SIST IEC 60364-4-44:2009
(Main)Low-voltage electrical installations - Part 4-44: Protection for safety - Protection against voltage disturbances and electromagnetic disturbances
Low-voltage electrical installations - Part 4-44: Protection for safety - Protection against voltage disturbances and electromagnetic disturbances
The rules of this Part of IEC 60364 are intended to provide requirements for the safety of electrical installations in the event of voltage disturbances and electromagnetic disturbances generated for different specified reasons. The rules of this part are not intended to apply to systems for distribution of energy to the public, or power generation and transmission for such systems (see the scope of IEC 60364-1) although such disturbances may be conducted into or between electrical installations via these supply systems.
Installations électriques à basse tension - Partie 4-44: Protection pour assurer la sécurité - Protection contre les perturbations de tension et les perturbations électromagnétiques
Les règles de la présente Partie de la CEI 60364 sont destinées à donner des exigences pour la sécurité des installations électriques en cas de perturbations de tension ou d'influences électromagnétiques dues à des raisons diverses.[
]Cette deuxième édition de la CEI 60364-4-44 annule et remplace la première édition parue en 2001, l'amendement 1 (2003) et l'amendement 2 (2006).
Električne inštalacije zgradb - 4-44. del: Zaščitni ukrepi - Zaščita pred prenapetostmi - Zaščita pred napetostnimi in elektromagnetnimi motnjami
General Information
Relations
Overview
SIST IEC 60364-4-44:2009 is an international standard published by the International Electrotechnical Commission (IEC) that focuses on the safety of low-voltage electrical installations. Specifically, it addresses protection measures against voltage disturbances and electromagnetic disturbances. This second edition, released in 2007, replaces the first edition and subsequent amendments, consolidating updated guidelines and requirements.
The main objective of SIST IEC 60364-4-44:2009 is to provide comprehensive rules that help ensure electrical installations remain safe and reliable under conditions of voltage fluctuations and electromagnetic interference. It covers various types of disturbances, including temporary overvoltages due to earth faults, atmospheric origin surges, and electromagnetic interference (EMI) caused by external sources. The standard is part of the broader IEC 60364 series, which covers different aspects of low-voltage electrical installation safety.
Key Topics
Protection against Overvoltages
The standard specifies requirements for controlling transient and temporary overvoltages within low-voltage systems:- Overvoltages due to earth faults in high- and low-voltage systems
- Atmospheric origin surges such as lightning and switching surges
- Classification and impulse withstand voltage criteria for electrical equipment
- Use and application of Surge Protective Devices (SPDs)
Electromagnetic Disturbance Mitigation
SIST IEC 60364-4-44:2009 emphasizes techniques and structural measures to reduce electromagnetic interference, including:- Sources and effects of EMI on electrical systems
- Earthing and equipotential bonding arrangements to minimize interference
- Segregation and cable management to prevent electromagnetic coupling
- Design guidelines for TN, TT, and IT earthing systems focusing on electromagnetic compatibility
Safety and System Reliability
The standard details the required measures to maintain system integrity and user safety, addressing:- Effects of neutral conductor loss and earth faults in various earthing configurations
- Protective devices suitable for different types of disturbances
- Structural provisions for multiple-source power systems including buildings with information technology equipment
- Coordination of protective measures across different building structures and system components
Applications
SIST IEC 60364-4-44:2009 serves as a critical reference for:
Electrical Installers and Designers
Ensures low-voltage installations are designed to mitigate risks from voltage and electromagnetic disturbances thereby improving safety and equipment longevity.Building and Industrial Electrical Systems
Supports the implementation of safe electrical infrastructures in residential, commercial, and industrial environments by providing guidelines on earthing, cable management, and protective device placement.Surge Protection Implementation
Provides practical criteria for selecting and installing Surge Protective Devices and managing overvoltage conditions originating from natural and artificial sources.Information Technology Infrastructure
Addresses special considerations for IT equipment sensitive to electromagnetic interference, ensuring reliable operation within commercial and industrial facilities.Multiple-Source Power Supplies
Guides coordination of safety measures where alternative power sources or complex supply networks are involved.
Related Standards
IEC 60364 Series
SIST IEC 60364-4-44:2009 is part of the comprehensive IEC 60364 family covering low-voltage electrical installations and safety measures throughout different parts.IEC 61000 Series – Electromagnetic Compatibility (EMC)
Provides more detailed requirements for electromagnetic compatibility and mitigation techniques beyond installation protection.IEC 61643 Series – Surge Protective Devices
Focuses on the characteristics, testing, and application of SPDs, which complement the requirements specified in SIST IEC 60364-4-44:2009.ISO/IEC Directives
The preparation and maintenance of SIST IEC 60364-4-44:2009 follow these directives, ensuring harmonized international standards.
Keywords: SIST IEC 60364-4-44:2009, low-voltage electrical installations, voltage disturbances, electromagnetic disturbances, electrical safety, overvoltage protection, surge protective devices, electromagnetic interference mitigation, earthing and bonding, TN system, TT system, IT system, electrical installation standards, IEC standards, low-voltage safety requirements.
Frequently Asked Questions
SIST IEC 60364-4-44:2009 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Low-voltage electrical installations - Part 4-44: Protection for safety - Protection against voltage disturbances and electromagnetic disturbances". This standard covers: The rules of this Part of IEC 60364 are intended to provide requirements for the safety of electrical installations in the event of voltage disturbances and electromagnetic disturbances generated for different specified reasons. The rules of this part are not intended to apply to systems for distribution of energy to the public, or power generation and transmission for such systems (see the scope of IEC 60364-1) although such disturbances may be conducted into or between electrical installations via these supply systems.
The rules of this Part of IEC 60364 are intended to provide requirements for the safety of electrical installations in the event of voltage disturbances and electromagnetic disturbances generated for different specified reasons. The rules of this part are not intended to apply to systems for distribution of energy to the public, or power generation and transmission for such systems (see the scope of IEC 60364-1) although such disturbances may be conducted into or between electrical installations via these supply systems.
SIST IEC 60364-4-44:2009 is classified under the following ICS (International Classification for Standards) categories: 29.120.50 - Fuses and other overcurrent protection devices; 91.140.50 - Electricity supply systems. The ICS classification helps identify the subject area and facilitates finding related standards.
SIST IEC 60364-4-44:2009 has the following relationships with other standards: It is inter standard links to SIST IEC 60364-4-44:2006, SIST HD 60364-4-444:2011. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
SIST IEC 60364-4-44:2009 is associated with the following European legislation: EU Directives/Regulations: TRRTP131. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.
You can purchase SIST IEC 60364-4-44:2009 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of SIST standards.
