Abstract

IEC 61058-1:2026 applies to switches or switching devices for appliances. The switches are intended to control electrical appliances and other equipment for household or similar purposes with a rated voltage not exceeding 600 V and a rated current not exceeding 63 A. This fifth edition cancels and replaces the fourth edition published in 2016. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
a) Extension to 600 V in the scope;
b) Add requirements on ground-fuse (Clause 17);
c) DC arc extinction test (Annex P and Clause 17);
d) Table 5 re-arranged to line-up with classifications;
e) Table 6 correction due to inhomogeneous values;
f) Deletion of X3 capacitors in classification and in Table 19.

Status
Published
Publication Date
29-Jul-2026
Current Stage
PPUB - Publication issued - 60 Publication
Start Date
30-Jul-2026
Due Date
31-Jul-2026
Completion Date
31-Jul-2026

Buy Documents

Standard

IEC 61058-1:2026 - Switches for appliances - Part 1: General requirements

ISBN:978-2-8327-1361-7
Release Date:30-Jul-2026
English language (124 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

REDLINE IEC 61058-1:2026 RLV - Switches for appliances - Part 1: General requirements

ISBN:978-2-8327-1432-4
Release Date:30-Jul-2026
English language (255 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

IEC 61058-1:2026 - Interrupteurs pour appareils - Partie 1: Exigences générales

ISBN:978-2-8327-1361-7
Release Date:30-Jul-2026
French language (131 pages)
sale 15% off
Preview
sale 15% off
Preview

IEC 61058-1:2026 is an International Standard from the IEC for switches and switching devices for appliances. It specifies general requirements for switches used to control electrical appliances and other equipment for household or similar purposes, with rated voltage not exceeding 600 V and rated current not exceeding 63 A. It is intended for manufacturers, test laboratories, certification bodies, quality teams and buyers who need to identify, test and specify appliance switches.

What does IEC 61058-1:2026 specify?

IEC 61058-1:2026 applies to switches or switching devices for appliances, including products operated directly by a person, by indirect actuation, or by an actuating sensing unit. The standard also covers switches with electronic control functions and the circuitry needed for the switching function.

IEC 61058-1:2026 uses the terms “switching devices” and “switches” interchangeably in the IEC 61058 series. It applies in conjunction with Part 1-1 for mechanical switches and Part 1-2 for electronic switches, and it excludes switches covered by IEC 60669 and IEC 60730.

The document is organized into clauses 1 to 25, followed by annexes that support measurement, testing, application guidance and production sampling.

AnnexWhat it covers
Annex AMeasurement of clearances and creepage distances
Annex BDiagram for dimensioning clearances and creepage distances
Annex CProof tracking test
Annex DSwitch application guide
Annex LGuidance for production sampling after type testing
Annex MExample grouping of switch types into switch families
Annex PDC arc extinction test

What are the key requirements of IEC 61058-1:2026?

IEC 61058-1:2026 combines ratings, classification, marking, construction and test requirements so a switch can be declared for a specific appliance use and then verified against that declaration. In practice, the standard tells the manufacturer what must be stated, how the product is built, and which tests demonstrate compliance.

How are switches tested?

Clause 5 sets the basic test conditions. IEC 61058-1:2026 says specimens are tested as delivered and mounted as declared by the manufacturer, with actuation allowed by test equipment where suitable. The clause also allows representative testing in some cases, so not every rating combination needs a separate full test plan if the standard permits equivalence.

This matters because the declared mounting, loading and operating method affect the result. A switch that passes in the wrong setup may not be safe in the appliance it is actually intended for.

What ratings and classifications does it use?

Clause 6 sets the maximum rated voltage at 600 V and the maximum rated current at 63 A. Clause 7 then classifies switches by supply type, load type, ambient temperature, number of operating cycles, ingress protection, electric shock protection class, pollution degree, marking mode, glow-wire resistance, impulse withstand voltage, overvoltage category, type of disconnection, coating type, terminal type, switching configuration, duty type, linkage between actuator and contact speed, built-in protection, forced cooling and capacitor class.

This classification is practical because it defines the intended duty of the switch. For a buyer or engineer, it shows whether a switch is meant for AC, DC or both, what kind of load it may control, and what environmental or safety limits apply.

What must be marked or documented?

Clause 8 separates information that is given by marking from information that is given by documentation. The standard uses this to identify the manufacturer or vendor, the type reference, rated voltage and current, load type, ambient temperature limits, operating cycles, terminals, disconnection type, duty pattern, cooling conditions and protective-device data.

IEC 61058-1:2026 also requires marking to remain legible and durable. In practice, this helps installers, inspectors and service personnel match the switch to its declared use without relying on guesswork.

How does the standard address safety, terminals and construction?

Clauses 9 to 13 deal with protection against electric shock, earthing, terminals, construction and mechanism. The requirements cover accessible parts, removable covers, actuating members, Class II use, earthing arrangements for Class I products, and safe mounting of the switch in the appliance.

Clause 11 is especially detailed on terminals and terminations. It covers terminal design, fixing, location, shielding, interconnection of multiple conductors, thermal stress and the terminal tests TT1 to TT4, including conductor escape, terminal displacement and strand escape. This is important because many field failures start at the wiring connection rather than in the switching contact itself.

Clause 13 covers how the mechanism must behave. It addresses series contacts, intermediate positions, return or retention of the actuator after release, pull-cord operation and the way multi-pole switches make and break their poles.

Which electrical, thermal and mechanical checks are central?

Clauses 15 to 18 cover insulation resistance, dielectric strength, heating, endurance and mechanical strength. IEC 61058-1:2026 requires the switch to withstand electrical stress without breakdown, to stay within thermal limits in normal use, and to resist wear and other harmful effects during endurance testing.

Annex A and Annex B provide the methods used to measure and dimension clearances and creepage distances. Annex C defines the proof tracking test using IEC 60112. Annex P adds the DC arc extinction test sequence for the endurance evaluation of DC switches classified under the relevant load type.

These checks matter because they address the main failure modes of appliance switches: insulation breakdown, overheating, arcing, wear and loss of mechanical integrity.

How does it handle materials, components and EMC?

Clauses 20 to 25 cover clearances, creepage distances, solid insulation, coatings of rigid printed board assemblies, resistance to heat and abnormal heat, resistance to rusting, abnormal operation and fault conditions, switch components and EMC requirements. Clause 24 addresses protective devices, fuses, cut-outs, PTC thermistors, capacitors and resistors.

Clause 25 covers both immunity and emission. The immunity tests include voltage dips and short interruptions, surge, electrical fast transient, electrostatic discharge, radiated electromagnetic field and power-frequency magnetic field tests. The emission side covers low-frequency and radio-frequency emission. For products that include electronics, this is often a decisive part of the evaluation.

What terms does IEC 61058-1:2026 define?

IEC 61058-1:2026 defines its own terminology in Clause 3, and several terms are used repeatedly in declarations, marking and testing.

TermMeaning in the standard
Switching deviceIn the IEC 61058 series, “switching devices” and “switches” are used interchangeably for appliance control products.
UTUnique type reference, the limited marking option for identifying a switch type.
CTCommon type reference, the full marking option for identifying a switch type.
PTIProof tracking test, the insulating-material test described in Annex C and based on IEC 60112.
Switch familyA grouping of switch types that are representative of one another in construction and performance for sampling plans.
Duty type S1/S2/S3The operating pattern codes used for continuous, short-time and intermittent periodic duty.
General purpose loadA declared load class for inductive or general use that is not specifically a motor or lamp load.

Who uses IEC 61058-1:2026?

IEC 61058-1:2026 is used by appliance switch manufacturers, appliance OEMs and design teams that need to choose the right switch rating, terminal type, enclosure protection and marking format. It is also used by test laboratories and certification bodies that verify insulation, heating, endurance, mechanical strength, EMC and abnormal-operation performance.

Quality managers and buyers use IEC 61058-1:2026 to compare offered products against a common technical basis. That is useful when checking whether a switch is intended for the right load type, environmental class, duty pattern and installation method.

What changed in IEC 61058-1:2026 from the previous edition?

IEC 61058-1:2026 is the fifth edition and it cancels and replaces IEC 61058-1:2016. The edition is identified as a technical revision, and the stated significant changes are:

  • Extension of the scope to 600 V
  • New requirements for ground-fuse in Clause 17
  • DC arc extinction test added in Clause 17 and Annex P
  • Table 5 re-arranged to line up with classifications
  • Table 6 corrected because of inhomogeneous values
  • X3 capacitors deleted from the classification and from Table 19

Which standards are used with IEC 61058-1:2026?

IEC 61058-1:2026 cites companion and supporting standards for fuses, capacitors, enclosures, insulation, fire testing, EMC, probes and related switch parts.

ReferenceWhat it contributes
IEC 60127, IEC 60269-3Fuse requirements used for protective-device related provisions
IEC 60384-14Capacitors for EMI suppression and connection to the supply mains
IEC 60417, IEC 60617Graphical symbols for equipment and diagrams
IEC 60529IP code for enclosure protection
IEC 60664-3Insulation coordination using coating, potting or moulding
IEC 60691Thermal-links
IEC 60695-2-11, IEC 60695-10-2, IEC 60695-11-10, IEC 60695-11-20Glow-wire, ball pressure and flame test methods
IEC 60730 (all parts), IEC 60730-1:2022, IEC 60730-2-9:2015 and amendmentsAutomatic electrical controls referenced for related functions and methods
IEC 60738-1PTC thermistors
IEC 61000-3-2, IEC 61000-3-3, IEC TS 61000-3-5EMC emission and flicker-related limits
IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-8, IEC 61000-4-11EMC immunity test methods
IEC 61032:1997Probes for verifying protection by enclosures
IEC 61058-1-1:2016, IEC 61058-1-2:2016Companion parts for mechanical and electronic switches
IEC 61210Flat quick-connect terminations
IEC 62368-1:2023Safety requirements for AV, ICT and related equipment
CISPR 14-1, CISPR 15:2018 and amendmentEmission limits and methods for household, lighting and similar equipment

What does the IEC 61058-1:2026 document contain?

