Acoustics — Application of new measurement methods in building and room acoustics

ISO 18233:2006 gives guidelines and specifies requirements for the application of new methods for the measurement of the acoustic properties of buildings and building elements. Guidelines and requirements for selection of the excitation signal, signal processing and environmental control are given, together with requirements for linearity and time-invariance for the systems to be tested. ISO 18233:2006 is applicable to such measurements as airborne sound insulation between rooms and of façades, measurement of reverberation time and other acoustic parameters of rooms, measurement of sound absorption in a reverberation room, and measurement of vibration level differences and loss factor. ISO 18233:2006 specifies methods to be used as substitutes for measurement methods specified in standards covering classical methods, such as ISO 140 (all parts), ISO 3382 (all parts) and ISO 17497-1.

Acoustique — Application de nouvelles méthodes de mesurage dans l'acoustique des bâtiments et des salles

L'ISO 18233:2006 donne des recommandations et spécifie des exigences pour l'application de nouvelles méthodes de mesurage des propriétés acoustiques des bâtiments et des éléments de construction. Les recommandations et les exigences pour le choix du signal d'excitation, du traitement des signaux et du contrôle environnemental sont accompagnées des exigences de linéarité et d'invariance temporelle des systèmes à soumettre aux essais. L'ISO 18233:2006 s'applique à des mesurages tels que l'isolation au bruit aérien entre salles adjacentes et celle des façades, le mesurage de la durée de réverbération et autres paramètres acoustiques des salles, le mesurage de l'absorption acoustique en salle réverbérante et le mesurage des écarts de niveau de vibration et du facteur de perte. L'ISO 18233:2006 spécifie les méthodes de mesurage à utiliser en alternative à des méthodes de mesurage spécifiées dans les normes traitant des méthodes classiques, telles que l'ISO 140 (toutes les parties), l'ISO 3382 (toutes les parties) et l'ISO 17497-1.

General Information

Status
Published
Publication Date
31-May-2006
Current Stage
9093 - International Standard confirmed
Completion Date
11-Mar-2021
Ref Project

Relations

Buy Standard

Standard
ISO 18233:2006 - Acoustics -- Application of new measurement methods in building and room acoustics
English language
26 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
ISO 18233:2006 - Acoustique -- Application de nouvelles méthodes de mesurage dans l'acoustique des bâtiments et des salles
French language
27 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

INTERNATIONAL ISO
STANDARD 18233
First edition
2006-06-01


Acoustics — Application of new
measurement methods in building and
room acoustics
Acoustique — Application de nouvelles méthodes de mesurage dans
l'acoustique des bâtiments et des salles




Reference number
ISO 18233:2006(E)
©
ISO 2006

---------------------- Page: 1 ----------------------
ISO 18233:2006(E)
PDF disclaimer
This PDF file may contain embedded typefaces. In accordance with Adobe's licensing policy, this file may be printed or viewed but
shall not be edited unless the typefaces which are embedded are licensed to and installed on the computer performing the editing. In
downloading this file, parties accept therein the responsibility of not infringing Adobe's licensing policy. The ISO Central Secretariat
accepts no liability in this area.
Adobe is a trademark of Adobe Systems Incorporated.
Details of the software products used to create this PDF file can be found in the General Info relative to the file; the PDF-creation
parameters were optimized for printing. Every care has been taken to ensure that the file is suitable for use by ISO member bodies. In
the unlikely event that a problem relating to it is found, please inform the Central Secretariat at the address given below.


©  ISO 2006
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by any means,
electronic or mechanical, including photocopying and microfilm, without permission in writing from either ISO at the address below or
ISO's member body in the country of the requester.
ISO copyright office
Case postale 56 • CH-1211 Geneva 20
Tel. + 41 22 749 01 11
Fax + 41 22 749 09 47
E-mail copyright@iso.org
Web www.iso.org
Published in Switzerland

ii © ISO 2006 – All rights reserved

---------------------- Page: 2 ----------------------
ISO 18233:2006(E)
Contents Page
Foreword. iv
Introduction . v
1 Scope . 1
2 Normative references . 1
3 Terms definitions and abbreviated terms . 1
3.1 Terms and definitions. 1
3.2 Abbreviated terms . 2
4 Designations . 2
4.1 Maximum length sequence method (MLS). 2
4.2 Swept-sine method (SS). 2
5 Theory . 2
5.1 General. 2
5.2 Sound in a room. 3
5.3 Sound transmission between two rooms. 5
5.4 Using the frequency response function. 6
6 Measurement of the impulse response . 7
6.1 General. 7
6.2 Excitation signal . 7
6.3 Measurement of the response. 9
7 Measurement of the frequency response function . 14
8 Precision. 14
9 Test report . 15
Annex A (normative) Maximum length sequence method. 16
Annex B (normative) Swept-sine method. 20
Bibliography . 26

© ISO 2006 – All rights reserved iii

---------------------- Page: 3 ----------------------
ISO 18233:2006(E)
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards bodies
(ISO member bodies). The work of preparing International Standards is normally carried out through ISO
technical committees. Each member body interested in a subject for which a technical committee has been
established has the right to be represented on that committee. International organizations, governmental and
non-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely with the
International Electrotechnical Commission (IEC) on all matters of electrotechnical standardization.
International Standards are drafted in accordance with the rules given in the ISO/IEC Directives, Part 2.
The main task of technical committees is to prepare International Standards. Draft International Standards
adopted by the technical committees are circulated to the member bodies for voting. Publication as an
International Standard requires approval by at least 75 % of the member bodies casting a vote.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. ISO shall not be held responsible for identifying any or all such patent rights.
ISO 18233 was prepared by Technical Committee ISO/TC 43, Acoustics, Subcommittee SC 2, Building
acoustics.
iv © ISO 2006 – All rights reserved