Standards Content (Sample)
SLOVENSKI SIST IEC 60364-4-44:2006
STANDARD
september 2006
Električne inštalacije zgradb – 4-44. del: Zaščitni ukrepi – Zaščita pred
prenapetostmi – Zaščita pred napetostnimi motnjami in pred
elektromagnetnimi motnjami
Electrical installations of buildings - Part 4-44: Protection for safety - Protection
against voltag
...
SLOVENSKI STANDARD
01-april-2009
1DGRPHãþD
SIST IEC 60364-4-44:2006
(OHNWULþQHLQãWDODFLMH]JUDGEGHO=DãþLWQLXNUHSL=DãþLWDSUHG
SUHQDSHWRVWPL=DãþLWDSUHGQDSHWRVWQLPLLQHOHNWURPDJQHWQLPLPRWQMDPL
Low-voltage electrical installations - Part 4-44: Protection for safety - Protection against
voltage disturbances and electromagnetic disturbances
Installations électriques à basse tension - Partie 4-44: Protection pour assurer la sécurité
- Protection contre les perturbations de tension et les perturbations électromagnétiques
Ta slovenski standard je istoveten z: IEC 60364-4-44
ICS:
29.120.50 9DURYDONHLQGUXJD Fuses and other overcurrent
PHGWRNRYQD]DãþLWD protection devices
91.140.50 Sistemi za oskrbo z elektriko Electricity supply systems
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
Edition 2.0 2007-08
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Low-voltage electrical installations –
Part 4-44: Protection for safety – Protection against voltage disturbances and
electromagnetic disturbances
Installations électriques à basse tension –
Partie 4-44: Protection pour assurer la sécurité – Protection contre les
perturbations de tension et les perturbations électromagnétiques
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
XA
CODE PRIX
ICS 91.140.50 ISBN 2-8318-9261-9
– 2 – 60364-4-44 © IEC:2007
CONTENTS
FOREWORD.5
INTRODUCTION.7
440.1 Scope .8
440.2 Normative references.8
441 (Vacant).9
442 Protection of low-voltage installations against temporary overvoltages due to earth
faults in the high-voltage system and due to faults in the low-voltage system .
442.1 Scope and object .9
442.1.1 General.9
442.1.2 Symbols .10
442.2 Overvoltages in LV-systems during a high-voltage earth fault .11
442.2.1 Magnitude and duration of power frequency fault-voltage .12
442.2.2 Magnitude and duration of power frequency stress-voltages.13
442.2.3 Requirements for calculation of limits .14
442.3 Power frequency stress voltage in case of loss of the neutral conductor in a
TN and TT system .14
442.4 Power frequency stress voltage in the event of an earth fault in an IT system
with distributed neutral .14
442.5 Power frequency stress voltage in the event of short-circuit between a line
conductor and the neutral conductor .14
443 Protection against overvoltages of atmospheric origin or due to switching.14
443.1 General .14
443.2 Classification of impulse withstand voltages (overvoltage categories) .15
443.2.1 Purpose of classification of impulse withstand voltages
(overvoltage categories) .15
443.2.2 Relationship between impulse withstand voltages of equipment and
overvoltage categories .15
443.3 Arrangements for overvoltage control.16
443.3.1 Inherent overvoltage control .16
443.3.2 Protective overvoltage control.16
443.4 Required impulse withstand voltage of equipment.18
444 Measures against electromagnetic influences.18
444.1 General .18
444.2 (void) .19
444.3 Definitions .19
444.4 Mitigation of Electromagnetic Interference (EMI) .20
444.4.1 Sources of EMI.20
444.4.2 Measures to reduce EMI.21
444.4.3 TN-system .22
444.4.4 TT system .26
444.4.5 IT system .27
444.4.6 Multiple-source supply.28
444.4.7 Transfer of supply .31
444.4.8 Services entering a building.33
444.4.9 Separate buildings.34
444.4.10 Inside buildings .34
444.4.11 Protective devices .36
60364-4-44 © IEC:2007 – 3 –
444.4.12 Signal cables.36
444.5 Earthing and equipotential bonding.36
444.5.1 Interconnection of earth electrodes.36
444.5.2 Interconnection of incoming networks and earthing arrangements.37
444.5.3 Different structures for the network of equipotential conductors and
earthing conductors.37
444.5.4 Equipotential bonding networks in buildings with several floors .39
444.5.5 Functional earthing conductor.40
444.5.6 Commercial or industrial buildings containing significant amounts
of information technology equipment.41
444.5.7 Earthing arrangements and equipotential bonding of information
technology installations for functional purposes .41
444.6 Segregation of circuits .42
444.6.1 General.42
444.6.2 Design guidelines .42
444.6.3 Installation guidelines .43
444.7 Cable management systems .44
444.7.1 General.44
444.7.2 Design guidelines .44
444.7.3 Installation guidelines .45
445 Protection against undervoltage .47
445.1 General requirements .47
Annex A (informative) Explanatory notes concerning 442.1 and 442.2.48
Annex B (informative) Guidance for overvoltage control by SPDs applied to overhead
lines.50
Annex C (normative) Determination of the conventional length, d .52
Bibliography .54
Figure 44.A1 – Representative schematic sketch for possible connections to earth in
substation and LV-Installation and occurring overvoltages in case of faults .11
Figure 44.A2 – Tolerable fault-voltage due to an earth-fault in the HV system .13
Figure 44.R1 − By-pass conductor for screen reinforcement to provide a common
equipotential bonding system .21
Figure 44.R2 − Example of a substitute or by-pass equipotential bonding conductor in a
TT-system.22
Figure 44.R3A − Avoidance of neutral conductor currents in a bonded structure by
using the TN-S system from the origin of the public supply up to and including the final
circuit within a building .23
Figure 44.R3B − Avoidance of neutral conductor currents in a bonded structure by using
a TN-S system downstream of a consumer’s private supply transformer .24
Figure 44.R4 − TN-C-S system within an existing building installation .25
Figure 44.R5 – TT system within a building installation .26
Figure 44.R6 – IT system within a building installation .27
Figure 44.R7A – TN multiple-source power supply with a non-suitable multiple
connection between PEN and earth .28
Figure 44.R7B – TN multiple source power supplies to an installation with connection to
earth of the star points at one and the same point .29
– 4 – 60364-4-44 © IEC:2007
Figure 44.R8 – TT multiple-source power supplies to an installation with connection to
earth of the star points at one and the same point .30
Figure 44.R9A − Three-phase alternative power supply with a 4-pole switch .31
Figure 44.R9B – Neutral current flow in a three-phase alternative power supply with an
unsuitable 3-pole switch .32
Figure 44.R9C − Single-phase alternative power supply with 2-pole switch.33
Figure 44.R10 − Armoured cables and metal pipes entering the buildings (examples) .34
Figure 44.R11 − Illustration of measures in an existing building .35
Figure 44.R12 – Interconnected earth electrodes.36
Figure 44.R13 – Examples of protective conductors in star network .37
Figure 44.R14 – Example of multiple meshed bonding star network .38
Figure 44.R15 – Example of a common meshed bonding star network .39
Figure 44.R16 – Example of equipotential bonding networks in structures without
lightning protection systems .40
Figure 44.R17A − Separation between power and information technology cables for
cable route lengths ≤ 35 m .43
Figure 44.R17B − Separation between power and information technology cables for
cable route lengths > 35 m .43
Figure 44.R18 – Separation of cables in wiring systems.44
Figure 44.R19 – Cable arrangements in metal cable-trays .45
Figure 44.R20 – Continuity of metallic system components .46
Figure 44.R21 – Location of cables inside metallic construction elements .46
Figure 44.R22 – Connection of metallic sections.47
Figure 44.Q – Examples of how to apply d , d and d for the determination of d .53
1 2 3
Table 44.A1 – Power frequency stress voltages and power frequency fault voltage in the
low voltage system .12
Table 44.A2 – Permissible power frequency stress-voltage.13
Table 44.B – Required rated impulse withstand voltage of equipment .18
Table B.1 – Different possibilities for IT systems.51
60364-4-44 © IEC:2007 – 5 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
_______________
LOW-VOLTAGE ELECTRICAL INSTALLATIONS –
Part 4-44: Protection for safety –
Protection against voltage disturbances and
electromagnetic disturbances
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60364-4-44 has been prepared by IEC technical committee 64:
Electrical installations and protection against electric shock.