IEC 61058-1:2026 contains 25 clauses, plus annexes and figures that support design, testing and certification. The body includes tables for classification, marking, terminal types, dielectric strength, load ratings and EMC-related information, as well as figures for terminal constructions, load circuits, impact mounting, duty cycles and endurance test setups.

Annex A and Annex B explain how to measure and dimension clearances and creepage distances. Annex C gives the proof tracking test, Annex D is an application guide, Annex L supports production sampling after type testing, Annex M gives an example of switch-family grouping, and Annex P covers DC arc extinction testing.

In practice, the document is used to design a switch, verify a prototype, define type tests, check production consistency and support conformity assessment.

Relations

Effective Date
05-Sep-2023

Buy Documents

Standard

IEC 61058-1:2026 - Switches for appliances - Part 1: General requirements

ISBN:978-2-8327-1361-7
Release Date:30-Jul-2026
English language (124 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

REDLINE IEC 61058-1:2026 RLV - Switches for appliances - Part 1: General requirements

ISBN:978-2-8327-1432-4
Release Date:30-Jul-2026
English language (255 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

IEC 61058-1:2026 - Interrupteurs pour appareils - Partie 1: Exigences générales

ISBN:978-2-8327-1361-7
Release Date:30-Jul-2026
French language (131 pages)
sale 15% off
Preview
sale 15% off
Preview

Get Certified

Connect with accredited certification bodies for this standard

IMQ S.p.A. (Certification)

Italian electrical product certification.

ACCREDIA Italy Verified

SLG Prüf- und Zertifizierungs GmbH

German testing and certification body.

DAKKS Germany Verified

UL Solutions

Global safety science company with testing, inspection and certification.

ANAB United States Verified

Sponsored listings

Frequently Asked Questions

IEC 61058-1:2026 is a standard published by the International Electrotechnical Commission (IEC). Its full title is "Switches for appliances - Part 1: General requirements". This standard covers: IEC 61058-1:2026 applies to switches or switching devices for appliances. The switches are intended to control electrical appliances and other equipment for household or similar purposes with a rated voltage not exceeding 600 V and a rated current not exceeding 63 A. This fifth edition cancels and replaces the fourth edition published in 2016. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) Extension to 600 V in the scope; b) Add requirements on ground-fuse (Clause 17); c) DC arc extinction test (Annex P and Clause 17); d) Table 5 re-arranged to line-up with classifications; e) Table 6 correction due to inhomogeneous values; f) Deletion of X3 capacitors in classification and in Table 19.

IEC 61058-1:2026 applies to switches or switching devices for appliances. The switches are intended to control electrical appliances and other equipment for household or similar purposes with a rated voltage not exceeding 600 V and a rated current not exceeding 63 A. This fifth edition cancels and replaces the fourth edition published in 2016. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) Extension to 600 V in the scope; b) Add requirements on ground-fuse (Clause 17); c) DC arc extinction test (Annex P and Clause 17); d) Table 5 re-arranged to line-up with classifications; e) Table 6 correction due to inhomogeneous values; f) Deletion of X3 capacitors in classification and in Table 19.

IEC 61058-1:2026 is classified under the following ICS (International Classification for Standards) categories: 29.120.40 - Switches. The ICS classification helps identify the subject area and facilitates finding related standards.

IEC 61058-1:2026 has the following relationships with other standards: It is inter standard links to IEC 61058-1:2016. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

IEC 61058-1:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 3.1 General terms and definitions
  • 3.1.1 mechanical switching device
  • 3.1.2 conductive part
  • 3.1.3 live part
  • 3.1.4 pole of a switching device
  • 3.1.5 detachable part
  • 3.1.6 tool
  • 3.1.7 normal use
  • 3.1.8 unique type reference
  • 3.1.9 common type reference
  • 3.1.10 cover
  • 3.1.11 signal indicator
  • 3.1.12 unprepared conductor
  • 3.1.13 prepared conductor
  • 3.1.14 polarity reversal
  • 3.1.15 semiconductor device
  • 3.1.16 semiconductor circuit
  • 3.1.17 electronic switch
  • 3.1.18 duty
  • 3.1.19 duty-type
  • 3.1.20 protective impedance
  • 3.1.21 exposed conductive parts
  • 3.2 Terms and definitions relating to voltage and current
  • 3.2.1 rated voltage
  • 3.2.2 safety extra-low voltage
  • 3.2.3 rated current
  • 3.2.4 rated load
  • 3.2.5 over-current
  • 3.2.6 working voltage
  • 3.2.7 overvoltage
  • 3.2.8 overvoltage category
  • 3.2.9 impulse withstand voltage
  • 3.2.10 minimum load
  • 3.2.11 thermal current
  • 3.3 Terms and definitions relating to the different types of switches
  • 3.3.1 incorporated switch
  • 3.3.2 integrated switch
  • 3.3.3 rotary switch
  • 3.3.4 lever switch
  • 3.3.5 rocker switch
  • 3.3.6 push-button switch
  • 3.3.7 cord-operated switch
  • 3.3.8 push-pull switch
  • 3.3.9 biased switch
  • 3.4 Terms and definitions relating to the operation of the switch
  • 3.4.1 actuation
  • 3.4.2 indirect actuation
  • 3.4.3 actuating member
  • 3.4.4 actuating means
  • 3.4.5 disconnection
  • 3.4.6 micro-disconnection
  • 3.4.7 electronic-disconnection
  • 3.4.8 full-disconnection
  • 3.4.9 all-pole disconnection single-phase
  • 3.4.10 operating cycle
  • 3.4.11 electronic actuating member
  • 3.4.12 electronic actuating means
  • 3.4.13 abnormal conditions
  • 3.4.14 sensing unit
  • 3.4.15 fault conditions
  • 3.5 Terms and definitions relating to connections to the switch
  • 3.5.1 external conductor
  • 3.5.2 integrated conductor
  • 3.6 Terms and definitions relating to terminals and terminations
  • 3.6.1 terminal
  • 3.6.2 screw type terminal
  • 3.6.3 screwless terminal
  • 3.6.4 termination
  • 3.6.5 flat quick-connect termination
  • 3.6.6 tab
  • 3.6.7 female connector
  • 3.6.8 solder terminal
  • 3.6.9 insulation-piercing terminal
  • 3.7 Terms and definitions relating to insulation
  • 3.7.1 basic insulation
  • 3.7.2 supplementary insulation
  • 3.7.3 double insulation

1 Scope

This part of IEC 61058 applies to switches or switching devices for appliances. The switches are intended to control electrical appliances and other equipment for household or similar purposes with a rated voltage not exceeding 600 V and a rated current not exceeding 63 A. In the IEC 61058 series the terms "switching devices" and "switches" are used interchangeably. Switches for appliances are intended to be operated by - a person via an actuating member, - indirect actuation, - an actuating sensing unit.

Transmission of a signal between the actuating member or sensing unit and the switch can be connected by optical, acoustic, thermal, electrical or other relevant connection and can include remote controlled units.

This document applies to switches for appliances with additional control functions provided by the switch using electronic circuits.

This document applies to circuitry when evaluated with a switch and necessary for the switching function.

This part document applies in general to switches for appliances in conjunction with the following parts:

  • Part 1-1: Requirements for mechanical switches, and/or
  • Part 1-2: Requirements for electronic switches.

This document does not apply to switches covered by:

  • IEC 60669 (all parts), Switches for household and similar fixed-electrical installations, and
  • IEC 60730 (all parts), Automatic electrical controls.

NOTE 1 Attention is drawn to the fact that the end product standards for appliances can contain additional or alternative requirements for switches (see Annex O).

NOTE 2 Throughout this document, the word "appliance" means "appliance or equipment".

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.

IEC 60127 (all parts), Miniature fuses IEC 60269-3, Low-voltage fuses - Part 3: Supplementary requirements for fuses for use by unskilled persons (fuses mainly for household or similar applications) - Examples of standardized systems of fuses A to F IEC 60384-14, Fixed capacitors for use in electronic equipment - Part 14: Sectional specification - Fixed capacitors for electromagnetic interference suppression and connection to the supply mains

IEC 60417, Graphical symbols for use on equipment (available at: http://www.graphicalsymbols.info/equipment) IEC 60529:1989, Degree of protection provided by enclosures (IP code) IEC 60529:1989/AMD1:1999 IEC 60529:1989/AMD2:2013 IEC 60617, Graphical symbols for diagrams IEC 60664-3:2016, Insulation coordination for equipment within low-voltage systems - Part 3:

Use of coating, potting or moulding for protection against pollution IEC 60691, Thermal-links - Requirements and application guide IEC 60695-2-11, Fire hazard testing - Part 2-11: Glowing/hot-wire based test methods - Glow-wire flammability test method for end-products IEC 60695-10-2, Fire hazard testing - Part 10-2: Abnormal heat - Ball pressure test method IEC 60695-11-10, Fire hazard testing - Part 11-10: Test flames - 50 W horizontal and vertical flame test methods IEC 60695-11-20, Fire hazard testing - Part 11-20: Test flames - 500 W flame test method IEC 60730 (all parts), Automatic electrical controls IEC 60730-1:2022, Automatic electrical controls - Part 1: General requirements IEC 60730-2-9:2015, Automatic electrical controls - Part 2-9: Particular requirements for temperature sensing controls IEC 60730-2-9:2015/AMD1:2018 IEC 60730-2-9:2015/AMD2:2020 IEC 60738-1, Thermistors - Directly heated positive temperature coefficient - Part 1: Generic specification IEC 61000-3-2, Electromagnetic compatibility (EMC) - Part 3.2: Limits - Limits for harmonic current emissions (equipment input current ≤ 16 A per phase) IEC 61000-3-3, Electromagnetic compatibility (EMC) - Part 3-3: Limits - Limitation of voltage changes, voltage fluctuations and flicker in public low-voltage supply systems, for equipment with rated current ≤ 16 A per phase and not subject to conditional connection IEC TS 61000-3-5, Electromagnetic compatibility (EMC) - Part 3-5: Limits - Limitation of voltage fluctuations and flicker in low-voltage power supply systems for equipment with rated current greater than 75 A IEC 61000-4-2, Electromagnetic compatibility (EMC) - Part 4-2: Testing and measurement techniques - Electrostatic discharge immunity test IEC 61000-4-3, Electromagnetic compatibility (EMC) - Part 4-3: Testing and measurement techniques - Radiated, radio-frequency, electromagnetic field immunity test IEC 61000-4-4, Electromagnetic compatibility (EMC) - Part 4-4: Testing and measurement techniques - Electrical fast transient/burst immunity test

IEC 61000-4-5, Electromagnetic compatibility (EMC) - Part 4-5: Testing and measurement techniques - Surge immunity test IEC 61000-4-8, Electromagnetic compatibility (EMC) - Part 4-8: Testing and measurement techniques - Power frequency magnetic field immunity test IEC 61000-4-11, Electromagnetic compatibility (EMC) - Part 4-11: Testing and measurement techniques - Voltage dips, short interruptions and voltage variations immunity tests for equipment with input current up to 16 A per phase IEC 61032:1997, Protection of persons and equipment by enclosures - Probes for verification IEC 61058-1-1:2016, Switches for appliances - Part 1-1: Requirements for mechanical switches IEC 61058-1-2:2016, Switches for appliances - Part 1-2: Requirements for electronic switches IEC 61210, Connecting devices - Flat quick-connect terminations for electrical copper conductors - Safety requirements IEC 62368-1:2023, Audio/video, information and communication technology equipment - Part 1:

Safety requirements CISPR 14-1, Electromagnetic compatibility - Requirements for household appliances, electric tools and similar apparatus - Part 1: Emission CISPR 15:2018, Limits and methods of measurement of radio disturbance characteristics of electrical lighting and similar equipment CISPR 15:2018/AMD1:2024

3 Terms and definitions

For the purposes of this document, the following terms and definitions apply. ISO and IEC maintain terminology databases for use in standardization at the following addresses:

  • IEC Electropedia: available at https://www.electropedia.org/
  • ISO Online browsing platform: available at https://www.iso.org/obp

3.1 General terms and definitions

3.1.1 mechanical switching device

switching device designed to close and open one or more electric circuits by means of separable contacts Note 1 to entry: Any mechanical switching device may be designated according to the medium in which its contacts open and close, e.g. air, SF6 ("sulphur hexafluoride"), oil.

[SOURCE: IEC 60050-441:1984, 441-14-02]

3.1.2 conductive part

part which is capable of conducting current although it may not necessarily be used for carrying service current [SOURCE: IEC 60050-441:1984, 441-11-09]

3.1.3 live part

conductive part intended to be energized under normal operating conditions, including the neutral conductor and mid-point conductor, but excluding the PEN conductor, PEM conductor and PEL conductor [SOURCE: IEC 60050-195:2021, 195-02-19, modified – The domain <in electrical installations and equipment> has been removed.]

3.1.4 pole of a switching device

portion of a switching device associated exclusively with one electrically separated conducting path of its main circuit and excluding those portions which provide a means for mounting and operating all poles together Note 1 to entry: A switching device is called "single pole" if it has only one pole. If it has more than one pole, it may be called "multipole" (two-pole, three-pole, etc.) provided that the poles are coupled in such a manner as to operate together.

[SOURCE: IEC 60050-441:1984, 441-15-01]

3.1.5 detachable part

part which is removable without the use of a tool when the switch is mounted as in normal use

3.1.6 tool

screwdriver, or any other object which may be used to operate a nut, a screw or a similar part

3.1.7 normal use

use of the switch for the purpose for which it was made and declared

3.1.8 unique type reference

UT identification marking on a switch such that by quoting it in full to the switch manufacturer a unique switch model can be identified Note 1 to entry: This note applies to the French language only.

3.1.9 common type reference

CT identification marking on a switch which does not require any further specific information additional to that provided by the marking requirements of this document for selection, installation and use in accordance with this document

3.1.10 cover

cover plate cover made of insulating material, used to cover live parts in order to avoid accidental electric contact and which is accessible when the switch is mounted as in normal use

3.1.11 signal indicator

device associated with a switch to indicate the circuit state visually

3.1.12 unprepared conductor

conductor which has been cut and the insulation of which has been removed for insertion into a terminal Note 1 to entry: A conductor the shape of which is arranged for introduction into a terminal or the strands of which are twisted to consolidate the end is considered as an unprepared conductor. [SOURCE: IEC 60050-442:1998, 442-01-26]

3.1.13 prepared conductor

conductor the end of which is fitted with an attachment such as eyelet, sleeve or cable lug [SOURCE: IEC 60050-442:1998, 442-01-27]

3.1.14 polarity reversal

change of the polarity on the terminals connected to the load by a switching action

3.1.15 semiconductor device

SD device the essential electric characteristics of which are due to the flow of charge carriers within one or more semiconductor materials

3.1.16 semiconductor circuit

circuit containing multiple components, where at least one is a semiconductor device

3.1.17 electronic switch

switch for appliances provided with a semiconductor device or a semiconductor circuit in its intended load path Note 1 to entry: The electronic switch can be provided with series and/or parallel mechanical contacts.

3.1.18 duty

statement of the load to which the switch is subjected, including, if applicable, making, controlling and breaking and including their durations and sequence in time

3.1.19 duty-type

continuous, short-time or periodic duty comprising one or more loads remaining constant for the duration specified, or a non-periodic duty in which generally the load varies within the permissible operating range [SOURCE: IEC 60050-411:1996, 411-51-13, modified - "and speed" is deleted.]

3.1.20 protective impedance

component or assembly of components whose impedance and construction are intended to limit steady-state touch current and electric charge to non-hazardous levels [SOURCE: IEC 60050-195:2021, 195-06-34, modified - "device" is deleted.]

3.1.21 exposed conductive parts

conductive part of electrical equipment, which can be touched and which is not normally live, but which can become live when basic insulation fails Note 1 to entry: A conductive part of electrical equipment which can only become live through contact with an exposed-conductive-part which has become live is not considered to be an exposed-conductive-part itself. [SOURCE: IEC 60050-442:1998, 442-01-21]

3.2 Terms and definitions relating to voltage and current

3.2.1 rated voltage

voltage assigned by the manufacturer for a specified operating condition Note 1 to entry: This value is the maximum value and covers all lower values. [SOURCE: IEC 60050-442:1996, 442-01-03, modified - "accessory" is deleted]

3.2.2 safety extra-low voltage

SELV voltage which does not exceed 50 V AC RMS or 120 V DC between conductors or between any conductor and earth in a circuit which is insulated from the supply mains Note 1 to entry: SELV is an unearthed extra low voltage (see IEC 61140). Note 2 to entry: Different values for the SELV voltage limit may apply in the end equipment standard.

3.2.3 rated current

current assigned by the manufacturer for a specified operating condition Note 1 to entry: This value is the maximum value and covers all lower values. [SOURCE: IEC 60050-442:1998, 442-01-02, modified - "for accessory" is deleted.]

3.2.4 rated load

type of load assigned by the manufacturer, according to classifications

3.2.5 over-current

current exceeding the rated current [SOURCE: IEC 60050-441:1984/AMD1:2000, 441-11-06]

3.2.6 working voltage

highest RMS value of the AC or DC voltage across any particular insulation which can occur when the switch is supplied at rated voltage Note 1 to entry: Transients are disregarded.

Note 2 to entry: Both open-circuit conditions and normal operating conditions are taken into account. [SOURCE: IEC60050-851:2008, 851-12-31]

3.2.7 overvoltage

voltage having a peak value exceeding the corresponding peak value of maximum steady-state voltage at normal operating conditions

3.2.8 overvoltage category

numeral defining a transient overvoltage condition Note 1 to entry: See Annex E.

[SOURCE: IEC60050-581:2008, 581-21-02]

3.2.9 impulse withstand voltage

highest peak value of impulse voltage of prescribed form and polarity which does not cause breakdown of insulation under specified conditions [SOURCE: IEC60050-442:2014, 442-09-18]

3.2.10 minimum load

load at which when declared, the electronic switch still operates correctly

3.2.11 thermal current

continuous resistive current which, under the test conditions declared by the manufacturer (which may also include the ambient temperature), generates, without forced cooling, the same heating as when the electronic switch is operating under specified ambient conditions at rated load in the appliance with forced cooling present, if any Note 1 to entry: The concept "thermal current" allows simplified testing of electronic switches, which in normal application have complex cooling conditions. The thermal current will always be determined by tests of the switch positioned on a table or in a simple test rig and comparative tests in the appliance in question. Consequently, the thermal current will normally be lower than the rated current. This necessitates additional tests of the terminals, contacts, etc., in order to verify that they will be able to carry the rated current, when the electronic switch is mounted in the appliance. These additional tests are specified in Clause 17 of IEC 61058-1-2:2016.