---------------------- Page: 4 ----------------------
ISO 18233:2006(E)
Introduction
Stochastic signal analysis methods for the measurement of sound transmission phenomena started to be
developed around 1960, but lack of available computing power excluded the use of these methods outside the
best equipped research laboratories.
The development of digitizing circuitry, powerful personal computers and the use of digital signal processing
components in sound measuring equipment for field use, have made the application of measuring equipment
based on extended digital signal analysis readily available. Dedicated instruments, as well as specialized
software used on general computers, currently apply such methods and are already widely used.
The new methods bring a number of advantages compared to the well-established classical methods, such as
suppression of background noise and extended measurement range. However, there is also risk of unreliable
results if certain guidelines are not followed. The new methods may demonstrate larger sensitivity to time-
variations and change in the environmental conditions than the classical methods.
This International Standard is developed to give requirements and guidelines for the use of new measurement
methods in building and room acoustic measurements, but can also be used in the construction of measuring
equipment for the implementation of the methods.
As even an experienced user of equipment based on classical methods may be unaware of the difficulties and
limitations for some applications of the new methods, the user is encouraged to develop a deeper
understanding of the theoretical bases for the new methods. Instrument manufacturers are also encouraged to
give further guidelines for applications and to make it an objective to design instruments that give warnings
when results are not reliable.
This International Standard gives guidelines and requirements for the application of new methods for the
measurement of sound insulation in buildings and building elements and for the measurement of reverberation
time and related quantities. Reference is made to the standards for the classical methods regarding what to
measure, the number and the selection of measurement points, and the conditions for measurements.
© ISO 2006 – All rights reserved v

---------------------- Page: 5 ----------------------
INTERNATIONAL STANDARD ISO 18233:2006(E)

Acoustics — Application of new measurement methods in
building and room acoustics
1 Scope
This International Standard gives guidelines and specifies requirements for the application of new methods for
the measurement of the acoustic properties of buildings and building elements. Guidelines and requirements
for selection of the excitation signal, signal processing and environmental control are given, together with
requirements for linearity and time-invariance for the systems to be tested.
This International Standard is applicable to such measurements as airborne sound insulation between rooms
and of façades, measurement of reverberation time and other acoustic parameters of rooms, measurement of
sound absorption in a reverberation room, and measurement of vibration level differences and loss factor.
This International Standard specifies methods to be used as substitutes for measurement methods specified
in standards covering classical methods, such as ISO 140 (all parts), ISO 3382 (all parts) and ISO 17497-1.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
IEC 61260, Electroacoustics — Octave-band and fractional-octave-band filters
IEC 61672-1, Electroacoustics — Sound level meters — Part 1: Specifications
3 Terms definitions and abbreviated terms
3.1 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
3.1.1
classical method
conventional method of measurement where the resulting sound pressure levels or decay rates are
determined directly from the recorded responses to random noise or impulse signals
3.1.2
new method
measurement method in which various deterministic signals can be used to first obtain the impulse response
of the system under test and from which the required sound pressure levels and decay rates can be obtained
NOTE The new methods may have additional, intentional features such as giving results under situations where no
result is obtained by the classical method. The new methods may, for instance, be more immune to noise from other
sources.
© ISO 2006 – All rights reserved 1

---------------------- Page: 6 ----------------------
ISO 18233:2006(E)
3.1.3
effective signal-to-noise ratio
signal-to-noise ratio
ten times the logarithm to the base 10 of the ratio of the mean-square value of the signal part caused by the
excitation and obtained by the new method, to the mean-square value of the unwanted part of the signal
obtained by the same method and caused by sources other than the excitation
NOTE 1 The effective signal-to-noise ratio is expressed in decibels.
NOTE 2 The effective signal-to-noise ratio is used as a substitute for the normal signal-to-noise ratio when establishing
procedures for the new method based on a classical method.
3.1.4
peak-to-noise ratio
ten times the logarithm to the base 10 of the ratio of the squared peak value of the signal part caused by the
excitation and obtained by the new method, to the mean-square value of the unwanted part of the signal
obtained by the same method and caused by other sources than the excitation
NOTE The effective peak-to-noise ratio is expressed in decibels.
3.1.5
fractional-octave band
frequency range, in hertz, from lower to higher band edge frequency for a fractional-octave-band filter as
specified in IEC 61260
NOTE Both full-octave- and fractional-octave-band filters are designated fractional-octave-band filters.
3.2 Abbreviated terms
MLS Maximum length sequence method
SS Swept-sine method
4 Designations
4.1 Maximum length sequence method (MLS)
An MLS method in accordance with this International Standard shall be designated as “ISO 18233–MLS”.
4.2 Swept-sine method (SS)
An SS method in accordance with this International Standard shall be designated as “ISO 18233–SS”.
5 Theory
5.1 General
The transmission of sound within a room as well as the transmission of sound between rooms may normally
be considered as a close approximation to a linear and time-invariant system. The general theory applicable
to such systems may therefore be used to establish the relationship between excitation and response for the
sound transmission.
The impulse response is the basis of all measurements. The methods are applicable to the velocities
measured on structures as well as to sound pressures measured in rooms.
2 © ISO 2006 – All rights reserved

---------------------- Page: 7 ----------------------
ISO 18233:2006(E)
5.2 Sound in a room
The scope of Parts 3 to 5 of ISO 140 and of Parts 9 to 12 of ISO 140 is to specify methods to measure the
airborne sound insulation for building elements and the insulation between dwellings. ISO 3382 (all parts)
specifies the measurement of reverberation time. In order to measure these quantities, the sound pressure
level and the reverberation time in rooms by the application of noise excitation shall be measured.
For the measurement of reverberation time, the noise source is switched on for a time sufficient to obtain a
steady level. The source is thereafter switched off, and the decay of the sound in the room is observed. The
time for switching the noise off is set to t = 0 in this International Standard.
A recording of the sound pressure level versus time will, in general, contain information on the obtained
stationary sound pressure level in the room as well as the reverberation time. A typical level versus time
diagram is shown in Figure 1. The stationary sound pressure level before the sound source is switched off is
given by the recording for t < 0, and information about the decay will be given for t W 0. The decay may be
further processed to obtain the reverberation time.

Key
L stationary noise level before the excitation is switched off
0
L background noise level
N
t time
NOTE The excitation is switched off at time t = 0.
Figure 1 — Typical level versus time curve
The classical methods for the measurement of airborne sound in rooms, defined in the ISO 140 and ISO 3382
series, specify a stochastic signal for the excitation. Although the room in most cases may be described as a
deterministic system, statistical spread from the random excitation will lead to a certain stochastic variation in
the result, which may be characterized by a standard deviation. Therefore, averaging of more measurements
is normally needed to obtain results close to the stochastically expected values. Such averaging may for the
classical method be combined with the spatial averaging needed to obtain a mean value for the room.
The methods described in this International Standard intend to obtain measurement values in fractional-
octave bands. Requirements and guidelines are selected accordingly.
It has been shown (Reference [6]) that the expected decay in one particular observation point may be
obtained without averaging, by processing the impulse response between the excitation signal (loudspeaker)
© ISO 2006 – All rights reserved 3