This second edition of IEC 60364-4-44 cancels and replaces the first edition published in 2001,
amendment 1 (2003) and amendment 2 (2006).
The document 64/1600/FDIS, circulated to the National Committees as Amendment 3, led to
the publication of the new edition.
– 6 – 60364-4-44 © IEC:2007
The text of this standard is based on the first edition, its Amendment 1, Amendment 2 and the
following documents:
FDIS Report on voting
64/1600/FDIS 64/1609/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
A list of all the parts in the IEC 60364 series, under the general title Low-voltage electrical
installations, can be found on the IEC website.
Future standards in this series will carry the new general title as cited above. Titles of existing
standards in this series will be updated at the time of the next edition.
The committee has decided that the contents of this publication will remain unchanged until the
maintenance result date indicated on the IEC web site under "http://webstore.iec.ch" in the data
related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
60364-4-44 © IEC:2007 – 7 –
INTRODUCTION
Part 4-44 of IEC 60364 covers the protection of electrical installations and measures against
voltage disturbances and electromagnetic disturbances.
The requirements are arranged into four clauses as follows:
Clause 442 Protection of low-voltage installations against temporary overvoltages due to
earth faults in the high-voltage system and due to faults in the low-voltage
system
Clause 443 Protection against overvoltages of atmospheric origin or due to switching
Clause 444 Measures against electromagnetic influences
Clause 445 Protection against undervoltage
– 8 – 60364-4-44 © IEC:2007
LOW-VOLTAGE ELECTRICAL INSTALLATIONS –
Part 4-44: Protection for safety –
Protection against voltage disturbances and
electromagnetic disturbances
440.1 Scope
The rules of this Part of IEC 60364 are intended to provide requirements for the safety of
electrical installations in the event of voltage disturbances and electromagnetic disturbances
generated for different specified reasons.
The rules of this part are not intended to apply to systems for distribution of energy to the
public, or power generation and transmission for such systems (see the scope of IEC 60364-1)
although such disturbances may be conducted into or between electrical installations via these
supply systems.
440.2 Normative references
The following referenced documents are indispensable for the application of this document. For
dated references, only the edition cited applies. For undated references, the latest edition of
the referenced document (including any amendments) applies.
IEC 60038:1983, IEC standard voltages
IEC 60050-604:1987, International Electrotechnical Vocabulary – Chapter 604: Generation,
transmission and distribution of electricity – Operation
IEC 60364-1, Low-voltage electrical installations – Part 1: Fundamental principles, assessment
of general characteristics, definitions
IEC 60364-4-41:2005, Electrical installations of buildings – Part 4-41: Protection for safety –
Protection against electric shock
IEC 60364-5-54:2002, Electrical installations of buildings − Part 5-54: Selection and erection of
electrical equipment – Earthing arrangements and protective bonding conductors
IEC 60479-1:2005, Effects of current on human beings and livestock – Part 1: General aspects
IEC 60664-1:2007, Insulation co-ordination for equipment within low-voltage systems – Part 1:
Principles, requirements and tests
IEC 60950-1, Information technology equipment – Safety – Part 1: General requirements
IEC 61000-2-5:1995, Electromagnetic compatibility (EMC) − Part 2: Environment − Section 5:
Classification of electromagnetic environments – Basic EMC publication
IEC 61000-6-1, Electromagnetic compatibility (EMC) – Part 6-1: Generic standards – Immunity
for residential, commercial and light-industrial environments
IEC 61000-6-2, Electromagnetic compatibility (EMC) – Part 6-2: Generic standards – Immunity
for industrial environments
___________
A third edition is currently in preparation.
60364-4-44 © IEC:2007 – 9 –
IEC 61000-6-3, Electromagnetic compatibility (EMC) – Part 6-3: Generic standards – Emission
standard for residential, commercial and light-industrial environments
IEC 61000-6-4, Electromagnetic compatibility (EMC) – Part 6-4: Generic standards – Emission
standard for industrial environments
IEC 61558-2-1, Safety of power transformers, power supplies, reactors and similar products –
Part 2-1: Particular requirements for tests for separating transformers and power supplies
incorporating separating transformers for general applications
IEC 61558-2-4, Safety of power transformers, power supply units and similar – Part 2-4:
Particular requirements for isolating transformers for general use
IEC 61558-2-6, Safety of power transformers, power supply units and similar – Part 2-6:
Particular requirements for safety isolating transformers for general use
IEC 61558-2-15, Safety of power transformers, power supply units and similar – Part 2-15:
Particular requirements for isolating transformers for the supply of medical locations
IEC 61643 (all parts), Low-voltage surge protective devices
IEC 61936-1, Power installations exceeding 1 kV a.c. – Part 1: Common rules
IEC 62305-1, Protection against lightning – Part 1: General principles
IEC 62305-3, Protection against lightning – Part 3: Physical damage to structures and life
hazard
IEC 62305-4, Protection against lightning – Part 4: Electrical and electronic systems within
structures
441 (Vacant)
442 Protection of low-voltage installations against temporary overvoltages due
to earth faults in the high-voltage system and due to faults in the low-
voltage system
442.1 Field of application
The rules of this clause provide requirements for the safety of low-voltage installation in the
event of
– a fault between the high-voltage system and earth in the transformer substation that
supplies the low-voltage installation,
– a loss of the supply neutral in the low-voltage system,
– a short-circuit between a line conductor and neutral,
– an accidental earthing of a line conductor of a low-voltage IT-system.
