1 kV bis einschliel3lich 52 kV

Appareillage à haute tension - Compartiments sous pression de gaz pour appareillage à courant alternatif de tensions assignées supérieures à 1 kV et inférieures ou égales à 52 kV

Le présent document s’applique aux compartiments sous pression (compartiments sous pression de gaz d’une pression admissible maximale supérieure à 50 kPa, pression relative) d’appareillages à courant alternatif de tensions assignées supérieures à 1 kV et inférieures ou égales à 52 kV, pour installation intérieure ou extérieure. Tous les gaz stables et non corrosifs dans les conditions régnant à l’intérieur du compartiment sont couverts, comme le SF6, l’air comprimé, les gaz d’origine naturelle et les autres composés fluorés utilisés seuls ou en mélanges de gaz d’origine naturelle, le gaz ou le mélange de gaz étant principalement utilisé pour ses propriétés diélectriques et/ou ses propriétés d’extinction des arcs.

Visokonapetostne stikalne in krmilne naprave - Plinske pregrade za stikalne in krmilne naprave z izmeničnim tokom z naznačeno napetostjo nad 1 kV do vključno 52 kV

General Information

Status
Not Published
Current Stage
4099 - Decision to launch vote
Due Date
25-Apr-2022
Completion Date
25-Apr-2022

RELATIONS

Buy Standard

Draft
prEN 50187:2021
English language
12 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (sample)

SLOVENSKI STANDARD
oSIST prEN 50187:2021
01-oktober-2021
Visokonapetostne stikalne in krmilne naprave - Plinske pregrade za stikalne in
krmilne naprave z izmeničnim tokom z naznačeno napetostjo nad 1 kV do vključno
52 kV

High-voltage switchgear and controlgear - Gas-filled compartments of AC switchgear and

controlgear with rated voltages above 1 kV up to and including 52 kV
Gasgefullte Schottraume für Wechselstrom-Schaltgerate und -Schaltanlagen mit
Nennspannungen über 1 kV bis einschliel3lich 52 kV

Appareillage à haute tension - Compartiments sous pression de gaz pour appareillage à

courant alternatif de tensions assignées supérieures à 1 kV et inférieures ou égales à 52

Ta slovenski standard je istoveten z: prEN 50187:2021
ICS:
29.130.99 Druge stikalne in krmilne Other switchgear and
naprave controlgear
oSIST prEN 50187:2021 en,fr,de

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN 50187:2021
---------------------- Page: 2 ----------------------
oSIST prEN 50187:2021
EUROPEAN STANDARD DRAFT
prEN 50187
NORME EUROPÉENNE
EUROPÄISCHE NORM
August 2021
ICS 29.130.99 Will supersede EN 50187:1996 and all of its
amendments and corrigenda (if any)
English Version
High-voltage switchgear and controlgear - Gas-filled
compartments of AC switchgear and controlgear with rated
voltages above 1 kV up to and including 52 kV

Appareillage à haute tension - Compartiments sous Gasgefullte Schottraume für Wechselstrom-Schaltgerate

pression de gaz pour appareillage à courant alternatif de und -Schaltanlagen mit Nennspannungen über 1 kV bis

tensions assignées supérieures à 1 kV et inférieures ou einschliel3lich 52 kV
égales à 52 kV
This draft European Standard is submitted to CENELEC members for enquiry.
Deadline for CENELEC: 2021-10-29.
It has been drawn up by CLC/TC 17AC.

If this draft becomes a European Standard, CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which

stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CENELEC in three official versions (English, French, German).

A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to

the CEN-CENELEC Management Centre has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,

Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the

Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,

Turkey and the United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to

provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and

shall not be referred to as a European Standard.
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels

© 2021 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.