---------------------- Page: 8 ----------------------
ISO 18233:2006(E)
and the observation point (microphone) directly. This holds for the decay curve and the stationary levels as
long as the system is linear and time-invariant. The theory may be extended and applied to sound in the
source room, to sound in the receiving room, and to the transmission from the source to the receiving room.
The measured response in the classical method based on noise excitation may, in theory, be described as a
convolution between the excitation signal and the impulse response of the room. However, in the classical
method with noise excitation, the response is recorded directly and information about the impulse response is
normally not known.
According to the new methods described in this International Standard, the results may be obtained from
processing of the impulse response itself.
NOTE 1 The impulse response is normally the combined impulse response of the system, consisting of amplifiers,
transducers, applied filters, and the enclosure between the transmitting and the receiving points.
Several methods may be applied to obtain the impulse response or the frequency response function, which is
linked to the impulse response by Fourier transformation. All such methods may be used if they are able to
demonstrate reliable results within normal measurement conditions.
When a room has been excited by stationary white noise for a time sufficient to obtain stationary conditions
[6]
and the noise is thereafter switched off at the time t = 0, the expected level at any time t W 0 will be :

⎡⎤
W
2
0
⎢⎥
Lt()=10 lg h (t)dt dB (1)

⎢⎥C
ref
⎣⎦t
where
W is a constant specifying the signal power per unit bandwidth of the excitation signal;
0
ht() is the impulse response;
C is an arbitrary selected reference value for the level calculation.
ref
The decay corresponds to the expected decay based on the classical method, which conventionally is
approximated by a straight line.
NOTE 2 Due to the fact that the running time, t, is the lower start point for the integration, the operation in Equation (1)
may be described as backwards integration. In an alternative form of the formula, the integral starts at +∞ and runs
backwards to the actual time. Historically, this was achieved using analog technology by playing a tape with the recorded
response in the reverse direction.
Equation (1) does not consider the extraneous noise normally accompanying a measurement.
When a fractional-octave-band filter is a part of the measured system, Equation (1) will describe the expected
decay according to the classical method for the applied filter band.
Equation (1) may be used to compute the expected level at any time after the signal source was switched off.
It may also be used to obtain the expected mean level before the excitation was switched off, L . The level
0
may be obtained from Equation (1) by setting t = 0:

⎡⎤
W
0 2
⎢⎥
Lh= 10 lg (t) dt dB (2)
0

⎢⎥C
ref
0
⎣⎦
Figure 2 illustrates how the level versus time function is obtained by the classical and the new method.
4 © ISO 2006 – All rights reserved

---------------------- Page: 9 ----------------------
ISO 18233:2006(E)

a)  Classical method b)  New method
Key
L sound level
h impulse response
t running time
NOTE In the classical method, an approximation, L (t), of the expected decay is found by averaging (ensemble) a
m
number of individual decays, L (t), L (t), … L (t), based on noise excitation. By application of the new method, the
1 2 N
expected decay, L(t), is found by processing the impulse response h(t).
Figure 2 — Illustration of the difference between classical and new method
5.3 Sound transmission between two rooms
If a noise source is placed in a source room and the sound pressure level is measured at a point S, the
expected level, L , may according to Equation (2) be obtained from the impulse response between the
1
excitation point and the point S: ht().
1

⎡⎤
W
0 2
⎢⎥
Lh= 10 lg (t)dt dB (3)
11

⎢⎥C
ref
0
⎣⎦
© ISO 2006 – All rights reserved 5

---------------------- Page: 10 ----------------------
ISO 18233:2006(E)
In a similar way, if the sound level is measured in an adjacent receiving room at a point R, the expected level,
L , may be obtained from the impulse response between the excitation point and the point R: ht() .
2 2

⎡⎤
W
2
0
⎢⎥
Lh= 10 lg (t)dt dB (4)
22

⎢⎥C
ref
⎣⎦0
The expected sound level difference, D, between the source and the receiver room may therefore be
computed as:

⎡⎤
2
⎢⎥
ht()dt
1

⎢⎥
0
⎢⎥
DL=−L= 10 lg dB (5)
12

⎢⎥
2
⎢⎥ht()dt
2

⎢⎥
0
⎣⎦
The variable describing the excitation power, W , is eliminated in the result for the level difference as the
0
arbitrary chosen reference C .
ref
NOTE The new methods specified in this International Standard can also be applied to the measurement of sound
insulation of façades. In this context one of the measurement positions will be an outdoor position.
5.4 Using the frequency response function
A sinusoidal signal has a unique position in the theory of signals and linear time-invariant systems. If the
transients formed when signals are switched on and off are disregarded, the response for such a system to a
sinusoidal excitation will always be sinusoidal with the same frequency. The amplitude (gain) and the phase
may, however, change. Information about the change of amplitude and phase between input and output as a
function of frequency is called the frequency response function of the system. The frequency response
function will, as the impulse response, give full information about the response to any input signal. The
frequency response function may be obtained from the impulse response by Fourier transformation.
Equation (2) may be transformed by the application of Parseval's theorem:
∞∞
W
2
2 0
Wh ()t dt= H(ω) dω (6)
0
∫∫

0 −∞
where
ω is the angular frequency;
H()ω is the frequency response function obtained by the Fourier transformation of the impulse
responseht( ) :

−jωt
H(ω)==F ht() ht()e dt (7)
{}

−∞
where j1=−
NOTE In Equation (6), it is assumed that h(t) = 0 for t < 0, which will be the case for a physical, causal system.
6 © ISO 2006 – All rights reserved

---------------------- Page: 11 ----------------------
ISO 18233:2006(E)
Equation (6) shows that only the modulus of the frequency response function may be used for the level
calculation. This is in contrast to the measurement of reverberation time, where both the phase and modulus
of the frequency response function are required.
By combining Equations (5) and (6), the expected sound level difference, D , between the source room and
the receiving room may be computed from the frequency responses for the rooms. The expected sound level
ω
1
difference for a fractional octave band with lower band edge frequency f = and upper band edge
1