The requirements for the earthing arrangement at the transformer substation are given in
IEC 61936-1.
442.1.1 General requirements
As Clause 442 covers faults between a high-voltage line and the earth in the HV/LV substation,
it gives rules for the designer and installer of the substation. It is necessary to have the
following information concerning the high-voltage system:
– quality of the system earthing;
– 10 – 60364-4-44 © IEC:2007
– maximum level of earth fault current;
– resistance of the earthing arrangement.
The following subclauses consider four situations as proposed in 442.1, which generally cause
the most severe temporary overvoltages such as defined in IEC 60050-604:
– fault between the high-voltage system(s) and earth (see 442.2);
– loss of the neutral in a low-voltage system (see 442.3);
– accidental earthing of a low-voltage IT system (see 442.4);
– short-circuit in the low-voltage installation (see 442.5).
442.1.2 Symbols
In Clause 442 the following symbols are used (see Figure 44.A1):
I part of the earth fault current in the high-voltage system that flows through the earthing
E
arrangement of the transformer substation.
resistance of the earthing arrangement of the transformer substation.
R
E
R resistance of the earthing arrangement of the exposed-conductive-parts of the
A
equipment of the low-voltage installation.
R resistance of the earthing arrangement of the low-voltage system neutral, for low-
B
voltage systems in which the earthing arrangements of the transformer substation and
of the low-voltage system neutral are electrically independent.
U in TN- and TT-systems: nominal a.c. r.m.s. line voltage to earth
o
in IT-systems: nominal a.c. voltage between line conductor and neutral conductor or
mid point conductor, as appropriate
U power-frequency fault voltage that appears in the low-voltage system between exposed-
f
conductive-parts and earth for the duration of the fault.
power-frequency stress voltage between the line conductor and the exposed-
U
conductive-parts of the low-voltage equipment of the transformer substation during the
fault.
U power-frequency stress voltage between the line conductor and the exposed-
conductive-parts of the low-voltage equipment of the low-voltage installation during the
fault.
NOTE 1 The power-frequency stress voltage (U and U ) is the voltage that appears across the insulation of low-
1 2
voltage equipment and across surge protective devices connected to the low-voltage system.
The following additional symbols are used in respect of IT-systems in which the exposed-
conductive-parts of the equipment of the low-voltage installation are connected to an earthing
arrangement that is electrically independent of the earthing arrangement of the transformer
substation.
I fault current that flows through the earthing arrangement of the exposed-conductive-
h
parts of the equipment of the low-voltage installation during a period when there is a
high-voltage fault and a first fault in the low-voltage installation (see Table 44.A1).
I fault current, in accordance with 411.6.2, that flows through the earthing arrangement
d
of the exposed-conductive-parts of the low-voltage installation during the first fault in a
low-voltage system (see Table 44.A1).
60364-4-44 © IEC:2007 – 11 –
Z impedance (e.g. IMD internal impedance, artificial neutral impedance) between the low-
voltage system and an earthing arrangement.
NOTE 2 An earthing arrangement may be considered electrically independent of another earthing arrangement if a
rise of potential with respect to earth in one earthing arrangement does not cause an unacceptable rise of potential
with respect to earth in the other earthing arrangement. See IEC 61936-1.
442.2 Overvoltages in LV-systems during a high-voltage earth fault
In case of a fault to earth on the HV-side of the substation, the following types of overvoltage
may affect the LV-installation:
• power frequency fault-voltage (U );
f
• power frequency stress-voltages (U and U ).
1 2
Table 44.A1 provides the relevant methods of calculation for the different types of
overvoltages.
NOTE 1 Table 44.A1 deals with IT systems with a neutral point only. For IT systems with no neutral point, the
formulae should be adjusted accordingly.
Substation
U LV Installation
U
HV LV
L1
L2
L3
or N or PEN
Z
I R R R U
E E B A f
IEC 1379/07
Figure 44.A1 – Representative schematic sketch for possible connections to earth
in substation and LV-installation and occurring overvoltages in case of faults
Where high- and low-voltage earthing systems exist in proximity to each other, two practices
are presently used:
– interconnection of all high-voltage (R ) and low-voltage (R ) earthing systems;
E B
– separation of high-voltage (R ) from low-voltage (R ) earthing systems.
E B
The general method used is interconnection. The high- and low-voltage earthing systems shall
be interconnected if the low-voltage system is totally confined within the area covered by the
high-voltage earthing system (see IEC 61936-1).
NOTE 2 Details of the different types of system earthing (TN, TT, IT) are shown in IEC 60364-1.
– 12 – 60364-4-44 © IEC:2007
Table 44.A1 – Power-frequency stress voltages and power-frequency fault
voltage in low-voltage system
Types of
Types of earth
system U U U
1 2 f
connections
earthing
R and R connected U *) R × I + U 0 *)
E B
o E E o
TT
R and R separated R × I + U U *) 0 *)
E B
E E o o
R and R connected U *) U *) R × I **)
E B
o o E E
TN
R and R separated R × I + U U*) 0 *)
E B
E E o o
U *) R × I + U 0 *)
o E E o
R and Z connected
E
R and R separated
E A
R × I
U × 3 R × I + U × 3
A h
o E E o
U *) U *)
R × I
o o
E E
R and Z connected
E
IT R and R interconnected
E A
R × I
U × 3 U × 3
E E
o o
R × I + U U*) 0 *)
E E o o
R and Z separated
E
R and R separated
E A
R × I
R × I + U × 3 U × 3
A d
E E o o
*) No consideration needs to be given.
**) See 442.2.1 second paragraph.
With existing earth fault in the installation.
NOTE 3 The requirements for U and U are derived from design criteria for insulation of low-voltage equipment
1 2
with regard to temporary power-frequency overvoltage (see also Table 44.A2).
NOTE 4 In a system whose neutral is connected to the earthing arrangement of the transformer substation, such
temporary power-frequency overvoltage is also to be expected across insulation which is not in an earthed
enclosure when the equipment is outside a building.
NOTE 5 In TT- and TN-systems the statement “connected” and “separated” refers to the electrical connection
between RE and RB. For IT-systems it refers to the electrical connection between RE and Z and the connection
between R and R .