Project: 70260 Ref. No. prEN 50187:2021 E
---------------------- Page: 3 ----------------------
oSIST prEN 50187:2021
prEN 50187:2021 (E)
1 Contents Page

2 European foreword .................................................................................................................................... 3

3 Introduction ................................................................................................................................................ 4

4 1 Scope ............................................................................................................................................. 5

5 2 Normative references ................................................................................................................... 5

6 3 Terms and definitions .................................................................................................................. 5

7 4 Normal and special service conditions ...................................................................................... 6

8 5 Design and construction .............................................................................................................. 6

9 5.1 General ........................................................................................................................................... 6

10 5.2 Materials ........................................................................................................................................ 7

11 5.3 Corrosion allowance .................................................................................................................... 7

12 5.4 Manholes and inspection openings ............................................................................................ 7

13 5.5 Design pressure ............................................................................................................................ 7

14 5.6 Design temperature ...................................................................................................................... 7

15 5.7 Design ............................................................................................................................................ 7

16 5.7.1 General ........................................................................................................................................... 7

17 5.7.2 Calculation methods .................................................................................................................... 8

18 6 Manufacturing and workmanship ............................................................................................... 8

19 7 Quality assurance ......................................................................................................................... 8

20 8 Inspection and testing .................................................................................................................. 9

21 8.1 General ........................................................................................................................................... 9

22 8.2 Routine pressure test ................................................................................................................... 9

23 8.3 Type tests ...................................................................................................................................... 9

24 9 Pressure relief devices ................................................................................................................. 9

25 10 Certification and marking ..........................................................................................................10

26 10.1 Design specification, drawings and data sheets.....................................................................10

27 10.2 Certificates ..................................................................................................................................10

28 10.3 Marking ........................................................................................................................................10

29 10.4 Final Inspection ..........................................................................................................................10

30 11 Transport .....................................................................................................................................10

31 Annex A (informative) A-deviations ......................................................................................................11

32 Bibliography .............................................................................................................................................12

---------------------- Page: 4 ----------------------
oSIST prEN 50187:2021
prEN 50187:2021 (E)
34 European foreword

35 This document [prEN 50187:2021] has been prepared by CLC/TC17AC "High-voltage switchgear and

36 controlgear".
37 This document is currently submitted to the Enquiry.
38 The following dates are proposed:
• latest date by which the existence of this (doa) dor + 6 months
document has to be announced at national
level
• latest date by which this document has to be (dop) dor + 12 months
implemented at national level by publication of
an identical national standard or by
endorsement
• latest date by which the national standards (dow) dor + 36 months
conflicting with this document have to be (to be confirmed or
withdrawn modified when voting)

39 This document will supersede EN 50187:1996 and all its amendments and corrigenda (if any).

40 This edition includes the following significant technical changes with respect to EN 50187:1996:

41 ▪ Consistency with EN 62271-200;
42 ▪ Added references to quality standards for welding;
43 ▪ Added Clause 11 on transport;

44 ▪ Removal of the limitation on maximum product pressure x volume of 2 000 bar litres in the scope;

45 ▪ Removal of the 300 kPa design pressure limitation;

46 ▪ Compressed air, natural origin gases, alternative fluorinated compounds used alone or in gas mixtures with

47 natural-origin gases are added in the scope.

48 The present document has been established as an international specification for the design, construction,

49 testing and certification of pressurized compartments used in high-voltage switchgear and controlgear,

50 regarding safety aspects.

51 In this respect, this document constitutes the exclusion of HV switchgear from the scope of the Directive

52 2014/68/EU (superseding 97/23/EC) concerning pressure equipment. Article 1, 2. (l) excludes “compartments

53 for high-voltage electrical equipment such as switchgear, controlgear, transformers, and rotating machines”

54 from the scope of the Directive.

55 This document supplements the general specifications given in EN 62271-200 in that it provides specific

56 requirements for pressurized gas-filled compartments of high-voltage switchgear and controlgear.

57 Due to the compartment geometries dictated by electrical and installation conditions they require the verification

58 of the design by proof tests instead of calculations.

59 National deviations from this European Standard are listed in Annex A (informative).

Compressed air, natural-origin gases and alternative fluorinated compounds used alone or in gas mixtures

with natural origin gases are described in future edition 2 of IEC 62271-4.
---------------------- Page: 5 ----------------------
oSIST prEN 50187:2021
prEN 50187:2021 (E)
60 Introduction

61 This document covers the requirements for the design, construction, testing, transportation, inspection and

62 certification of gas-filled compartments with maximum allowable pressure above 50 kPa (relative), for use in AC

63 switchgear and controlgear or for associated gas-filled equipment. Special consideration is given to these

64 compartments for the following reasons:

65 a) The compartments usually form the containment of electrical equipment; thus, their shape is determined

66 by electrical rather than mechanical requirements.

67 b) The compartments are installed in restricted areas and the equipment is operated by instructed, authorized

68 persons only.