ω
2
frequency f = will be given by:
2

ω
⎡⎤2
2
⎢⎥
H ()ωωd
1

⎢⎥
ω
1
⎢⎥
DL=−L= 10 lg dB (8)
12
⎢⎥ω
2
2
⎢⎥
H ()ωωd
2

⎢⎥
⎢⎥ω
⎣⎦1
6 Measurement of the impulse response
6.1 General
The impulse response for a room will typically be an oscillatory signal with a large number of periods. The
envelope of the signal will be irregular but typically have a fast attack-time and an exponential decay.
The impulse response may be measured as the response of the room to a very short acoustic pulse. However,
it will in most cases where sources other than a loudspeaker are used, be difficult to have sufficient control of
the spectral content and the directional characteristics of the excitation.
To obtain the required control of the excitation signal, the impulse response is in most practical cases
obtained by digital signal processing. The room is excited by a known signal for a certain time and the impulse
response is calculated from the response to the excitation. The excitation signal is distributed over a longer
period of time to increase the total radiated energy. This procedure will enhance the achievable dynamic
range and reduce the influence of extraneous noise.
Several methods for the measurement of the impulse response are described in the literature, see
References [6] to [8] and [13] to [15] in the Bibliography.
For measurements of the impulse response, movement of the source or the microphones is not acceptable as
it will violate the requirement for time-invariance. The impulse response of a room is formed by a complex
interaction of sound waves reflected between the floor, ceiling and walls of the room. Between the reflections,
the air in the room influences the transmission. Movement of the air or change in the speed of sound
(temperature) may also violate the requirement for time-invariance.
6.2 Excitation signal
6.2.1 General
In the classical methods, random noise or an impulse with a bandwidth at least equal to the bandwidth of the
measurement channel is required. The random nature of the noise will give a stochastic distribution of the
measured levels and will limit the repeatability of the measurement. The new methods apply deterministic
excitation signals, i.e. they can be accurately reproduced, and thereby enhance the repeatability of the
measurement.
© ISO 2006 – All rights reserved 7

---------------------- Page: 12 ----------------------
ISO 18233:2006(E)
6.2.2 Spectral requirements
6.2.2.1 General
The effective frequency range of the excitation signal shall at least cover the actual fractional-octave band
being measured. If a broad-band measurement covering the whole audio range is being performed, the aim is
to approximate the shape of the spectrum of the excitation signal, as captured at the receiver position, to that
of the ambient noise prevailing there. By this, a frequency-independent signal-to-noise ratio will be obtained.
The typical sources of background noise (air-conditioning, traffic, etc.) tend to have a spectral distribution that
increases with decreasing frequency. For this reason, the excitation signal should feature an emphasis at
lower frequencies when room impulse responses are to be measured.
In many of these cases, a pink excitation signal (with constant energy per fractional-octave band) is suitable to
obtain a sufficient signal-to-noise ratio.
In sound insulation measurements, however, the sound reduction index normally increases at higher
frequencies, making it necessary to increase the energy of the excitation signal in this range.
The most sophisticated emphasis scheme would involve compensating the acoustical power response of the
measurement loudspeaker and adapting to the spectral distribution of the background noise. A smoothed
version of the latter, multiplied by the inverted speaker response, confined to the intended frequency range,
can be used as a template for the generation of a suitable excitation spectrum.
6.2.2.2 Repetitive excitation
If a repetitive excitation signal is used, the spectrum of the excitation will consist of narrow spectral lines
where the distance between adjacent lines, ∆f, will be given as the inverse of the time for one repetition period
T :
REP
1
∆=f (9)
T
REP
In order to ensure that all modes of the room are excited, the repetition period shall not be shorter than the
reverberation time, T, for the room being measured. This requirement applies to the measurement of
reverberation time as well as level differences:
TTW (10)
REP
NOTE Each room mode may be approximated by a second-order band-pass function with a certain quality factor
(Q-factor). A larger Q-factor means a narrower frequency response and a longer decay after excitation has ceased. For a
second-order function with bandwidth (–3 dB), B, in hertz, the virtual reverberation time will be approximately (2,2/B). The
requirement for the repetition time ensures that at least two spectral lines of excitation fall within the bandwidth of any
room mode.
6.2.2.3 Non-repetitive excitation
A non-repetitive excitation signal may be of any suitable length. However, the excitation shall be succeeded
by a period of silence in order to allow the decaying response to be properly recorded. The decay shall be
recorded over a period equal to at least half of the reverberation time. For a sweep excitation from a low to a
high frequency as described in Annex B, the required length of the period of silence will normally be
determined by the reverberation time for the higher frequencies.
6.2.3 Level and linearity
The sound power in the excitation shall be sufficiently high to obtain an effective signal-to-noise ratio satisfying
the requirements given in the International Standard specifying the applicable classical method.
Methods involving deterministic excitation signals are generally more efficient at suppressing extraneous
noise than the classical method. Enhancement of the signal-to-noise ratio by 20 dB to 30 dB or more
compared to the classical method may be obtainable.
8 © ISO 2006 – All rights reserved

---------------------- Page: 13 ----------------------
ISO 18233:2006(E)
The use of louds
...

NORME ISO
INTERNATIONALE 18233
Première édition
2006-06-01



Acoustique — Application de nouvelles
méthodes de mesurage dans l'acoustique
des bâtiments et des salles
Acoustics — Application of new measurement methods in building and
room acoustics




Numéro de référence
ISO 18233:2006(F)
©
ISO 2006

---------------------- Page: 1 ----------------------
ISO 18233:2006(F)
PDF – Exonération de responsabilité
Le présent fichier PDF peut contenir des polices de caractères intégrées. Conformément aux conditions de licence d'Adobe, ce fichier
peut être imprimé ou visualisé, mais ne doit pas être modifié à moins que l'ordinateur employé à cet effet ne bénéficie d'une licence
autorisant l'utilisation de ces polices et que celles-ci y soient installées. Lors du téléchargement de ce fichier, les parties concernées
acceptent de fait la responsabilité de ne pas enfreindre les conditions de licence d'Adobe. Le Secrétariat central de l'ISO décline toute
responsabilité en la matière.
Adobe est une marque déposée d'Adobe Systems Incorporated.
Les détails relatifs aux produits logiciels utilisés pour la création du présent fichier PDF sont disponibles dans la rubrique General Info
du fichier; les paramètres de création PDF ont été optimisés pour l'impression. Toutes les mesures ont été prises pour garantir
l'exploitation de ce fichier par les comités membres de l'ISO. Dans le cas peu probable où surviendrait un problème d'utilisation,
veuillez en informer le Secrétariat central à l'adresse donnée ci-dessous.