3.3 Terms and definitions relating to the different types of switches

3.3.1 incorporated switch

switch intended for incorporation in or on an appliance, which however can be tested separately [SOURCE: IEC 60050-442:1998, 442-04-01]

3.3.2 integrated switch

switch, the function of which is depending on its correct mounting and fixing in an appliance, and which can be tested only in combination with the relevant parts of that appliance [SOURCE: IEC 60050-442:1998, 442-04-02]

3.3.3 rotary switch

switch where the actuating member is a shaft or a spindle which has to be rotated to one or more indexed positions in order to achieve a change in contact state Note 1 to entry: The rotation of the actuating member may be unlimited or restricted in either direction. [SOURCE: IEC 60050-442:1998, 442-04-04]

3.3.4 lever switch

switch where the actuating member is a lever which has to be moved (tilted) to one or more indexed positions in order to achieve a change in contact state [SOURCE: IEC 60050-442:1998, 442-04-05]

3.3.5 rocker switch

switch where the actuating member is a low-profile lever (rocker) which has to be tilted to one or more indexed positions in order to achieve a change in contact state [SOURCE: IEC 60050-442:1998, 442-04-06]

3.3.6 push-button switch

switch where the actuating member is a button which has to be pushed in order to achieve a change in contact state Note 1 to entry: The switch can be provided with one or more actuating members. [SOURCE: IEC 60050-442:1998, 442-04-07]

3.3.7 cord-operated switch

switch where the actuating member is a pull-cord which has to be pulled in order to achieve a change in contact state [SOURCE: IEC 60050-442:1998, 442-04-08, modified - "operating means" changed to "actuating member".]

3.3.8 push-pull switch

switch where the actuating member is a rod which has to be pulled or pushed to one or more indexed positions in order to achieve a change in contact state [SOURCE: IEC 60050-442:1998, 442-04-09]

3.3.9 biased switch

switch where the contacts and actuating member return to a predetermined position when the actuating member is released following actuation [SOURCE: IEC 60050-442:1998, 442-04-10]

3.4 Terms and definitions relating to the operation of the switch

3.4.1 actuation

movement of the actuating member of the switch by hand, by foot, or by any other human activity

3.4.2 indirect actuation

movement of the actuating member of the switch indirectly by a part of an appliance into which the switch is incorporated or integrated, for example the door of an appliance [SOURCE: IEC 60050-442:1998, 442-04-13]

3.4.3 actuating member

part which is pulled, pushed, turned or otherwise moved to cause an operation of the switch [SOURCE: IEC 60050-442:1998, 442-04-14]

3.4.4 actuating means

any part which can be interposed between the actuating member and the contact mechanism in order to achieve contact operation [SOURCE: IEC 60050-442:1998, 442-04-15]

3.4.5 disconnection

interruption of an electrical circuit in a pole so as to provide insulation between the supply and those parts intended to be disconnected from the supply

3.4.6 micro-disconnection

disconnection that provides correct functional performance by contact separation in the case of long-term temporary overvoltage

3.4.7 electronic-disconnection

disconnection that provides a non-cycling correct functional performance by a semiconductor device (SD) in the case of long-term temporary overvoltage

3.4.8 full-disconnection

disconnection that provides correct functional performance by contact separation in the case of short-term and long-term temporary overvoltage and impulse withstand voltage equivalent to basic insulation

3.4.9 all-pole disconnection single-phase

concurrent disconnection of all supply conductors, except the earthed conductor, by a single switching action for AC and DC appliances

3.4.10 operating cycle

succession of operations from one position to another and back to the first position through all other positions, if any [SOURCE: IEC 60050-441:1984/AMD1:2000, 441-16-02]

3.4.11 electronic actuating member

part, component or component group which controls the actuating means or the switching device Note 1 to entry: An optical or acoustic sensing unit is an example of a component group.

3.4.12 electronic actuating means

part, component or component group which controls electronically the switching device

3.4.13 abnormal conditions

conditions leading to reduced safety, which may occur in the appliance or in the switch during normal operation Note 1 to entry: These conditions (e.g. rise in temperature, lack of protection against shock) may be the consequence of faults of the switch or related ambient conditions, which in case of defects or deteriorated operation of other components of the application are foreseeable. (Intended) misuse is not covered.

3.4.14 sensing unit

unit adjustable by other than mechanical means containing electronic components and controlling the output via electronic components or unit that is activated by any physical phenomenon or combination of phenomena

...

Contents

  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 3.1 General terms and definitions
  • 3.1.1 mechanical switching device
  • 3.1.2 conductive part
  • 3.1.3 live part
  • 3.1.4 pole of a switch switching device
  • 3.1.5 detachable part
  • 3.1.6 tool
  • 3.1.7 normal use
  • 3.1.8 unique type reference
  • 3.1.9 common type reference
  • 3.1.10 cover
  • 3.1.11 signal indicator
  • 3.1.12 unprepared conductor
  • 3.1.13 prepared conductor
  • 3.1.14 polarity reversal
  • 3.1.15 semiconductor device
  • 3.1.16 semiconductor circuit
  • 3.1.17 electronic switch
  • 3.1.18 duty
  • 3.1.19 duty-type
  • 3.1.20 protective impedance
  • 3.1.21 exposed conductive parts
  • 3.2 Terms and definitions relating to voltage and current
  • 3.2.1 rated voltage
  • 3.2.2 safety extra-low voltage
  • 3.2.3 rated current
  • 3.2.4 rated load
  • 3.2.5 over-current
  • 3.2.6 overload
  • 3.2.6 working voltage
  • 3.2.7 overvoltage
  • 3.2.8 overvoltage category
  • 3.2.9 impulse withstand voltage
  • 3.2.10 minimum load
  • 3.2.11 thermal current
  • 3.3 Terms and definitions relating to the different types of switches
  • 3.3.1 incorporated switch
  • 3.3.2 integrated switch
  • 3.3.3 rotary switch
  • 3.3.4 lever switch
  • 3.3.5 rocker switch
  • 3.3.6 push-button switch
  • 3.3.7 cord-operated switch
  • 3.3.8 push-pull switch
  • 3.3.9 biased switch
  • 3.4 Terms and definitions relating to the operation of the switch
  • 3.4.1 actuation
  • 3.4.2 indirect actuation
  • 3.4.3 actuating member
  • 3.4.4 actuating means
  • 3.4.5 disconnection
  • 3.4.6 micro-disconnection
  • 3.4.7 electronic-disconnection
  • 3.4.8 full-disconnection
  • 3.4.9 all-pole disconnection single-phase
  • 3.4.10 operating cycle
  • 3.4.11 electronic actuating member
  • 3.4.12 electronic actuating means
  • 3.4.13 abnormal conditions
  • 3.4.14 sensing unit
  • 3.4.15 fault conditions
  • 3.5 Terms and definitions relating to connections to the switch
  • 3.5.1 external conductor
  • 3.5.2 integrated conductor
  • 3.6 Terms and definitions relating to terminals and terminations
  • 3.6.1 terminal
  • 3.6.2 screw type terminal
  • 3.6.3 screwless terminal
  • 3.6.4 termination
  • 3.6.5 flat quick-connect termination
  • 3.6.6 tab
  • 3.6.7 female connector
  • 3.6.8 solder terminal
  • 3.6.9 insulation-piercing terminal
  • 3.7 Terms and definitions relating to insulation
  • 3.7.1 basic insulation
  • 3.7.2 supplementary insulation

1 Scope

This part of IEC 61058 applies to switches or switching devices for appliances. The switches are intended to control electrical appliances and other equipment for household or similar purposes with a rated voltage not exceeding 480 600 V and a rated current not exceeding 63 A.

In the IEC 61058 series the terms "switching devices" and "switches" are used interchangeably. Switches for appliances are intended to be operated by - a person via an actuating member, - indirect actuation, - an actuating sensing unit.

Transmission of a signal between the actuating member or sensing unit and the switch may can be connected by optical, acoustic, thermal, electrical or other relevant connection and may can include remote controlled units.

This document applies to switches for appliances provided with additional control functions governed provided by the switch provided with using electronic circuits and devices that are necessary for the intended and/or correct operation of the switch. This document applies to circuitry when evaluated with a switch and necessary for the switching function.

This part document applies in general to switches for appliances in conjunction with the following parts:

  • Part 1-1: Requirements for mechanical switches, and/or
  • Part 1-2: Requirements for electronic switches.

This document does not apply to devices switches covered by:

  • IEC 60669 (all parts), Switches for household and similar fixed-electrical installations, and
  • IEC 60730 (all parts), Automatic electrical controls.

This part of IEC 61058 does not contain requirements for safety isolating switches (IEC 60050- 811:1991, 811-29-17).

NOTE 1 For switches used in tropical climates, additional requirements may be necessary. NOTE 2 1 Attention is drawn to the fact that the end product standards for appliances may can contain additional or alternative requirements for switches (see Annex O).

NOTE 3 2 Throughout this document, the word "appliance" means "appliance or equipment".

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.

