Fixed firefighting systems - Components for sprinkler and water spray systems - Part 3: Dry alarm valve assemblies

This European Standard specifies requirements for construction and performance of dry alarm valve assemblies, accelerators and exhausters used in automatic sprinkler systems conforming to prEN 12845 'Automatic sprinkler systems: Design and Installation'. Auxiliary components and attachments to dry alarm valve assemblies, accelerators and exhausters are not covered by this standard.

Ortsfeste Löschanlagen - Bauteile für Sprinkler- und Sprühwasseranlagen - Teil 3: Trockenalarmventile und Zubehör

Dieser Teil der EN 12259 legt Anforderungen an die Konstruktion und Leistung von Trockenalarmventilen mit Zubehör, Schnellöffnern und Schnellentlüftern für den Einsatz in automatischen Sprinkleranlagen nach den Anhängen A und B von prEN 12845 "Ortsfeste Löschanlagen - Automatische Sprinkleranlagen - Planung und Einbau" fest.
Zusätzliche Bauteile und Zubehör zu Trockenalarmventilen, Schnellöffnern und Schnellentlüftern werden durch diese Norm nicht abgedeckt.

Systemes fixes de lutte contre l'incendie - Composants des systemes sprinkleurs et a pulvérisation d'eau - Partie 3: Postes d'alarme sous air

Vgrajene naprave za gašenje - Sestavni deli sprinklerskih sistemov in sistemov s pršečo vodo - 3. del: Suhi alarmni ventili

General Information

Status
Published
Publication Date
30-Sep-2001
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
01-Oct-2001
Due Date
01-Oct-2001
Completion Date
01-Oct-2001

Relations

Buy Standard

Amendment
EN 12259-3:2001/A1:2001
English language
10 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 12259-3:2001/A1:2001
01-oktober-2001
9JUDMHQHQDSUDYH]DJDãHQMH6HVWDYQLGHOLVSULQNOHUVNLKVLVWHPRYLQVLVWHPRYV
SUãHþRYRGRGHO6XKLDODUPQLYHQWLOL
Fixed firefighting systems - Components for sprinkler and water spray systems - Part 3:
Dry alarm valve assemblies
Ortsfeste Löschanlagen - Bauteile für Sprinkler- und Sprühwasseranlagen - Teil 3:
Trockenalarmventile und Zubehör
Systemes fixes de lutte contre l'incendie - Composants des systemes sprinkleurs et a
pulvérisation d'eau - Partie 3: Postes d'alarme sous air
Ta slovenski standard je istoveten z: EN 12259-3:2000/A1:2001
ICS:
13.220.10 Gašenje požara Fire-fighting
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
SIST EN 12259-3:2001/A1:2001 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 12259-3:2001/A1:2001

---------------------- Page: 2 ----------------------

SIST EN 12259-3:2001/A1:2001
EUROPEAN STANDARD
EN 12259-3:2000/A1
NORME EUROPÉENNE
EUROPÄISCHE NORM
March 2001
ICS 13.220.20; 13.320
English version
Fixed firefighting systems - Components for sprinkler and water
spray systems - Part 3: Dry alarm valve assemblies
Systèmes fixes de lutte contre l'incendie - Composants des Ortsfeste Löschanlagen - Bauteile für Sprinkler- und
systèmes sprinkleurs et à pulvérisation d'eau - Partie 3: Sprühwasseranlagen - Teil 3: Trockenalarmventile und
Postes d'alarme sous air Zubehör
This amendment A1 modifies the European Standard EN 12259-3:2000; it was approved by CEN on 20 January 2001.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for inclusion of this
amendment into the relevant national standard without any alteration. Up-to-date lists and bibliographical references concerning such
national standards may be obtained on application to the Management Centre or to any CEN member.
This amendment exists in three official versions (English, French, German). A version in any other language made by translation under the
responsibility of a CEN member into its own language and notified to the Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece,
Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36  B-1050 Brussels
© 2001 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 12259-3:2000/A1:2001 E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------