©  ISO 2006
Droits de reproduction réservés. Sauf prescription différente, aucune partie de cette publication ne peut être reproduite ni utilisée sous
quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie et les microfilms, sans l'accord écrit
de l'ISO à l'adresse ci-après ou du comité membre de l'ISO dans le pays du demandeur.
ISO copyright office
Case postale 56 • CH-1211 Geneva 20
Tel. + 41 22 749 01 11
Fax. + 41 22 749 09 47
E-mail copyright@iso.org
Web www.iso.org
Publié en Suisse

ii © ISO 2006 – Tous droits réservés

---------------------- Page: 2 ----------------------
ISO 18233:2006(F)
Sommaire Page
Avant-propos. iv
Introduction . v
1 Domaine d'application. 1
2 Références normatives . 1
3 Termes, définitions et termes abrégés. 1
3.1 Termes et définitions. 1
3.2 Termes abrégés . 2
4 Désignations . 2
4.1 Méthode de la séquence de longueur maximale (MLS). 2
4.2 Méthode du balayage sinusoïdal (SS) . 2
5 Principe théorique . 3
5.1 Généralités . 3
5.2 Mesurage acoustique dans une salle . 3
5.3 Transmission du son entre deux salles . 6
5.4 Utilisation de la fonction de réponse en fréquence . 6
6 Mesurage de la réponse impulsionnelle. 7
6.1 Généralités . 7
6.2 Signal d'excitation . 8
6.3 Mesurage de la réponse. 9
7 Mesurage de la fonction de réponse en fréquence. 15
8 Fidélité . 15
9 Rapport d'essai . 16
Annexe A (normative) Méthode de la séquence de longueur maximale . 17
Annexe B (normative) Méthode du balayage sinusoïdal . 21
Bibliographie . 27

© ISO 2006 – Tous droits réservés iii

---------------------- Page: 3 ----------------------
ISO 18233:2006(F)
Avant-propos
L'ISO (Organisation internationale de normalisation) est une fédération mondiale d'organismes nationaux de
normalisation (comités membres de l'ISO). L'élaboration des Normes internationales est en général confiée
aux comités techniques de l'ISO. Chaque comité membre intéressé par une étude a le droit de faire partie du
comité technique créé à cet effet. Les organisations internationales, gouvernementales et non
gouvernementales, en liaison avec l'ISO participent également aux travaux. L'ISO collabore étroitement avec
la Commission électrotechnique internationale (CEI) en ce qui concerne la normalisation électrotechnique.
Les Normes internationales sont rédigées conformément aux règles données dans les Directives ISO/CEI,
Partie 2.
La tâche principale des comités techniques est d'élaborer les Normes internationales. Les projets de Normes
internationales adoptés par les comités techniques sont soumis aux comités membres pour vote. Leur
publication comme Normes internationales requiert l'approbation de 75 % au moins des comités membres
votants.
L'attention est appelée sur le fait que certains des éléments du présent document peuvent faire l'objet de
droits de propriété intellectuelle ou de droits analogues. L'ISO ne saurait être tenue pour responsable de ne
pas avoir identifié de tels droits de propriété et averti de leur existence.
L'ISO 18233 a été élaborée par le comité technique ISO/TC 43, Acoustique, sous-comité SC 2, Acoustique
des bâtiments.
iv © ISO 2006 – Tous droits réservés

---------------------- Page: 4 ----------------------
ISO 18233:2006(F)
Introduction
L'utilisation des méthodes d'analyse des signaux aléatoires pour le mesurage des phénomènes de
transmission des sons a commencé à se développer dans les années 60, mais le manque de puissance de
calcul disponible excluait l'emploi de ces méthodes si ce n'est dans les laboratoires de recherche très équipés.
Le développement de circuits de numérisation et de micro-ordinateurs puissants, ainsi que l'utilisation
d'organes de traitement numérique des signaux dans les instruments de mesure acoustique employés sur le
terrain, ont permis la mise en œuvre d'instruments de mesure fondés sur une analyse étendue des signaux
numériques. Les instruments dédiés, ainsi que des logiciels spécialisés exécutés sur des ordinateurs d'usage
général, appliquent actuellement ces méthodes dont l'emploi est déjà largement généralisé.
Les nouvelles méthodes présentent un certain nombre d'avantages par rapport aux méthodes classiques bien
connues, telles que la suppression du bruit de fond et l'utilisation d'une gamme de mesures étendue.
Cependant, elles comportent également un risque d'obtention de résultats peu fiables si certaines
recommandations ne sont pas suivies. Il est admis que ces nouvelles méthodes peuvent se montrer plus
sensibles aux variations temporelles et aux modifications des conditions ambiantes que les méthodes
classiques.
La présente Norme internationale est destinée à fournir des exigences et des recommandations pour
l'utilisation de nouvelles méthodes de mesurage dans l'acoustique des bâtiments et des salles, mais elle peut
également être utilisée dans la fabrication d'instruments de mesure permettant de mettre en œuvre ces
méthodes.
Sachant que même un utilisateur expérimenté d'instruments fondés sur les méthodes classiques peut ignorer
les difficultés et les limites de certaines applications de nouvelles méthodes, les utilisateurs sont encouragés à
développer une meilleure connaissance des bases théoriques des nouvelles méthodes. Les fabricants
d'instruments sont également encouragés à fournir d'autres lignes directrices pour les applications et à se
fixer pour objectif la conception d'instruments qui émettent des avertissements lorsque les résultats obtenus
ne sont pas fiables.
La présente Norme internationale donne des recommandations et des exigences pour l'application de
nouvelles méthodes de mesurage de l'isolation acoustique, de la durée de réverbération et des grandeurs
correspondantes pour les bâtiments et les éléments de construction Il est fait référence aux normes
applicables aux méthodes classiques pour ce qui concerne les valeurs à mesurer, le nombre et le choix des
points de mesurage et les conditions de mesurage.
© ISO 2006 – Tous droits réservés v

---------------------- Page: 5 ----------------------
NORME INTERNATIONALE ISO 18233:2006(F)