IEC 60038, IEC standard voltages IEC 60060-1, High-voltage techniques – Part 1: General definitions and test requirements

IEC 60065:2014, Audio, video and similar electronic apparatus – Safety requirements IEC 60068-2-75, Environmental testing – Part 2-75: Tests – Test Eh: Hammer tests IEC 60112:2003, Method for the determination of the proof and the comparative tracking indices of solid insulating materials Amendment 1:2009 IEC 60127 (all parts), Miniature fuses IEC 60127-2, Miniature fuses – Part 2: Cartridge fuse-links IEC 60269-3, Low-voltage fuses - Part 3: Supplementary requirements for fuses for use by unskilled persons (fuses mainly for household or similar applications) - Examples of standardized systems of fuses A to F IEC 60384-14, Fixed capacitors for use in electronic equipment - Part 14: Sectional specification - Fixed capacitors for electromagnetic interference suppression and connection to the supply mains IEC 60417, Graphical symbols for use on equipment (available at: http://www.graphicalsymbols.info/equipment) IEC 60529:1989, Degree of protection provided by enclosures (IP code) IEC 60529:1989/AMD1:1999 IEC 60529:1989/AMD2:2013 IEC 60617, Graphical symbols for diagrams IEC 60664-3:20032016, Insulation coordination for equipment within low-voltage systems - Part 3: Use of coating, potting or moulding for protection against pollution IEC 60691, Thermal-links - Requirements and application guide IEC 60695-2-11, Fire hazard testing - Part 2-11: Glowing/hot-wire based test methods - Glow-wire flammability test method for end-products IEC 60695-10-2, Fire hazard testing - Part 10-2: Abnormal heat - Ball pressure test method IEC 60695-11-10, Fire hazard testing - Part 11-10: Test flames - 50 W horizontal and vertical flame test methods IEC 60695-11-20, Fire hazard testing - Part 11-20: Test flames - 500 W flame test method IEC 60730 (all parts), Automatic electrical controls IEC 60730-1:20132022, Automatic electrical controls - Part 1: General requirements IEC 60730-2-9:2015, Automatic electrical controls - Part 2-9: Particular requirements for temperature sensing controls IEC 60730-2-9:2015/AMD1:2018 IEC 60730-2-9:2015/AMD2:2020 IEC 60738-1, Thermistors - Directly heated positive temperature coefficient - Part 1: Generic specification

IEC 61000-3-2, Electromagnetic compatibility (EMC) - Part 3.2: Limits - Limits for harmonic current emissions (equipment input current ≤ 16 A per phase) IEC 61000-3-3, Electromagnetic compatibility (EMC) - Part 3-3: Limits - Limitation of voltage changes, voltage fluctuations and flicker in public low-voltage supply systems, for equipment with rated current ≤ 16 A per phase and not subject to conditional connection IEC TS 61000-3-5, Electromagnetic compatibility (EMC) - Part 3-5: Limits - Limitation of voltage fluctuations and flicker in low-voltage power supply systems for equipment with rated current greater than 75 A IEC 61000-4-2, Electromagnetic compatibility (EMC) - Part 4-2: Testing and measurement techniques - Electrostatic discharge immunity test IEC 61000-4-3, Electromagnetic compatibility (EMC) - Part 4-3: Testing and measurement techniques - Radiated, radio-frequency, electromagnetic field immunity test IEC 61000-4-4, Electromagnetic compatibility (EMC) - Part 4-4: Testing and measurement techniques - Electrical fast transient/burst immunity test IEC 61000-4-5, Electromagnetic compatibility (EMC) - Part 4-5: Testing and measurement techniques - Surge immunity test IEC 61000-4-8, Electromagnetic compatibility (EMC) - Part 4-8: Testing and measurement techniques - Power frequency magnetic field immunity test IEC 61000-4-11, Electromagnetic compatibility (EMC) - Part 4-11: Testing and measurement techniques - Voltage dips, short interruptions and voltage variations immunity tests for equipment with input current up to 16 A per phase IEC 61032:1997, Protection of persons and equipment by enclosures - Probes for verification IEC 61058-1-1:2016, Switches for appliances - Part 1-1: Requirements for mechanical switches IEC 61058-1-2:2016, Switches for appliances - Part 1-2: Requirements for electronic switches IEC 61210:2010, Connecting devices - Flat quick-connect terminations for electrical copper conductors - Safety requirements IEC 62368-1:2023, Audio/video, information and communication technology equipment - Part 1:

Safety requirements CISPR 14-1, Electromagnetic compatibility - Requirements for household appliances, electric tools and similar apparatus - Part 1: Emission CISPR 15:20132018, Limits and methods of measurement of radio disturbance characteristics of electrical lighting and similar equipment CISPR 15:2018/AMD1:2024

3 Terms and definitions

For the purposes of this document, the following terms and definitions apply. ISO and IEC maintain terminology databases for use in standardization at the following addresses:

  • IEC Electropedia: available at https://www.electropedia.org/
  • ISO Online browsing platform: available at https://www.iso.org/obp

3.1 General terms and definitions

3.1.1 mechanical switching device

switching device designed to close and open one or more electric circuits by means of separable contacts Note 1 to entry: In the IEC 61058 series the terms “switching devices” and “switches” are used interchangeably. Any mechanical switching device may be designated according to the medium in which its contacts open and close, e.g. air, SF6 ("sulphur hexafluoride"), oil.

[SOURCE: IEC 60050-441:1984, 441-14-02]

3.1.2 conductive part

part which is capable of conducting current although it may not necessarily be used for carrying service current [SOURCE: IEC 60050-441:1984, 441-11-09]

3.1.3 live part

conductor or conductive part intended to be energized under normal operation operating conditions, including the neutral conductor and mid-point conductor, but by convention not excluding the PEN conductor, PEM conductor and PEL conductor Note 1 to entry: For appliance switches, “live part” implies a risk of electric shock. Note 2 to entry: Unless otherwise specified, parts connected to a SELV supply or equal to or less than 24 V are not considered to be live parts.

[SOURCE: IEC 60050-195:2021, 195-02-19, modified – The domain <in electrical installations and equipment> has been removed.]

3.1.4 pole of a switch switching device

portion of a switching device associated exclusively with one electrically separated conducting path of its main circuit and excluding those portions which provide a means for mounting and operating all poles together Note 1 to entry: A switch switching device is called "single pole" if it has only one pole. If it has more than one pole, it may be called "multipole" (two-pole, three-pole, etc.) provided that the poles are coupled in such a manner as to operate together.

[SOURCE: IEC 60050-441:1984, 441-15-01, modified — Pole of a switching device replaced by pole of a switch]

3.1.5 detachable part

part which is removable without the use of a tool when the switch is mounted as in normal use

3.1.6 tool

screwdriver, coin, or any other object which may be used to operate a nut, a screw or a similar part

3.1.7 normal use

use of the switch for the purpose for which it was made and declared

3.1.8 unique type reference

UT identification marking on a switch such that by quoting it in full to the switch manufacturer a unique switch model can be identified Note 1 to entry: This note applies to the French language only.

3.1.9 common type reference

CT identification marking on a switch which does not require any further specific information additional to that provided by the marking requirements of this document for selection, installation and use in accordance with this document Note 1 to entry: This note applies to the French language only.

3.1.10 cover

cover plate protective cover cover made of insulating material, used to cover live parts in order to avoid accidental electric contact and which is accessible when the switch is mounted as in normal use but which can be removed with the aid of a tool

3.1.11 signal indicator

device associated with a switch to indicate the circuit state visually Note 1 to entry: The device may or may not be controlled by the switch.

3.1.12 unprepared conductor

conductor which has been cut and the insulation of which has been removed for insertion into a terminal Note 1 to entry: A conductor the shape of which is arranged for introduction into a terminal or the strands of which are twisted to consolidate the end is considered as an unprepared conductor. [SOURCE: IEC 60050-442:1998, 442-01-26]

3.1.13 prepared conductor

conductor the end of which is fitted with an attachment such as eyelet, sleeve or cable lug [SOURCE: IEC 60050-442:1998, 442-01-27]

3.1.14 polarity reversal

change of the polarity on the terminals connected to the load by a switching action

3.1.15 semiconductor device

SD device the essential electric characteristics of which are due to the flow of charge carriers within one or more semiconductor materials Note 1 to entry: Previous editions of IEC 61058-1 refer to a semiconductor device as a “semiconductor switching device or solid state device (SD)”.

[SOURCE: IEC 60050-521:2002, 521-04-01]

3.1.16 semiconductor circuit

circuit containing multiple components, where at least one is a semiconductor device

3.1.17 electronic switch

switch for appliances provided with a semiconductor device or a semiconductor circuit in its intended load path Note 1 to entry: The electronic switch may can be provided with series and/or parallel mechanical contacts. See examples in Table 15 in IEC 61058-1-2:2016.

3.1.18 duty

statement of the load to which the switch is subjected, including, if applicable, making, controlling and breaking and including their durations and sequence in time

3.1.19 duty-type

continuous, short-time or periodic duty comprising one or more loads remaining constant for the duration specified, or a non-periodic duty in which generally the load varies within the permissible operating range [SOURCE: IEC 60050-411:1996, 411-51-13, modified - "and speed" is deleted.]

3.1.20 protective impedance

component or assembly of components whose impedance and construction are intended to limit steady-state touch current and electric charge to non-hazardous levels [SOURCE: IEC 60050-195:2021, 195-06-34, modified - "device" is deleted.]

3.1.21 exposed conductive parts

conductive part of electrical equipment, which can be touched and which is not normally live, but which can become live when basic insulation fails Note 1 to entry: A conductive part of electrical equipment which can only become live through contact with an exposed-conductive-part which has become live is not considered to be an exposed-conductive-part itself. [SOURCE: IEC 60050-442:1998, 442-01-21]

3.2 Terms and definitions relating to voltage and current

3.2.1 rated voltage

voltage assigned by the manufacturer for a specified operating condition Note 1 to entry: It is measured in r.m.s. unless specifically indicated otherwise. Note 2 1 to entry: This value is the maximum value and covers all lower values. [SOURCE: IEC 60050-442:1996, 442-01-03, modified - "accessory" is deleted]

3.2.2 safety extra-low voltage

SELV voltage which does not exceed 50 V AC RMS or 120 V DC between conductors or between any conductor and earth in a circuit which is insulated from the supply mains Note 1 to entry: SELV is an unearthed extra low voltage (see IEC 61140). Note 2 to entry: Different values for the SELV voltage limit may apply in the end equipment standard.