E A
442.2.1 Magnitude and duration of power-frequency fault voltage
The magnitude and the duration of the fault voltage U (as calculated in Table 44.A1) which
f
appears in the LV installation between exposed-conductive-parts and earth, shall not exceed
the values given for U by the curve of Figure 44.A2 for the duration of the fault.
f
Normally, the PEN conductor of the low-voltage system is connected to earth at more than one
point. In this case, the total resistance is reduced. For these multiple grounded PEN
conductors, U can be calculated as:
f
U = 0,5 R × I
f F F
60364-4-44 © IEC:2007 – 13 –
Fault voltage duration
1 200
1 100
1 000
10 100 1 000 10 000
Time of duration t (ms)
IEC 1380/07
Figure 44.A2 – Tolerable fault voltage due to an earth-fault in the HV system
NOTE The curve shown in Figure 44.A2 is taken from IEC 61936-1. On the basis of probabilistic and statistical
evidence this curve represents a low level of risk for the simple worst case where the low voltage system neutral
conductor is earthed only at the transformer substation earthing arrangements. Guidance is provided in
IEC 61936-1 concerning other situations.
442.2.2 Magnitude and duration of power-frequency stress voltages
The magnitude and the duration of the power-frequency stress voltage (U and U ) as
1 2
calculated in Table 44.A1 of the low-voltage equipment in the low-voltage installation due to an
earth fault in the high-voltage system shall not exceed the requirements given in Table 44.A2.
Table 44.A2 – Permissible power-frequency stress voltage
Duration of the earth fault in the Permissible power-frequency stress voltage on equipment
high-voltage system in low-voltage installations
t U
>5 s U + 250 V
o
U + 1 200 V
≤5 s
o
In systems without a neutral conductor, U shall be the line-to-line voltage.
o
NOTE 1 The first line of the table relates to high-voltage systems having long disconnection times, for example,
isolated neutral and resonant earthed high-voltage systems. The second line relates to high-voltage systems
having short disconnection times, for example low-impedance earthed high-voltage systems. Both lines together
are relevant design criteria for insulation of low-voltage equipment with regard to temporary power frequency
overvoltage, see IEC 60664-1.
NOTE 2 In a system whose neutral is connected to the earthing arrangement of the transformer substation,
such temporary power-frequency overvoltage is also to be expected across insulation which is not in an earthed
enclosure when the equipment is outside a building.
Fault voltage U (V)
f
– 14 – 60364-4-44 © IEC:2007
442.2.3 Requirements for calculation of limits
Where required by Table 44.A1, the permissible power-frequency stress voltage shall not
exceed the value given in Table 44.A2.
Where required by Table 44.A1, the permissible power-frequency fault voltage shall not exceed
the value given in Figure 44.A2.
The requirements of 442.2.1 and 442.2.2 are deemed to be fulfilled for installations receiving a
supply at low-voltage from a public electricity distribution system.
To fulfil the above requirements, coordination between the HV-system operator and the LV-
system installer is necessary. Compliance with the above requirements mainly falls into the
responsibility of the substation installer/owner/operator who needs also to fulfil requirements
provided by IEC 61936-1. Therefore the calculation for U , U and U is normally not necessary
1 2 f
for the LV system installer.
Possible measures to fulfil the above requirements are e.g.
• separation of earthing arrangement between HV and LV;
• change of LV system earthing;
• reduction of earth resistance R
E.
442.3 Power-frequency stress voltage in case of loss of the neutral conductor in a TN
and TT system
Consideration shall be given to the fact that, if the neutral conductor in a multi-phase system is
interrupted, basic, double and reinforced insulation as well as components rated for the voltage
between line and neutral conductors can be temporarily stressed with the line-to-Iine voltage.
The stress voltage can reach up to U = √3 U .
o
442.4 Power-frequency stress voltage in the event of an earth fault in an IT system
with distributed neutral
Consideration shall be given to the fact that, if a line conductor of an IT system is earthed
accidentally, insulation or components rated for the voltage between line and neutral
conductors can be temporarily stressed with the line-to-Iine voltage. The stress voltage can
reach up to U = √3 U .
o
442.5 Power-frequency stress voltage in the event of a short-circuit between a line
conductor and the neutral conductor
Consideration shall be given to the fact that if a short-circuit occurs in the low-voltage
installation between a phase conductor and the neutral conductor, the voltage between the
other line conductors and the neutral conductor can reach the value of 1,45 x U for a time up
o
to 5 s.
443 Protection against overvoltages of atmospheric origin or due to switching
443.1 General
This clause of IEC 60364-4-44 deals with protection of electrical installations against transient
overvoltages of atmospheric origin transmitted by the supply distribution system and against
switching overvoltages.
In general, switching overvoltages are lower than overvoltages of atmospheric origin and
therefore the requirements regarding protection against overvoltages of atmospheric origin
normally cover protection against switching overvoltages.
60364-4-44 © IEC:2007 – 15 –
NOTE 1 Statistical evaluations of measurements have shown that there is a low risk of switching overvoltages
higher than the level of overvoltage category II. See 443.2.
Consideration shall be given to the overvoltages which can appear at the origin of an
installation, to the expected keraunic level and to the location and characteristics of surge
protective devices, so that the probability of incidents due to overvoltage stresses is reduced to
an acceptable level for the safety of persons and property, as well as for the continuity of
service desired.
The values of transient overvoltages depend on the nature of the supply distribution system
(underground or overhead) and the possible existence of a surge protective device upstream of
the origin of the installation and the voltage level of the supply system.
This clause provides guidance where protection against overvoltages is covered by inherent
control or assured by protective control. If the protection according to this clause is not
provided, insulation co-ordination is not assured and the risk due to overvoltages shall be
evaluated.
This clause does not apply in case of overvoltages due to direct or nearby lightning. For
protection against transient overvoltages due to direct lightning, IEC 62305-1, IEC 62305-3,
IEC 62305-4 and the IEC 61643 series are applicable. This clause does not cover overvoltage
through data-transmission systems.
NOTE 2 As regards transient atmospheric overvoltages, no distinction is made between earthed and unearthed
systems.
NOTE 3 Switching overvoltages generated outside the installation and transmitted by the supply network are under
consideration.
NOTE 4 The risk due to overvoltages is considered in IEC 61662 and its amendment 1.
443.2 Classification of impulse withstand voltages (overvoltage categories)
443.2.1 Purpose of classification of impulse withstand voltages (overvoltage
categories)
NOTE 1 Overvoltage categories are defined within electrical installations for the purpose of insulation co-
ordination and a related classification of equipment with impulse withstand voltages is provided, see Table 44B.
NOTE 2 The rated impulse withstand voltage is an impulse withstand voltage assigned by the manufacturer to the
equipment or to a part of it, characterizing the specified withstand capability of its insulation against overvoltages
(in accordance with 3.9.2 of IEC 60664-1).