Acoustique — Application de nouvelles méthodes de mesurage
dans l'acoustique des bâtiments et des salles
1 Domaine d'application
La présente Norme internationale donne des recommandations et spécifie des exigences pour l'application de
nouvelles méthodes de mesurage des propriétés acoustiques des bâtiments et des éléments de construction.
Les recommandations et les exigences pour le choix du signal d'excitation, du traitement des signaux et du
contrôle environnemental sont accompagnées des exigences de linéarité et d'invariance temporelle des
systèmes à soumettre aux essais.
La présente Norme internationale s'applique à des mesurages tels que l'isolation au bruit aérien entre salles
adjacentes et celle des façades, le mesurage de la durée de réverbération et autres paramètres acoustiques
des salles, le mesurage de l'absorption acoustique en salle réverbérante et le mesurage des écarts de niveau
de vibration et du facteur de perte.
La présente Norme internationale spécifie les méthodes de mesurage à utiliser en alternative à des méthodes
de mesurage spécifiées dans les normes traitant des méthodes classiques, telles que l'ISO 140 (toutes les
parties), l'ISO 3382 (toutes les parties) et l'ISO 17497-1.
2 Références normatives
Les documents de référence suivants sont indispensables pour l'application du présent document. Pour les
références datées, seule l'édition citée s'applique. Pour les références non datées, la dernière édition du
document de référence s'applique (y compris les éventuels amendements).
CEI 61260, Électroacoustique — Filtres de bande d'octave et de bande d'une fraction d'octave
CEI 61672-1, Électroacoustique — Sonomètres — Partie 1: Spécifications
3 Termes, définitions et termes abrégés
3.1 Termes et définitions
Pour les besoins du présent document, les termes et définitions suivants s'appliquent.
3.1.1
méthode classique
méthode de mesurage conventionnelle dont les niveaux de pression acoustique ou les taux de décroissance
résultants sont directement déterminés à partir des réponses enregistrées à un bruit aléatoire ou à des
signaux impulsionnels
© ISO 2006 – Tous droits réservés 1

---------------------- Page: 6 ----------------------
ISO 18233:2006(F)
3.1.2
nouvelle méthode
méthode de mesurage dans laquelle divers signaux déterministes peuvent être utilisés pour obtenir en
premier lieu la réponse impulsionnelle du système soumis à l'essai et, à partir de là, obtenir les niveaux de
pression acoustique et les taux de décroissance requis
NOTE Les nouvelles méthodes peuvent disposer de fonctions supplémentaires délibérées, telles que la fourniture de
résultats lorsque la méthode classique ne fournit aucun résultat. Les nouvelles méthodes peuvent, par exemple, avoir une
immunité plus élevée au bruit en provenance d'autres sources.
3.1.3
rapport signal/bruit effectif
rapport signal/bruit
dix fois le logarithme de base 10 du rapport de la valeur quadratique moyenne de la partie du signal
provoquée par l'excitation, telle qu'obtenue par la nouvelle méthode, et de la valeur quadratique moyenne de
la partie indésirable du signal, obtenue par la même méthode et due à des sources autres que l'excitation
NOTE 1 Le rapport signal/bruit effectif est exprimé en décibels.
NOTE 2 Le rapport signal/bruit effectif est utilisé en remplacement du rapport signal/bruit normal lorsqu'il s'agit d'établir
des modes opératoires pour la nouvelle méthode sur la base d'une méthode classique.
3.1.4
rapport signal-crête/bruit
dix fois le logarithme de base 10 du rapport du carré de la valeur de crête de la partie du signal provoquée par
l'excitation, telle qu'obtenue par la nouvelle méthode, et de la valeur quadratique moyenne de la partie
indésirable du signal, obtenue par la même méthode et due à des sources autres que l'excitation
NOTE Le rapport signal-crête/bruit effectif est exprimé en décibels.
3.1.5
bande de fraction d'octave
gamme de fréquences, en hertz, de la fréquence la plus basse à la fréquence la plus haute d'extrémité de
bande pour un filtre de bande de fraction d'octave tel que spécifié dans la CEI 61260
NOTE Les filtres de bande de pleine octave et de bande de fraction d'octave sont tous deux couverts par la
désignation filtres de bande de fraction d'octave.
3.2 Termes abrégés
MLS Méthode de la séquence de longueur maximale (de l'anglais Maximum length sequence method)
SS Méthode du balayage sinusoïdal (de l'anglais Swept-sine method)
4 Désignations
4.1 Méthode de la séquence de longueur maximale (MLS)
Une méthode MLS conforme à la présente Norme internationale doit être désignée «ISO 18233-MLS».
4.2 Méthode du balayage sinusoïdal (SS)
Une méthode SS conforme à la présente Norme internationale doit être désignée «ISO 18233-SS».
2 © ISO 2006 – Tous droits réservés

---------------------- Page: 7 ----------------------
ISO 18233:2006(F)
5 Principe théorique
5.1 Généralités
La transmission du son dans une salle et la transmission du son entre salles peuvent normalement être
considérées comme une bonne approximation d'un système linéaire et invariant dans le temps. La théorie
générale applicable à de tels systèmes peut par conséquent être utilisée pour établir le rapport qui existe
entre excitation et réponse, en matière de transmission du son.
La réponse impulsionnelle est à la base de tous les mesurages. Les méthodes sont applicables aux vitesses
mesurées sur des structures ainsi qu'aux pressions acoustiques mesurées dans des salles.
5.2 Mesurage acoustique dans une salle
L'objet de l'ISO 140, Parties 3 à 5, et de l'ISO 140, Parties 9 à 12, est de spécifier des méthodes de mesurage
de l'isolation au bruit aérien pour des éléments de construction et de l'isolation entre logements. L'ISO 3382
(toutes les parties) spécifie le mesurage de la durée de réverbération. Pour obtenir ces grandeurs, un bruit
d'excitation doit être appliqué pour mesurer le niveau de pression acoustique et la durée de réverbération
dans les salles.
Pour mesurer la durée de réverbération, la source de bruit est activée pendant une durée suffisante pour
obtenir un niveau stable. La source est ensuite désactivée et la décroissance du son dans la salle est
observée. Le temps pour l'arrêt de la source de bruit est fixé à t = 0 dans la présente Norme internationale.
Un enregistrement du niveau de pression acoustique en fonction du temps fournira généralement des
informations sur le niveau de pression acoustique stationnaire obtenu dans la salle ainsi que la durée de
réverbération. La Figure 1 illustre un diagramme type du niveau de bruit en fonction du temps. Le niveau de
pression acoustique stationnaire avant arrêt de la source sonore est donné par l'enregistrement
correspondant à t < 0, et les informations relatives à la décroissance sont données pour t W 0.
La décroissance peut ensuite être traitée pour obtenir la durée de réverbération.