3.2.3 rated current

current assigned by the manufacturer for a specified operating condition Note 1 to entry: It is measured in r.m.s. unless specifically indicated otherwise. Note 2 1 to entry: This value is the maximum value and covers all lower values. [SOURCE: IEC 60050-442:1998, 442-01-02, modified - "for accessory" is deleted.]

3.2.4 rated load

type of load assigned by the manufacturer, according to classifications

3.2.5 over-current

current exceeding the rated current [SOURCE: IEC 60050-441:1984/AMD1:2000, 441-11-06]

3.2.6 overload

operating conditions in an electrically undamaged circuit, which cause an over-current [SOURCE: IEC60050-441:1984, 441-11-08]

3.2.6 working voltage

highest RMS value of the AC or DC voltage across any particular insulation which can occur when the switch is supplied at rated voltage Note 1 to entry: Transients are disregarded.

Note 2 to entry: Both open-circuit conditions and normal operating conditions are taken into account. [SOURCE: IEC60050-851:2008, 851-12-31]

3.2.7 overvoltage

voltage having a peak value exceeding the corresponding peak value of maximum steady-state voltage at normal operating conditions

3.2.8 overvoltage category

numeral defining a transient overvoltage condition Note 1 to entry: See Annex E.

[SOURCE: IEC60050-581:2008, 581-21-02]

3.2.9 impulse withstand voltage

highest peak value of impulse voltage of prescribed form and polarity which does not cause breakdown of insulation under specified conditions [SOURCE: IEC60050-442:2014, 442-09-18]

3.2.10 minimum load

load at which when declared, the electronic switch still operates correctly

3.2.11 thermal current

continuous resistive current which, under the test conditions declared by the manufacturer (which may also include the ambient temperature), generates, without forced cooling, the same heating as when the electronic switch is operating under specified ambient conditions at rated load in the appliance with forced cooling present, if any Note 1 to entry: The concept "thermal current" allows simplified testing of electronic switches, which in normal application have complex cooling conditions. The thermal current will always be determined by tests of the switch positioned on a table or in a simple test rig and comparative tests in the appliance in question. Consequently, the thermal current will normally be lower than the rated current. This necessitates additional tests of the terminals, contacts, etc., in order to verify that they will be able to carry the rated current, when the electronic switch is mounted in the appliance. These additional tests are specified in Clauses 16 and Clause 17 of IEC 61058-1-2:2016.

3.3 Terms and definitions relating to the different types of switches

3.3.1 incorporated switch

switch intended for incorporation in or on an appliance, which however can be tested separately [SOURCE: IEC 60050-442:1998, 442-04-01]

3.3.2 integrated switch

switch, the function of which is depending on its correct mounting and fixing in an appliance, and which can be tested only in combination with the relevant parts of that appliance [SOURCE: IEC 60050-442:1998, 442-04-02]

3.3.3 rotary switch

switch where the actuating member is a shaft or a spindle which has to be rotated to one or more indexed positions in order to achieve a change in contact state Note 1 to entry: The rotation of the actuating member may be unlimited or restricted in either direction. [SOURCE: IEC 60050-442:1998, 442-04-04]

3.3.4 lever switch

switch where the actuating member is a lever which has to be moved (tilted) to one or more indexed positions in order to achieve a change in contact state [SOURCE: IEC 60050-442:1998, 442-04-05]

3.3.5 rocker switch

switch where the actuating member is a low-profile lever (rocker) which has to be tilted to one or more indexed positions in order to achieve a change in contact state [SOURCE: IEC 60050-442:1998, 442-04-06]

3.3.6 push-button switch

switch where the actuating member is a button which has to be pushed in order to achieve a change in contact state Note 1 to entry: The switch may can be provided with one or more actuating members. [SOURCE: IEC 60050-442:1998, 442-04-07]

3.3.7 cord-operated switch

switch where the actuating member is a pull-cord which has to be pulled in order to achieve a change in contact state [SOURCE: IEC 60050-442:1998, 442-04-08, modified - "operating means" changed to "actuating member".]

3.3.8 push-pull switch

switch where the actuating member is a rod which has to be pulled or pushed to one or more indexed positions in order to achieve a change in contact state [SOURCE: IEC 60050-442:1998, 442-04-09]

3.3.9 biased switch

switch where the contacts and actuating member return to a predetermined position when the actuating member is released from the actuated position following actuation [SOURCE: IEC 60050-442:1998, 442-04-10]

3.4 Terms and definitions relating to the operation of the switch

3.4.1 actuation

movement of the actuating member of the switch by hand, by foot, or by any other human activity

3.4.2 indirect actuation

movement of the actuating member of the switch indirectly by a part of an appliance into which the switch is incorporated or integrated, for example the door of an appliance Note 1 to entry: For example, a switch can be incorporated or integrated in the door of an appliance. [SOURCE: IEC 60050-442:1998, 442-04-13]

3.4.3 actuating member

part which is pulled, pushed, turned or otherwise influenced moved to cause an operation of the switch [SOURCE: IEC 60050-442:1998, 442-04-14]

3.4.4 actuating means

any part which may can be interposed between the actuating member and the contact mechanism in order to achieve contact operation [SOURCE: IEC 60050-442:1998, 442-04-15]

...

Contents

  • 1 Domaine d'application
  • 2 Références normatives
  • 3 Termes et définitions
  • 3.1 Termes et définitions généraux
  • 3.1.1 appareil mécanique de connexion
  • 3.1.2 partie conductrice
  • 3.1.3 partie active
  • 3.1.4 pôle d'un appareil de connexion
  • 3.1.5 partie amovible
  • 3.1.6 outil
  • 3.1.7 usage normal
  • 3.1.8 référence unique de type
  • 3.1.9 référence commune de type
  • 3.1.10 capot
  • 3.1.11 indicateur de signalisation
  • 3.1.12 conducteur non préparé
  • 3.1.13 conducteur préparé
  • 3.1.14 inversion de polarité
  • 3.1.15 dispositif à semiconducteurs
  • 3.1.16 circuit à semiconducteur
  • 3.1.17 interrupteur électronique
  • 3.1.18 service
  • 3.1.19 service type
  • 3.1.20 impédance de protection
  • 3.1.21 masse
  • 3.2 Termes et définitions relatifs à la tension et au courant
  • 3.2.1 tension assignée
  • 3.2.2 très basse tension de sécurité
  • 3.2.3 courant assigné
  • 3.2.4 charge assignée
  • 3.2.5 surintensité
  • 3.2.6 tension locale
  • 3.2.7 surtension
  • 3.2.8 catégorie de surtension
  • 3.2.9 tension de tenue aux chocs
  • 3.2.10 charge minimale
  • 3.2.11 courant thermique
  • 3.3 Termes et définitions relatifs aux différents types d'interrupteurs
  • 3.3.1 interrupteur incorporé
  • 3.3.2 interrupteur intégré
  • 3.3.3 interrupteur rotatif
  • 3.3.4 interrupteur à levier
  • 3.3.5 interrupteur à touche basculante
  • 3.3.6 interrupteur à bouton poussoir
  • 3.3.7 interrupteur à tirage
  • 3.3.8 interrupteur poussez-tirez
  • 3.3.9 interrupteur prépositionné
  • 3.4 Termes et définitions relatifs au fonctionnement de l'interrupteur
  • 3.4.1 manœuvre
  • 3.4.2 manœuvre indirecte
  • 3.4.3 organe de manœuvre
  • 3.4.4 liaison de manœuvre
  • 3.4.5 coupure
  • 3.4.6 microcoupure
  • 3.4.7 coupure électronique
  • 3.4.8 coupure totale
  • 3.4.9 coupure omnipolaire monophasée
  • 3.4.10 cycle de manœuvres
  • 3.4.11 organe de manœuvre électronique
  • 3.4.12 liaison de manœuvre électronique
  • 3.4.13 conditions anormales
  • 3.4.14 unité sensible
  • 3.4.15 conditions de défaut
  • 3.5 Termes et définitions relatifs au raccordement de l'interrupteur
  • 3.5.1 conducteur externe
  • 3.5.2 conducteur intégré
  • 3.6 Termes et définitions relatifs aux bornes et aux terminaisons
  • 3.6.1 borne
  • 3.6.2 borne à vis
  • 3.6.3 borne sans vis
  • 3.6.4 terminaison
  • 3.6.5 bornes plates à connexion rapide
  • 3.6.6 languette
  • 3.6.7 clip
  • 3.6.8 borne à souder
  • 3.6.9 borne à perçage d'isolant
  • 3.7 Termes et définitions relatifs à l'isolation
  • 3.7.1 isolation principale
  • 3.7.2 isolation supplémentaire
  • 3.7.3 double isolation

1 Domaine d'application

La présente partie de l'IEC 61058 s'applique d'une manière générale aux interrupteurs ou appareils de connexion pour appareils. Les interrupteurs permettent de commander des appareils électriques et autres matériels pour usage domestique et analogue dont la tension assignée ne dépasse pas 600 V et le courant assigné ne dépasse pas 63 A. Dans la série IEC 61058, les termes "appareil de connexion" et "interrupteur" sont employés indifféremment.

Les interrupteurs pour appareils sont prévus pour être manœuvrés par:

  • une personne par l'intermédiaire d'un organe de manœuvre,
  • une manœuvre indirecte,
  • une unité sensible de manœuvre.

La transmission d'un signal entre l'organe de manœuvre ou l'unité sensible et l'interrupteur peut être associée à une liaison optique, acoustique, thermique, électrique ou toute autre liaison appropriée et peut comporter des unités télécommandées.