SIST EN 12259-3:2001/A1:2001
Page 2
EN 12259-3:2000/A1:2001
Foreword
This European Standard has been prepared by Technical Committee CEN/TC 191 "Fixed fire
fighting systems", the secretariat of which is held by BSI national standard body.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by September 2001, and conflicting national standards
shall be withdrawn at the latest by month of December 2002.
This European Standard has been prepared under a mandate given to CEN by the European
Commission and the European Free Trade Association, and supports essential requirements of EU
Directive(s).
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the
following countries are bound to implement this European Standard: Austria, Belgium, Czech
Republic, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg,
Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and the United Kingdom.
For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this
standard.
It forms one Part of EN 12259, covering components for automatic sprinkler systems and is included
in a series of European Standards planned to cover:
1
- automatic sprinkler systems (EN 12259 and EN 12845)
1
- Gaseous extinguishing systems (EN 12094)
1
- powder systems (EN 12416)
- explosion protection systems (EN 26 184)
- foam systems (EN 13565)
1
- hose reel systems (EN 671)
1
- smoke and heat control systems (EN 12101)
1
- water spray systems
EN 12259 has the general title “Fixed fire fighting systems - Components for sprinkler and water
spray systems” and will subdivided as follows:
Part 1: Sprinklers
Part 2: Wet alarm valve assemblies
Part 3: Dry alarm valve assemblies
Part 4: Water motor alarms.
Part 5: Water flow detectors.

1
 In preparation.

---------------------- Page: 4 ----------------------

SIST EN 12259-3:2001/A1:2001
Page 3
EN 12259-3:2000/A1:2001
Part 6: Pipe couplings.
Part 7: Pipe hangers.
Part 8: Pressure switches.
Part 9 Deluge alarm valve assemblies.
Part 10 Multiple controls.
Part 11 Medium and high velocity water sprayers.
Part 12 Sprinkler pump sets.

---------------------- Page: 5 ----------------------

SIST EN 12259-3:2001/A1:2001
Page 4
EN 12259-3:2000/A1:2001
9 Evaluation of conformity
9.1 General
The compliance of a wet alarm valve assembly with the requirements of this standard shall be
demonstrated by:
- initial type testing;
- factory production control by the manufacturer.
9.2 Initial type testing
Initial type testing shall be performed on first application of this standard. Tests previously performed
in accordance with the provisions of this standard (product, characteristic, test method, sampling
method and system of attestation of conformity etc.) may be taken into account. In addition, initial
type testing shall be performed at the beginning of the production of a product type or at the
beginning of a new method of production (where these may affect the stated properties).
All characteristics given in clause 4, and where appropriate clause 5, shall be subject to initial type
testing.
9.3 Factory production control (FPC)
The supplier shall establish, document and maintain an FPC system to ensure that the products
placed on the market conform with the stated performance characteristics.
The FPC system shall consist of procedures, regular inspections and tests and/or assessments and
the use of the results to control raw and other incoming materials or components, equipment, the
production process and the product. It shall be sufficiently detailed to ensure that the conformity of
the product is apparent, ensuring detection of irregularities at the earliest possible stage.
An FPC system conforming with the requirements of the relevant part(s) of EN ISO 9000, and made
specific to the requirements of this standard, shall be considered to satisfy the above requirements.
The results of inspections, tests or assessments requiring action shall be recorded, as shall any
action taken. The action to be taken when control values or criteria are not met shall be recorded.
The production control procedure shall be recorded in a manual, which shall be made available
when requested.
The supplier shall carry out and record the results of production tests as part of the production
control. These records shall be available if requested.
Leakage resistance, alarm and sensitivity characteristic tests, shall be carried out on each dry alarm
valve assembly.

---------------------- Page: 6 ----------------------

SIST EN 12259-3:2001/A1:2001
Page 5
EN 12259-3:2000/A1:2001
Annex L(informative)
Typical testing schedule and example of test specimen numbers for dry alarm valve
assemblies, accelerators and exhausters
1 x Dry alarm valve assembly.
   of each size
1 x Dry alarm valve assembly.
   only size with highest stress
   (one sample)
B  Strength test (body)
   4 x nominal pressure, 5 min
H  Resistance to adhesion
E3 Operational characteristics (dry alarm valve)
     3,5 bar outlet pressure. 90 days
o o
   1,4 bar, 2 bar to nominal pressure 1,4 bar, 5 m/s
     87 C, 21 C, 0,35 bar release
D1 Springs and diaphragms test
   5000 cycles, 6 per mi
...