The impulse withstand voltage (overvoltage category) is used to classify equipment energized
directly from the mains.
Impulse withstand voltages for equipment selected according to the nominal voltage are
provided to distinguish different levels of availability of equipment with regard to continuity of
service and an acceptable risk of failure. By selection of equipment with a classified impulse
withstand voltage, insulation co-ordination can be achieved in the whole installation, reducing
the risk of failure to an acceptable level.
NOTE 3 Transient overvoltages transmitted by the supply distribution system are not significantly attenuated
downstream in most installations.
443.2.2 Relationship between impulse withstand voltages of equipment and
overvoltage categories
Equipment with an impulse withstand voltage corresponding to overvoltage category IV is
suitable for use at, or in the proximity of, the origin of the installation, for example upstream of
the main distribution board. Equipment of category IV has a very high impulse withstand
capability providing the required high degree of reliability.
– 16 – 60364-4-44 © IEC:2007
NOTE 1 Examples of such equipment are electricity meters, primary overcurrent protection devices and ripple
control units.
Equipment with an impulse withstand voltage corresponding to overvoltage category III is for
use in the fixed installation downstream of, and including the main distribution board, providing
a high degree of availability.
NOTE 2 Examples of such equipment are distribution boards, circuit-breakers, wiring systems (see IEC 60050-
826, definition 826-15-01), including cables, bus-bars, junction boxes, switches, socket-outlets) in the fixed
installation, and equipment for industrial use and some other equipment, e.g. stationary motors with permanent
connection to the fixed installation.
Equipment with an impulse withstand voltage corresponding to overvoltage category II is
suitable for connection to the fixed electrical installation, providing a normal degree of
availability normally required for current-using equipment.
NOTE 3 Examples of such equipment are household appliances and similar loads.
Equipment with an impulse withstand voltage corresponding to overvoltage category I is only
suitable for use in the fixed installation of buildings where protective means are applied outside
the equipment – to limit transient overvoltages to the specified level.
NOTE 4 Examples of such equipment are those containing electronic circuits like computers, appliances with
electronic programmes, etc.
Equipment with an impulse withstand voltage corresponding to overvoltage category I shall not
have direct connection to a public supply system.
443.3 Arrangements for overvoltage control
Overvoltage control is arranged in accordance with the following requirements.
443.3.1 Inherent overvoltage control
This subclause does not apply when a risk assessment according to 443.3.2.2 is used.
Where an installation is supplied by a completely buried low-voltage system and does not
include overhead lines, the impulse withstand voltage of equipment in accordance with Table
44B is sufficient and no specific protection against overvoltages of atmospheric origin is
necessary.
NOTE 1 A suspended cable having insulated conductors with earthed metallic screen is considered as equivalent
to an underground cable.
Where an installation is supplied by or includes a low-voltage overhead line and the keraunic
level is lower than or equal to 25 days per year (AQ 1), no specific protection against over-
voltages of atmospheric origin is required.
NOTE 2 Irrespective of the AQ value, protection against overvoltages may be necessary in applications where a
higher reliability or higher risks (e.g. fire) are expected.
In both cases, consideration regarding protection against transient overvoltages shall be given
to equipment with an impulse withstand voltage according to overvoltage category I (see
443.2.2).
443.3.2 Protective overvoltage control
The decision as to which of the following methods are applied in a country with regard to the
provision of surge protective devices (SPDs) is left to the national committee based on the
local conditions.
...
SLOVENSKI STANDARD
01-april-2009
1DGRPHãþD
SIST IEC 60364-4-44:2006
(OHNWULþQHLQãWDODFLMH]JUDGEGHO=DãþLWQLXNUHSL=DãþLWDSUHG
SUHQDSHWRVWPL=DãþLWDSUHGQDSHWRVWQLPLLQHOHNWURPDJQHWQLPLPRWQMDPL
Low-voltage electrical installations - Part 4-44: Protection for safety - Protection against
voltage disturbances and electromagnetic disturbances
Installations électriques à basse tension - Partie 4-44: Protection pour assurer la sécurité
- Protection contre les perturbations de tension et les perturbations électromagnétiques
Ta slovenski standard je istoveten z: IEC 60364-4-44
ICS:
29.120.50 9DURYDONHLQGUXJD Fuses and other overcurrent
PHGWRNRYQD]DãþLWD protection devices
91.140.50 Sistemi za oskrbo z elektriko Electricity supply systems
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
Edition 2.0 2007-08
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Low-voltage electrical installations –
Part 4-44: Protection for safety – Protection against voltage disturbances and
electromagnetic disturbances
Installations électriques à basse tension –
Partie 4-44: Protection pour assurer la sécurité – Protection contre les
perturbations de tension et les perturbations électromagnétiques
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
XA
CODE PRIX
ICS 91.140.50 ISBN 2-8318-9261-9
– 56 – 60364-4-44 © CEI:2007
SOMMAIRE
AVANT-PROPOS.59
INTRODUCTION.61
440.1 Domaine d'application et objet .62
440.2 Références normatives .62
441 (Disponible) .63
442 Protection des installations électriques à basse tension contre les surtensions
temporaires dues à des défauts à la terre dans le réseau haute tension et dues à
des défauts dans le réseau basse tension .63
442.1 Domaine d’application .63
442.1.1 Généralités .63
442.1.2 Symboles .64
442.2 Surtensions dans un réseau BT en cas de défaut HT.65
442.2.1 Valeur et durée de la tension de défaut à fréquence industrielle .66
442.2.2 Valeur et durée des contraintes à fréquence industrielle .67
442.2.3 Exigences pour le calcul des limites.68
442.3 Contraintes de tension en cas de rupture du conducteur neutre en
schémas TN et en schéma TT .68
442.4 Contraintes de tension en cas de défaut à la terre en schéma IT avec
neutre distribué .68
442.5 Contraintes de tension en cas de court-circuit entre phase et neutre .69
443 Protection contre les surtensions d’origine atmosphérique ou dues à des
manœuvres .69
443.1 Généralités.69
443.2 Classification des tensions de tenue aux chocs (catégories de surtensions) .70
443.2.1 Objet de la classification des tensions de tenue aux chocs
(catégories de surtensions).70
443.2.2 Relation entre tensions de tenue aux chocs des matériels et
catégories de surtensions .70
443.3 Dispositions pour la maîtrise des surtensions .71