Le présent document s'applique aux interrupteurs pour appareils dont les fonctions de commande supplémentaires sont assurées par l'interrupteur au moyen de circuits électroniques.

Le présent document s'applique aux circuits lorsqu'ils sont évalués avec l'interrupteur, car nécessaires à sa fonction de coupure.

Le présent document s'applique d'une manière générale aux interrupteurs pour appareils conjointement avec les parties suivantes:

  • Partie 1-1: Exigences relatives aux interrupteurs mécaniques, et/ou
  • Partie 1-2: Exigences relatives aux interrupteurs électroniques. Le présent document ne s'applique pas aux interrupteurs couverts par:

- l'IEC 60669 (toutes les parties), Interrupteurs pour installations électriques fixes domestiques et analogues, et - l'IEC 60730 (toutes les parties), Dispositifs de commande électrique automatiques. NOTE 1 L'attention est attirée sur le fait que les normes des produits finaux pour appareils peuvent contenir des exigences supplémentaires ou différentes pour les interrupteurs (voir l'Annexe O). NOTE 2 Partout où il est utilisé dans le présent document, le terme "appareil" signifie "appareil ou équipement".

2 Références normatives

Les documents suivants sont cités dans le texte de sorte qu'ils constituent, pour tout ou partie de leur contenu, des exigences du présent document. Pour les références datées, seule l'édition citée s'applique. Pour les références non datées, la dernière édition du document de référence s'applique (y compris les éventuels amendements).

IEC 60127 (toutes les parties), Coupe-circuit miniatures IEC 60269-3, Fusibles basse tension - Partie 3: Exigences supplémentaires pour les fusibles destinés à être utilisés par des personnes non qualifiées (fusibles pour usages essentiellement domestiques et analogues) - Exemples de systèmes de fusibles normalisés A à F

IEC 60384-14, Condensateurs fixes utilisés dans les équipements électroniques - Partie 14: Spécification intermédiaire - Condensateurs fixes pour la suppression des interférences électromagnétiques et la connexion au réseau d'alimentation IEC 60417, Symboles graphiques utilisables sur le matériel (disponible sous: http://www.graphical-symbols.info/equipment) IEC 60529:1989, Degrés de protection procurés par les enveloppes (Code IP) IEC 60529:1989/AMD1:1999 IEC 60529:1989/AMD2:2013 IEC 60617, Symboles graphiques pour schémas IEC 60664-3:2016, Coordination de l'isolement des matériels dans les systèmes (réseaux) à basse tension - Partie 3: Utilisation de revêtement, d'empotage ou de moulage pour la protection contre la pollution IEC 60691, Protecteurs thermiques - Exigences et guide d'application IEC 60695-2-11, Essais relatifs aux risques du feu - Partie 2-11: Essais au fil incandescent/chauffant - Méthode d'essai d'inflammabilité pour produits finis IEC 60695-10-2, Essais relatifs aux risques du feu - Partie 10-2: Chaleurs anormales - Essai à la bille IEC 60695-11-10, Essais relatifs aux risques du feu - Partie 11-10: Flammes d'essai - Méthodes d'essai horizontale et verticale à la flamme de 50 W IEC 60695-11-20, Essais relatifs aux risques du feu - Partie 11-20: Flammes d'essai - Méthode d'essai à la flamme de 500 W IEC 60730 (toutes les parties), Dispositifs de commande électrique automatiques IEC 60730-1:2022, Dispositifs de commande électrique automatiques - Partie 1: Exigences générales IEC 60730-2-9:2015, Dispositifs de commande électrique automatiques - Partie 2-9: Exigences particulières pour les dispositifs de commande thermosensibles IEC 60730-2-9:2015/AMD1:2018 IEC 60730-2-9:2015/AMD2:2020 IEC 60738-1, Thermistances - Coefficient de température positif à chauffage direct - Partie 1: Spécification générique IEC 61000-3-2, Compatibilité électromagnétique (CEM) - Partie 3-2: Limites - Limites pour les émissions de courant harmonique (courant appelé par les appareils ≤ 16 A par phase) IEC 61000-3-3, Compatibilité électromagnétique (CEM) - Partie 3-3: Limites - Limitation des variations de tension, des fluctuations de tension et du papillotement dans les réseaux publics d'alimentation basse tension, pour les matériels ayant un courant assigné ≤ 16 A par phase et non soumis à un raccordement conditionnel IEC TS 61000-3-5, Compatibilité électromagnétique (CEM) - Partie 3-5: Limites - Limitation des fluctuations de tension et du flicker dans les réseaux basse tension pour les équipements ayant un courant appelé supérieur à 75 A

IEC 61000-4-2, Compatibilité électromagnétique (CEM) - Partie 4-2: Techniques d'essai et de mesure - Essai d'immunité aux décharges électrostatiques IEC 61000-4-3, Compatibilité électromagnétique (CEM) - Partie 4-3: Techniques d'essai et de mesure - Essai d'immunité aux champs électromagnétiques rayonnés aux fréquences radioélectriques IEC 61000-4-4, Compatibilité électromagnétique (CEM) - Partie 4-4: Techniques d'essai et de mesure - Essais d'immunité aux transitoires électriques rapides en salves IEC 61000-4-5, Compatibilité électromagnétique (CEM) - Partie 4-5: Techniques d'essai et de mesure - Essai d'immunité aux ondes de choc IEC 61000-4-8, Compatibilité électromagnétique (CEM) - Partie 4-8: Techniques d'essai et de mesure - Essai d'immunité au champ magnétique à la fréquence du réseau IEC 61000-4-11, Compatibilité électromagnétique (CEM) - Partie 4-11: Techniques d'essai et de mesure - Essais d'immunité aux creux de tension, coupures brèves et variations de tension pour les appareils à courant d'entrée inférieur ou égal à 16 A par phase IEC 61032:1997, Protection des personnes et des matériels par les enveloppes - Calibres d'essai pour la vérification IEC 61058-1-1:2016, Interrupteurs pour appareils - Partie 1-1: Exigences relatives aux interrupteurs mécaniques IEC 61058-1-2:2016, Interrupteurs pour appareils - Partie 1-2: Exigences relatives aux interrupteurs électriques IEC 61210, Dispositifs de connexion - Bornes plates à connexion rapide pour conducteurs électriques en cuivre - Exigences de sécurité IEC 62368-1:2023, Équipements des technologies de l'audio/vidéo, de l'information et de la communication - Partie 1: Exigences de sécurité CISPR 14-1, Compatibilité électromagnétique - Exigences relatives aux appareils électrodomestiques, aux outils électriques et aux appareils analogues - Partie 1: Émission CISPR 15:2018, Limites et méthodes de mesure des perturbations radioélectriques produites par les appareils électriques d'éclairage et les appareils analogues CISPR 15:2018/AMD1:2024

3 Termes et définitions

Pour les besoins du présent document, les termes et définitions suivants s'appliquent. L'ISO et l'IEC tiennent à jour des bases de données terminologiques destinées à être utilisées en normalisation, consultables aux adresses suivantes:

  • IEC Electropedia: disponible à l'adresse https://www.electropedia.org/
  • ISO Online browsing platform: disponible à l'adresse https://www.iso.org/obp

3.1 Termes et définitions généraux

3.1.1 appareil mécanique de connexion

appareil de connexion destiné à fermer et à ouvrir un ou plusieurs circuits électriques au moyen de contacts séparables Note 1 à l'article: Tout appareil mécanique de connexion peut être désigné en fonction du milieu dans lequel ses contacts s'ouvrent et se ferment, par exemple: air, SF6 ("hexafluorure de soufre"), huile. [SOURCE: IEC 60050-441:1984, 441-14-02]

3.1.2 partie conductrice

partie capable de conduire du courant, bien qu'elle ne soit pas nécessairement utilisée pour conduire du courant en service normal [SOURCE: IEC 60050-441:1984, 441-11-09]

3.1.3 partie active

partie sous tension partie conductrice destinée à être sous tension dans des conditions normales de fonctionnement, y compris le conducteur de neutre et le conducteur de point milieu, à l'exception toutefois du conducteur PEN, du conducteur PEM et du conducteur PEL [SOURCE: IEC 60050-195:2021, 195-02-19, modifié – Le domaine <installations et matériels électriques> a été supprimé.]

3.1.4 pôle d'un appareil de connexion

élément constituant d'un appareil de connexion associée exclusivement à un chemin conducteur électriquement séparé appartenant à son circuit principal, cet élément ne comprenant pas les éléments constituants assurant la fixation et le fonctionnement d'ensemble de tous les pôles Note 1 à l'article: Un appareil de connexion est appelé "unipolaire" s'il n'a qu'un pôle. S'il a plus d'un pôle, il peut être appelé "multipolaire" (bipolaire, tripolaire, etc.) à condition que les pôles soient liés entre eux de façon qu'ils fonctionnent ensemble.

[SOURCE: IEC 60050-441:1984, 441-15-01]

3.1.5 partie amovible

partie qui peut être enlevée sans l'aide d'un outil, l'interrupteur étant monté comme en usage normal

3.1.6 outil

tournevis ou autre objet qui peut être utilisé pour manœuvrer un écrou, une vis ou un élément analogue

3.1.7 usage normal

usage de l'interrupteur dans le but pour lequel il a été fabriqué et déclaré

3.1.8 référence unique de type

UT identification de marquage sur un interrupteur qui, par son libellé complet, permet au fabricant d'identifier un modèle d'interrupteur unique Note 1 à l'article: L'abréviation "UT" est dérivée du terme anglais développé correspondant "unique type reference".