69 c) Compartments are normally filled with a thoroughly dried gas or gas mixture that is stable and non-corrosive

70 in the conditions that prevail inside the compartment. For this reason, no internal corrosion allowance is

71 required on the wall thickness of these compartments.

72 d) The compartments are subjected to only small fluctuations of pressure as the gas-filling density will be

73 maintained within close product related limitations to ensure satisfactory insulating and arc-quenching

74 properties. Therefore, the compartments are not liable to fatigue due to pressure cycling.

75 e) The operating pressure is relatively low.

76 Due to the foregoing reasons and to ensure the maximum service continuity as well as to reduce the risk of

77 moisture and dust entering the compartments which could endanger safe electrical operation of the switchgear,

78 no pressure tests should be carried out after installation and before placing in service and no periodic inspection

79 of the compartment interiors or pressure tests should be carried out after the equipment is placed in service.

80 Current known gases and gas mixtures which have been applied or proposed to be applied in high-voltage gas-

81 filled switchgear and controlgear are:
82 • Sulphur Hexafluoride (SF6)
83 • SF6 mixtures with N2 and with CF4
84 • Compressed air
85 • Natural-origin gases and their mixtures (N2, O2, CO2)
86 • C5 F10 O (C5-FK) in mixtures with natural-origin gases (C5-FK mixtures)
87 • C4F7N (C4-FN) in mixtures with natural-origin gases (C4-FN mixtures)
88 • C3H2F4 (HFO1234zeE)

89 Other gases and gas mixtures based or not on those mentioned above which comply with the condition c) above

90 are possible to apply this document.
---------------------- Page: 6 ----------------------
oSIST prEN 50187:2021
prEN 50187:2021 (E)
91 1 Scope

92 This document applies to pressurized compartments (gas-filled compartments with maximum allowable

93 pressure above 50 kPa relative) of AC switchgear and controlgear with rated voltages above 1 kV up to and

94 including 52 kV for indoor or outdoor installations. All gases stable and non-corrosive in the conditions that

95 prevail inside the compartment are covered e.g. gases such as SF6, compressed air, natural-origin gases,

96 alternative fluorinated compounds used alone or in gas mixtures with natural origin gases. The gas or gas

97 mixture being used principally for its dielectric and/or arc-quenching properties.

98 2 Normative references

99 The following documents are referred to in the text in such a way that some or all of their content constitutes

100 requirements of this document. For dated references, only the edition cited applies. For undated references, the

101 latest edition of the referenced document (including any amendments) applies.

102 EN 62271-1:2017, High-voltage switchgear and controlgear - Part 1: Common specifications for alternating

103 current switchgear and controlgear

104 EN 62271-200, High-voltage switchgear and controlgear - Part 200: AC metal-enclosed switchgear and

105 controlgear for rated voltages above 1 kV and up to and including 52 kV

106 EN ISO 3834 (all parts), Quality requirements for fusion welding of metallic materials (ISO 3834)

107 EN ISO 5817, Welding - Fusion-welded joints in steel, nickel, titanium and their alloys (beam welding excluded)

108 - Quality levels for imperfections (ISO 5817)
109 EN ISO 9606 (all parts), Qualification testing of welders - Fusion welding

110 EN ISO 14732, Welding personnel - Qualification testing of welding operators and weld setters for mechanized

111 and automatic welding of metallic materials (ISO 14732)
112 3 Terms and definitions

113 For the purposes of this document, the following terms and definitions apply.

114 ISO and IEC maintain terminological databases for use in standardization at the following addresses:

115 • ISO Online browsing platform: available at https://www.iso.org/obp
116 • IEC Electropedia: available at https://www.electropedia.org/
117 3.1
118 compartment

119 part of gas-insulated metal-enclosed switchgear retaining the insulating gas under the prescribed conditions

120 necessary to safely maintain the rated insulation level, protecting the equipment against external influences and

121 providing a high degree of protection to personnel
122 3.2
123 manufacturer

124 individual or body finally responsible for designing and producing the compartment

125 Note 1 to entry: In this document, this is the switchgear manufacturer, even when the compartment is produced by a sub-

126 manufacturer.
---------------------- Page: 7 ----------------------
oSIST prEN 50187:2021
prEN 50187:2021 (E)
127 3.3
128 design pressure (of a compartment)
129 upper limit of the relative pressure between the pressure insi
...

Questions, Comments and Discussion