443.3.1 Situation naturelle des surtensions .71
443.3.2 Situation contrôlée des surtensions.71
443.4 Tensions de tenue aux chocs prescrites pour les matériels.72
444 Dispositions contre les influences électromagnétiques.73
444.1 Généralités.73
444.2 (disponible).73
444.3 Définitions .74
444.4 Mesures d’atténuation des influences électromagnétiques.75
444.4.1 Sources des influences électromagnétiques.75
444.4.2 Dispositions de réduction des perturbations électromagnétiques.75
444.4.3 Schéma TN .77
444.4.4 Schéma TT .81
444.4.5 Schéma IT .82
444.4.6 Alimentation par plusieurs sources.83
444.4.7 Commutation de l’alimentation .86
444.4.8 Pénétration des services dans un bâtiment .89
444.4.9 Bâtiments séparés .89
444.4.10 Installations dans les bâtiments .89
60364-4-44 © CEI:2007 – 57 –
444.4.11 Dispositifs de protection.92
444.4.12 Câbles de communication .92
444.5 Mise à la terre et liaisons équipotentielles .92
444.5.1 Interconnexion des prises de terre .92
444.5.2 Interconnexion des réseaux entrants et mise à la terre .93
444.5.3 Différentes structures du réseau des conducteurs
d'équipotentialité et de mise à la terre.93
444.5.4 Réseau de terre dans des bâtiments à plusieurs étages.95
444.5.5 Conducteurs d'équipotentialité fonctionnelle .96
444.5.6 Bâtiments tertiaires ou industriels avec une installation importante
de matériels de traitement de l'information.97
444.5.7 Dispositions de mise à la terre et équipotentialités fonctionnelles
des matériels de traitement de l’information pour des raisons
fonctionnelles.97
444.6 Séparation des circuits .98
444.6.1 Généralités .98
444.6.2 Conception .98
444.6.3 Règles de mise en œuvre .99
444.7 Mise en œuvre des canalisations.100
444.7.1 Généralités .100
444.7.2 Guide de conception .100
444.7.3 Règles d’installation.101
445 Protection contre les baisses de tension .103
445.1 Exigences générales .103
Annexe A (informative) Notes explicatives relatives à 442.1 et 442.2. 104
Annexe B (informative) Guide pour l'application d'une situation contrôlée des
surtensions par des parafoudres dans les lignes aériennes .106
Annexe C (normative) Détermination de la longueur conventionnelle, d .108
Bibliographie.110
Figure 44.A1 – Schéma représentatif des diverses liaisons à la terre dans le poste de
transformation et dans l’installation BT et des surtensions afférentes en cas de défaut.65
Figure 44.A2 – Tension de défaut acceptable due à un défaut en HT.67
Figure 44.R1 – Conducteur d’accompagnement de renfort d’écran pour assurer un
réseau commun d’équipotentialité.76
Figure 44.R2 – Exemple de conducteur d’accompagnement ou de substitution en
schéma TT.76
Figure 44.R3A − Elimination des courants de conducteur neutre dans une structure
alimentée en schéma TN-S depuis l’origine du réseau public jusques et y compris les
circuits terminaux à l’intérieur du bâtiment .78
Figure 44.R3B − Elimination des courants de conducteur neutre dans une structure
alimentée en schéma TN-S en aval du transformateur d’alimentation privé du
consommateur .79
Figure 44.R4 – Schéma TN-C-S dans un bâtiment existant.80
Figure 44.R5 – Schéma TT dans un bâtiment .81
Figure 44.R6 – Schéma IT dans un bâtiment .82
– 58 – 60364-4-44 © CEI:2007
Figure 44.R7A – Schéma TN alimenté par plusieurs sources avec connexion multiple
non appropriée entre le PEN et la terre.83
Figure 44.R7B – Schéma TN alimenté par plusieurs sources avec points étoiles
connectés à un seul et même point de terre.84
Figure 44.R8 – Schéma TT alimenté par plusieurs sources avec points étoiles
connectés à un seul et même point de terre.85
Figure 44.R9A – Alimentation triphasée avec commutateur à 4 pôles .86
Figure 44.R9B – Ecoulement de courant dans le conducteur neutre dans une
alimentation triphasée avec commutateur à 3 pôles non approprié.87
Figure 44.R9C – Alimentation monophasée avec commutateur à 2 pôles.88
Figure 44.R10 – Exemple de pénétration de câbles armés et de canalisations
métalliques dans un bâtiment .89
Figure 44.R11 − Illustration des mesures décrites par le présent article dans un
bâtiment existant .91
Figure 44.R12 – Prises de terre interconnectées.92
Figure 44.R13 – Exemples de conducteurs de protection en étoile.93
Figure 44.R14 – Exemple de réseau à mailles multiples en étoile .94
Figure 44.R15 – Exemple de réseau en étoile à maillage commun.95
Figure 44.R16 – Exemple de réseau équipotentiel dans des structures sans systèmes
de protection contre la foudre .96
Figure 44.R17A – Distances de séparation entre circuits de puissance et de
communication pour des longueurs de câbles ≤ 35 m .99
Figure 44.R17B – Distances de séparation entre circuits de puissance et de
communication pour des longueurs de câbles > 35 m .99
Figure 44.R18 – Séparation des câbles d’une canalisation . 100
Figure 44.R19 – Disposition de câbles dans un chemin de câbles métallique.101
Figure 44.R20 – Exemple de réalisation de la continuité de supports métalliques .102
Figure 44.R21 – Emplacement des câbles dans des éléments de construction
métallique .
Figure 44.R22 – Interruption de sections métalliques.103
Figure 44.Q – Exemples d’utilisation de d , d et d pour la détermination de d .109
1 2 3
Tableau 44.A1 – Contraintes de tension et tensions de défaut industrielles dans le
réseau BT.66
Tableau 44.A2 – Contraintes à fréquence industrielle admissibles .68
Tableau 44.B – Tension assignée de tenue aux chocs prescrite pour les matériels.73
Tableau B.1 – Différentes possibilités de schéma IT . 107
60364-4-44 © CEI:2007 – 59 –
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
______________
INSTALLATIONS ÉLECTRIQUES À BASSE TENSION –
Partie 4-44: Protection pour assurer la sécurité –
Protection contre les perturbations de tension
et les perturbations électromagnétiques
AVANT-PROPOS
1) La Commission Electrotechnique Internationale (CEI) est une organisation mondiale de normalisation
composée de l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI a
pour objet de favoriser la coopération internationale pour toutes les questions de normalisation dans les
domaines de l'électricité et de l'électronique. A cet effet, la CEI – entre autres activités – publie des Normes
internationales, des Spécifications techniques, des Rapports techniques, des Spécifications accessibles au
public (PAS) et des Guides (ci-après dénommés "Publication(s) de la CEI"). Leur élaboration est confiée à des
comités d'études, aux travaux desquels tout Comité national intéressé par le sujet traité peut participer. Les
organisations internationales, gouvernementales et non gouvernementales, en liaison avec la CEI, participent
également aux travaux. La CEI collabore étroitement avec l'Organisation Internationale de Normalisation (ISO),
selon des conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de la CEI concernant les questions techniques représentent, dans la mesure
du possible, un accord international sur les sujets étudiés, étant donné que les Comités nationaux de la CEI
intéressés sont représentés dans chaque comité d’études.