3.1.9 référence commune de type

CT identification de marquage sur un interrupteur qui ne nécessite pas d'autres informations spécifiques que celles qui sont fournies par les exigences de marquage de la présente partie de l'IEC 61058 pour le choix, l'installation et l'utilisation conformément à la présente partie de l'IEC 61058

3.1.10 capot

plaque de recouvrement enveloppe en matériaux isolants qui recouvre des parties actives afin d'éviter un contact électrique accidentel et qui est accessible lorsque l'interrupteur est monté comme en usage normal

3.1.11 indicateur de signalisation

dispositif associé à un interrupteur pour visualiser l'état des circuits

3.1.12 conducteur non préparé

conducteur dont l'extrémité coupée a été dénudée pour être insérée dans une borne Note 1 à l'article: Un conducteur dont la forme est arrangée pour qu'il soit introduit dans une borne ou dont les torons sont tressés pour en consolider l'extrémité est considéré comme un conducteur non préparé. [SOURCE: IEC 60050-442:1998, 442-01-26]

3.1.13 conducteur préparé

conducteur dont l'extrémité dénudée est munie d'un accessoire tel que manchon ou cosse ou raccord de câbles [SOURCE: IEC 60050-442:1998, 442-01-27]

3.1.14 inversion de polarité

changement de polarité des bornes raccordées à la charge par l'action d'un interrupteur

3.1.15 dispositif à semiconducteurs

SD dispositif dont les caractéristiques électriques essentielles sont dues au flux de porteurs de charges à l'intérieur d'un ou de plusieurs matériaux semiconducteurs Note 1 à l'article: L'abréviation "SD" est dérivée du terme anglais développé correspondant "semiconductor device".

3.1.16 circuit à semiconducteur

circuit qui comporte plusieurs composants dont au moins un est un dispositif à semiconducteurs

3.1.17 interrupteur électronique

interrupteur pour appareils qui comporte un dispositif à semiconducteurs ou un circuit à semiconducteurs dans son circuit de coupure Note 1 à l'article: L'interrupteur électronique peut comporter des contacts mécaniques en série et/ou en parallèle.

3.1.18 service

déclaration de la charge à laquelle l'interrupteur est soumis, y compris, le cas échéant, la fermeture, la commande et la coupure, ainsi que leurs durées et leur ordre de succession dans le temps

3.1.19 service type

service continu, temporaire ou périodique comprenant une ou plusieurs charges qui restent constantes pendant la durée spécifiée ou service non périodique pendant lequel généralement la charge varie dans la plage de fonctionnement admissible [SOURCE: IEC 60050-411:1996, 411-51-13, modifié – Les mots "et la vitesse" ont été supprimés.]

3.1.20 impédance de protection

composant ou ensemble de composants dont l'impédance et la conception sont telles qu'elles assurent la limitation du courant de contact en régime établi et de la charge électrique à des niveaux non dangereux [SOURCE: IEC 60050-195:2021, 195-06-34]

3.1.21 masse

partie conductrice d'un matériel électrique susceptible d'être touchée et qui n'est pas normalement sous tension, mais peut le devenir lorsque l'isolation principale est défaillante Note 1 à l'article: Une partie conductrice d'un matériel électrique qui ne peut être mise sous tension que par l'intermédiaire d'une masse qui est devenue sous tension n'est pas considérée comme une masse. [SOURCE: IEC 60050-442:1998, 442-01-21]

3.2 Termes et définitions relatifs à la tension et au courant

3.2.1 tension assignée

tension fixée par le constructeur pour le fonctionnement spécifié Note 1 à l'article: Cette valeur correspond à la valeur maximale et couvre l'ensemble des valeurs inférieures. [SOURCE: IEC 60050-442:1996, 442-01-03, modifié – Les mots "d'un appareil" ont été supprimés.]

3.2.2 très basse tension de sécurité

TBTS tension qui ne dépasse pas 50 V en valeur efficace en courant alternatif ou 120 V en courant continu entre conducteurs ou entre un conducteur et la terre dans un circuit isolé de l'alimentation principale Note 1 à l'article: La TBTS est une très basse tension non reliée à la terre (voir l'IEC 61140). Note 2 à l'article: Des valeurs différentes pour la limite de tension TBTS peuvent s'appliquer dans la norme relative au matériel final.

3.2.3 courant assigné

courant fixé par le constructeur pour le fonctionnement spécifié Note 1 à l'article: Cette valeur correspond à la valeur maximale et couvre l'ensemble des valeurs inférieures. [SOURCE: IEC 60050-442:1998, 442-01-02, modifié – Les mots "d'un appareil" ont été supprimés.]

3.2.4 charge assignée

type de charge attribuée par le fabricant, selon les classifications

3.2.5 surintensité

courant supérieur au courant assigné [SOURCE: IEC 60050-441:1984/AMD1:2000, 441-11-06]

3.2.6 tension locale

valeur efficace la plus élevée de la tension en courant alternatif ou continu qui peut apparaître à travers n'importe quelle isolation lorsqu'un interrupteur est alimenté sous la tension assignée Note 1 à l'article: Les surtensions transitoires sont négligées. Note 2 à l'article: Il est tenu compte à la fois des conditions à vide et des conditions normales de fonctionnement. [SOURCE: IEC 60050-851:2008, 851-12-31]

3.2.7 surtension

tension dont la valeur de crête dépasse la valeur de crête qui correspond à la tension maximale en régime établi dans les conditions normales de fonctionnement

3.2.8 catégorie de surtension

chiffre définissant une condition de surtension transitoire Note 1 à l'article: Voir l'Annexe E.

[SOURCE: IEC 60050-581:2008, 581-21-02]

3.2.9 tension de tenue aux chocs

valeur de crête la plus élevée d'une tension de choc, de forme et de polarité prescrites, qui ne provoque pas de claquage dans des conditions d'essai spécifiées [SOURCE: IEC 60050-442:2014, 442-09-18]

3.2.10 charge minimale

charge à laquelle, lorsqu'elle est déclarée, l'interrupteur électronique continue de fonctionner correctement

3.2.11 courant thermique

courant résistif continu qui, dans les conditions d'essai déclarées par le fabricant (qui peuvent inclure la température ambiante), génère, sans refroidissement forcé, le même échauffement que lorsque l'interrupteur électronique est en fonctionnement dans des conditions ambiantes spécifiées dans l'appareil à la charge assignée, avec un refroidissement forcé présent, s'il y a lieu Note 1 à l'article: Le concept de "courant thermique" permet un essai simplifié des interrupteurs électroniques, dont les conditions de refroidissement sont complexes dans une application normale. Le courant thermique est toujours déterminé par des essais d'un interrupteur positionné sur une table ou sur une simple plateforme d'essai, et des essais comparatifs dans l'appareil en question. Par conséquent, le courant thermique est normalement inférieur au courant assigné. Cela implique des essais supplémentaires des bornes, contacts, etc., afin de s'assurer qu'ils sont en mesure de supporter le courant assigné, lorsque l'interrupteur électronique est monté dans l'appareil. Ces essais supplémentaires sont spécifiés à l'Article 17 de l'IEC 61058-1-2:2016.

3.3 Termes et définitions relatifs aux différents types d'interrupteurs

3.3.1 interrupteur incorporé

interrupteur destiné à être incorporé dans ou monté sur un appareil d'utilisation, mais qui peut être essayé indépendamment de ce dernier [SOURCE: IEC 60050-442:1998, 442-04-01]

3.3.2 interrupteur intégré

interrupteur dont la fonction dépend de son montage et de sa fixation corrects dans un appareil d'utilisation et qui ne peut être essayé qu'avec les parties correspondantes de cet appareil [SOURCE: IEC 60050-442:1998, 442-04-02]

3.3.3 interrupteur rotatif

interrupteur dont l'organe de manœuvre est un axe ou une tige qui doit être tourné vers une ou plusieurs positions indexées afin d'obtenir un changement de l'état des contacts Note 1 à l'article: La rotation de l'organe de manœuvre peut être complète ou limitée dans l'une ou l'autre des directions.

[SOURCE: IEC 60050-442:1998, 442-04-04]

3.3.4 interrupteur à levier

interrupteur dont l'organe de manœuvre est un levier qui doit être déplacé (basculé) vers une ou plusieurs positions indexées afin d'obtenir un changement de l'état des contacts [SOURCE: IEC 60050-442:1998, 442-04-05]

3.3.5 interrupteur à touche basculante

interrupteur dont l'organe de manœuvre est un levier dont la forme est aplatie (touche basculante) qui doit être basculé vers une ou plusieurs positions indexées afin d'obtenir un changement de l'état des contacts [SOURCE: IEC 60050-442:1998, 442-04-06]

3.3.6 interrupteur à bouton poussoir

interrupteur dont l'organe de manœuvre est un bouton qui doit être poussé afin d'obtenir un changement de l'état des contacts Note 1 à l'article: L'interrupteur peut être équipé d'un ou de plusieurs organes de manœuvre. [SOURCE: IEC 60050-442:1998, 442-04-07]

3.3.7 interrupteur à tirage

interrupteur dont l'organe de manœuvre est un cordon de traction qui doit être tiré pour changer l'état des contacts [SOURCE: IEC 60050-442:1998, 442-04-08, modifié – "le dispositif de manœuvre" a été remplacé par "l'organe de manœuvre".]

3.3.8 interrupteur poussez-tirez

interrupteur dont l'organe de manœuvre est une tige qui doit être tirée ou poussée vers une ou plusieurs positions indexées afin d'obtenir un changement de l'état des contacts [SOURCE: IEC 60050-442:1998, 442-04-09]

3.3.9 interrupteur prépositionné

interrupteur dont les contacts et l'organe de manœuvre reviennent à une position prédéterminée lorsque l'organe de manœuvre est relâché à la suite d'une commande [SOURCE: IEC 60050-442:1998, 442-04-10]

...