Légende
L niveau de bruit stationnaire avant arrêt/coupure du signal d'excitation
0
L niveau de bruit de fond
N
t durée
NOTE L'excitation est désactivée à l'instant t = 0.
Figure 1 — Courbe type de niveau de bruit en fonction du temps
© ISO 2006 – Tous droits réservés 3

---------------------- Page: 8 ----------------------
ISO 18233:2006(F)
Les méthodes classiques de mesurage du bruit aérien dans des salles, telles que définies dans l'ISO 140 et
l'ISO 3382, spécifient l'utilisation d'un signal d'excitation aléatoire. Bien que dans la plupart des cas la salle
puisse être décrite comme un système déterministe, la dispersion statistique de l'excitation aléatoire donnera
lieu à une certaine variation aléatoire des résultats, qui peut être caractérisée par un écart-type. En
conséquence, il est normalement nécessaire de calculer la moyenne de plusieurs mesures pour obtenir des
résultats proches des valeurs aléatoirement attendues. Pour la méthode classique, ce moyennage peut être
combiné au moyennage spatial nécessaire à l'obtention d'une valeur moyenne pour la salle.
Les méthodes décrites dans la présente Norme internationale permettent d'obtenir des valeurs de mesurage
dans des bandes de fraction d'octave. Les exigences et recommandations sont choisies en conséquence.
La Référence [6] montre que la décroissance prévue en un point d'observation particulier peut être obtenue
sans moyennage, en traitant directement la réponse impulsionnelle entre le signal d'excitation (haut-parleur)
et le point d'observation (microphone). Cela est vrai pour la courbe de décroissance et les niveaux
stationnaires tant que le système est linéaire et invariant dans le temps. La théorie peut être étendue et
appliquée au son dans la salle d'émission, au son dans la salle de réception et à la transmission de la salle
d'émission vers la salle de réception.
La réponse mesurée par la méthode classique, fondée sur un bruit d'excitation, peut théoriquement être
décrite comme une convolution entre le signal d'excitation et la réponse impulsionnelle de la salle. Cependant,
dans la méthode classique avec bruit d'excitation, la réponse est directement enregistrée et, en général, les
informations concernant la réponse impulsionnelle ne sont pas connues.
Selon les nouvelles méthodes, décrites dans la présente Norme internationale, les résultats peuvent être
obtenus par traitement de la réponse impulsionnelle proprement dite.
NOTE 1 La réponse impulsionnelle est en général la combinaison des réponses impulsionnelles du système qui est
constitué d'amplificateurs, de capteurs, des filtres utilisés ainsi que de l'enceinte entre les points d'émission et de
réception.
Plusieurs méthodes peuvent être appliquées pour obtenir la réponse impulsionnelle ou la fonction de réponse
en fréquence, qui est liée à la réponse impulsionnelle par une transformation de Fourier. Toutes ces
méthodes peuvent être utilisées si elles peuvent démontrer, dans des conditions de mesurage normales,
l'obtention de résultats fiables.
Lorsqu'une salle a été excitée par un bruit blanc stationnaire pendant une durée suffisante pour obtenir des
conditions de régime établi et que, par la suite, le bruit est désactivé au moment t = 0, le niveau attendu à tout
[6]
instant t W 0 sera :

⎡⎤
W
0 2
⎢⎥
Lt()=10lg h ()t dt dB (1)

⎢⎥C
ref
t
⎣⎦

W est une constante spécifiant la puissance du signal par unité de largeur de bande du signal
0
d'excitation;
h(t) est la réponse impulsionnelle;
C est une valeur de référence sélectionnée arbitrairement pour le calcul de niveau.
ref
La décroissance correspond à la décroissance prévue sur la base de la méthode classique, qui est par
convention représentée approximativement par une ligne droite.
NOTE 2 L'instant courant, t, étant la borne inférieure de l'intégration, l'opération dans l'Équation (1) peut être décrite
comme une intégration inverse. Dans une autre version de la formule, l'intégrale part de +∞ et remonte l'axe des temps
jusqu'à l'instant courant. Historiquement, cela était obtenu en utilisant une technique analogique de reproduction d'une
bande magnétique produisant la réponse enregistrée dans le sens inverse.
L'Équation (1) ne tient pas compte du bruit parasite qui en général accompagne tout mesurage.
4 © ISO 2006 – Tous droits réservés

---------------------- Page: 9 ----------------------
ISO 18233:2006(F)
Lorsqu'un filtre de bande de fraction d'octave fait partie du système mesuré, l'Équation (1) décrira la
décroissance prévue en fonction de la méthode classique pour la bande du filtre utilisé.
L'Équation (1) peut être utilisée pour calculer le niveau prévu à tout moment après arrêt de la source du signal.
Il est également admis de l'utiliser pour obtenir le niveau moyen prévu avant arrêt du signal d'excitation,L .
0
Le niveau peut être obtenu à partir de l'Équation (1) en fixant la valeur de t = 0:

⎡⎤
W
0 2
⎢⎥
Lh= 10 lg (t) dt dB (2)
0

⎢⎥C
ref
⎣⎦0
La Figure 2 illustre la manière d'obtenir le niveau en fonction du temps par les méthodes classique et nouvelle.

a)  Méthode classique b)  Nouvelle méthode
Légende
L niveau de bruit
h réponse impulsionnelle
t durée
NOTE Dans la méthode classique, on obtient une approximation, L (t), de la décroissance prévue en moyennant
m
(ensemble) un certain nombre de valeurs de décroissance séparées, L (t), L (t), … L (t), sur la base du bruit d'excitation.
1 2 N
Dans la nouvelle méthode, la décroissance prévue, L(t), est obtenue par traitement de la réponse impulsionnelle, h(t).
Figure 2 — Illustration de la différence entre la méthode classique et la nouvelle méthode
© ISO 2006 – Tous droits réservés 5

---------------------- Page: 10 ----------------------
ISO 18233:2006(F)
5.3 Transmission du son entre deux salles
Si une source sonore est placée dans une salle d'émission et que le niveau de pression acoustique est
mesuré au point S, le niveau sonore, L , peut, selon l'Équation (2), être obtenu à partir de la réponse
1
impulsionnelle entre le point d'excitation et le point S: ht().
1

⎡⎤
W
2
0
⎢⎥
Lh= 10 lg (t) dt dB (3)
11

⎢⎥C
ref
⎣⎦0
De la même manière, si le niveau acoustique est mesuré dans une salle de réception adjacente, au point R, le
niveau sonore, L , peut être obtenu à partir de la réponse impulsionnelle entre le point d'excitation et le
2
point R: ht() .
2

⎡⎤
W
0 2
⎢⎥
Lh= 10 lg (t) dt dB (4)
22

⎢⎥C
ref
0
⎣⎦
Par conséquent, l'isolement acoustique brut, D , c'est-à-dire la différence de niveau sonore entre le lieu
d'émission et le local de réception, peut être calculé de la manière suivante:

⎡⎤
2
⎢⎥
ht()dt
1

⎢⎥
0
DL=−L= 10 lg dB (5)
⎢⎥
12

⎢⎥
2
ht()dt
⎢⎥
2

⎢⎥
⎣⎦0
La variable décrivant la puissance du signal d'excitation, W , est éliminée du résultat d'isolement acoustique
0
brut comme étant la référence arbitrairement choisie, C .
ref
NOTE Les nouvelles méthodes spécifiées dans la présente Norme internationale peuvent également s'appliquer au
mesurage de l'isolement acoustique brut des façades. Dans ce contexte, l'un des points de mesurage sera situé à
l'extérieur.
5.4 Utilisation de la fonction de réponse en fréquence
Dans la théorie des signaux et des systèmes linéaires invariants dans le temps, un signal sinusoïdal a un
statut unique. Si l'on ne tient pas compte des transitoires qui se constituent lorsque les signaux sont activés et
désactivés, la réponse d'un tel système à une excitation sinusoïdale sera toujours sinusoïdale à la même
fréquence. L'amplitude (gain) et la phase peuvent cependant changer. L'information correspondant au
changement d'amplitude et de phase entre entrée et sortie en fonction de la fréquence est appelée la fonction
de réponse en fréquence du système. Comme la réponse impulsionnelle, la fonction de réponse en fréquence
donnera des renseignements exhaustifs sur la réponse de tout signal en entrée. La fonction de réponse en
fréquence peut être obtenue à partir de la réponse impulsionnelle par transformation de Fourier.
L'Équation (2) peut être modifiée par application du théorème de Parseval:
∞∞
W
2
2
0
Wh ()t dt= H(ω) dω (6)
0
∫∫

0 −∞

ω est la pulsation;
6 © ISO 2006 – Tous droits réservés

---------------------- Page: 11 ----------------------
ISO 18233:2006(F)
H(ω) est la fonction de réponse en fréquence obtenue par transformation de Fourier de la réponse
impulsionnelle, h(t):

−jωt
H()ω==F ht() ht()e dt (7)
{}

−∞
où j1=−
NOTE Dans l'Équation (6), on suppose que h(t) = 0 pour t < 0, ce qui sera le cas dans un système physique causal.
L'Équation (6) montre que le module de la fonction de réponse en fréquence est suffisant pour calculer le
niveau sonore. Cela n'est pas le cas pour le mesurage de la durée de réverbération, qui nécessite à la fois la
phase et le module de la fonction de réponse en fréquence.
En combinant les Équations (5) et (6), il est possible de calculer l'isolement acoustique brut prévu entre la
salle d'émission et la salle de réception, D , à partir de la réponse en fréquence des deux salles. L'isolement
acoustique brut prévu pour une bande de fraction d'octave donnée, à la fréquence inférieure d'extrémité de
ω ω
1 2
bande, f = , et à la fréquence supérieure d'extrémité de bande, f = , sera donné par l'Équation
1 2
2π 2π
suivante:
ω
⎡⎤2
2
⎢⎥
H ()ωωd
1

⎢⎥
ω
1
⎢⎥
DL=−L= 10 lg dB (8)
12
⎢⎥ω
2
2
⎢⎥
H ()ωωd
2

⎢⎥
⎢⎥ω
⎣⎦1
6 Mesurage de la réponse impulsionnelle
6.1 Généralités
La réponse impulsionnelle d'une salle sera généralement un signal oscillant qui présente un grand nombre de
périodes. L'enveloppe du signal sera irrégulière mais aura normalement un temps d'attaque rapide et une
décroissance exponentielle.
La réponse impulsionnelle peut être mesurée comme étant la réponse d'une salle à une impulsion acoustique
très courte. Cependant, dans la plupart des cas, il sera difficile, si l'on utilise des sources autres qu'un haut-
parleur, de maîtriser suffisamment le contenu spectral et la caractéristique directionnelle de l'excitation.
Pour réaliser le contrôle requis du signal d'excitation, la réponse impulsionnelle est, dans la pratique, souvent
obtenue par traitement numérique du signal. La salle est excitée pendant un certain temps par un signal
connu et la réponse impulsionnelle est calculée à partir de la réponse à l'excitation. Le signal d'excitation est
réparti sur une période de temps plus longue pour augmenter l'énergie totale rayonnée. Cette procédure
améliore la plage dynamique réalisable et réduit l'influence du bruit parasite.
Plusieurs méthodes de mesurage de la réponse impulsionnelle sont décrites dans la documentation de
référence, voir [6] à [8] et [13] à [15] dans la Bibliographie.
Aucun mouvement de la source ou du microphone n'est acceptable pour mesurer la réponse impulsionnelle,
car cela enfreint l'exigence d'invariance temporelle. La réponse impulsionnelle d'une salle est constituée d'une
interaction complexe d'ondes sonores réfléchies entre le plancher, le plafond et les cloisons de la salle. Entre
les réflexions acoustiques, la transmission est influencée par l'air ambiant. Le mouvement de l'air ou les
changements de vitesse du son (température) peuvent également enfreindre l'invariance temporelle exigée.
© ISO 2006 – Tous droits réservés 7

---------------------- Page: 12 ----------------------
ISO 18233:2006(F)
6.2 Signal d'excitation
6.2.1 Généralités
Dans les méthodes classiques, il est nécessaire d'avoir un bruit aléatoire ou une impulsion de largeur de
bande au moins égale à la largeur de bande de la chaîne de mesure. La nature aléatoire du bruit donnera une
distribution aléatoire des niveaux mesurés et limitera la répétabilité du mesurage. Les nouvelles méthodes
appliquent des signaux d'excitation déterministes, c'est-à-dire des signaux reproductibles avec précision qui,
par conséquent, améliorent la répétabilité du mesurage.
6.2.2 Exigences spectrales
6.2.2.1 Généralités
La gamme de fréquences effective du signal d'excitation doit au moins contenir la bande de fraction d'octave
réellement mesurée. S'il est effectué un mesurage en bande large couvrant l'ensemble de la gamme des
fréquences audibles, le but est d'obtenir une approximation de la forme spectrale du signal d'excitation, tel
que capté à l'emplacement du récepteur, par rapport à celle du bruit ambiant prévalant à cet endroit. Cela
permet d'obtenir un rapport signal/bruit indépendant de la fréquence. Les sources types de bruit de fond
(climatisation, circulation, etc.) te
...