3) Les Publications de la CEI se présentent sous la forme de recommandations internationales et sont agréées
comme telles par les Comités nationaux de la CEI. Tous les efforts raisonnables sont entrepris afin que la CEI
s'assure de l'exactitude du contenu technique de ses publications; la CEI ne peut pas être tenue responsable
de l'éventuelle mauvaise utilisation ou interprétation qui en est faite par un quelconque utilisateur final.
4) Dans le but d'encourager l'uniformité internationale, les Comités nationaux de la CEI s'engagent, dans toute la
mesure possible, à appliquer de façon transparente les Publications de la CEI dans leurs publications
nationales et régionales. Toutes divergences entre toutes Publications de la CEI et toutes publications
nationales ou régionales correspondantes doivent être indiquées en termes clairs dans ces dernières.
5) La CEI n’a prévu aucune procédure de marquage valant indication d’approbation et n'engage pas sa
responsabilité pour les équipements déclarés conformes à une de ses Publications.
6) Tous les utilisateurs doivent s'assurer qu'ils sont en possession de la dernière édition de cette publication.
7) Aucune responsabilité ne doit être imputée à la CEI, à ses administrateurs, employés, auxiliaires ou
mandataires, y compris ses experts particuliers et les membres de ses comités d'études et des Comités
nationaux de la CEI, pour tout préjudice causé en cas de dommages corporels et matériels, ou de tout autre
dommage de quelque nature que ce soit, directe ou indirecte, ou pour supporter les coûts (y compris les frais
de justice) et les dépenses découlant de la publication ou de l'utilisation de cette Publication de la CEI ou de
toute autre Publication de la CEI, ou au crédit qui lui est accordé.
8) L'attention est attirée sur les références normatives citées dans cette publication. L'utilisation de publications
référencées est obligatoire pour une application correcte de la présente publication.
9) L’attention est attirée sur le fait que certains des éléments de la présente Publication de la CEI peuvent faire
l’objet de droits de propriété intellectuelle ou de droits analogues. La CEI ne saurait être tenue pour
responsable de ne pas avoir identifié de tels droits de propriété et de ne pas avoir signalé leur existence.
La Norme internationale CEI 60364-4-44 a été établie par le comité d’études 64 de la CEI:
Installations électriques et protection contre les chocs électriques.
Cette deuxième édition de la CEI 60364-4-44 annule et remplace la première édition parue en
2001, l’amendement 1 (2003) et l’amendement 2 (2006).
Le document 64/1600/FDIS, circulé comme Amendement 3 auprès des Comités nationaux de
la CEI, a conduit à la publication de la nouvelle édition.
– 60 – 60364-4-44 © CEI:2007
Le texte de cette norme est basé sur la première édition, son Amendement 1, son
Amendement 2 et sur les documents suivants:
FDIS Rapport de vote
64/1600/FDIS 64/1609/RVD
Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à l'approbation de cette norme.
Cette publication a été rédigée selon les Directives ISO/CEI, Partie 2.
Une liste de toutes les parties de la série CEI 60364, présentées sous le titre général
Installations éléctriques à basse tension, peut être consultée sur le site web de la CEI.
Les normes futures de cette série porteront dorénavant le nouveau titre général cité ci-
dessus. Le titre des normes existant déjà sera mis à jour lors d’une prochaine édition.
Le comité a décidé que le contenu de cette publication ne sera pas modifié avant la date de
maintenance indiquée sur le site web de la CEI sous «http://webstore.iec.ch» dans les
données relatives à la publication recherchée. A cette date, la publication sera
• reconduite;
• supprimée;
• remplacée par une édition révisée, ou
• amendée.
60364-4-44 © CEI:2007 – 61 –
INTRODUCTION
La Partie 4-44 de la CEI 60364 traite de la protection des installations électriques et des
dispositions contre les perturbations de tension et les interférences électromagnétiques.
Les exigences sont traitées dans les quatre articles suivants:
Article 442: Protection des installations électriques à basse tension contre les surtensions
temporaires dues à des défauts à la terre dans le réseau haute tension et dues
à des défauts dans le réseau basse tension;
Article 443: Protection contre les surtensions d’origine atmosphérique ou dues à des
manœuvres;
Article 444: Dispositions contre les influences électromagnétiques.
Article 445: Protection contre les baisses de tension
– 62 – 60364-4-44 © CEI:2007
INSTALLATIONS ÉLECTRIQUES À BASSE TENSION –
Partie 4-44: Protection pour assurer la sécurité –
Protection contre les perturbations de tension
et les perturbations électromagnétiques
440.1 Domaine d'application
Les règles de la présente Partie de la CEI 60364 sont destinées à donner des exigences pour
la sécurité des installations électriques en cas de perturbations de tension ou d’influences
électromagnétiques dues à des raisons diverses.
Les règles de la présente partie ne s’appliquent pas aux réseaux de distribution d’énergie
public ou à la génération de puissance et à sa transmission (voir le domaine d’application de
la CEI 60364-1) bien que de telles perturbations peuvent être transmises dans ou entre des
installations électriques par ces réseaux.
440.2 Références normatives
Les documents de référence suivants sont indispensables pour l'application du présent
document. Pour les références datées, seule l'édition citée s'applique. Pour les références
non datées, la dernière édition du document de référence s'applique (y compris les éventuels
amendements).
CEI 60038:1983, Tensions normales de la CEI
CEI 60050-604:1987, Vocabulaire Electrotechnique International – Chapitre 604: Production,
transport et distribution de l'énergie électrique – Exploitation
CEI 60364-1, Installations électriques des bâtiments – Partie 1: Principes fondamentaux,
détermination des caractéristiques générales, définitions
CEI 60364-4-41:2005, Installations électriques des bâtiments – Partie 4-41: Protection pour
assurer la sécurité – Protection contre les chocs électriques
CEI 60364-5-54:2002, Installations électriques des bâtiments − Partie 5-54: Choix et mise en
œuvre des matériels électriques − Mises à la terre, conducteurs de protection et conducteurs
d’équipotentialité de protection
CEI 60479-1:2005, Effets du courant sur l'homme et les animaux domestiques – Partie 1:
Aspects généraux
CEI 60664-1:2007, Coordination de l'isolement des matériels dans les systèmes (réseaux) à
basse tension – Partie 1: Principes, exigences et essais
CEI 60950-1, Matériels de traitement de l’information – Sécurité – Partie 1: Exigences
générales
CEI 61000-2-5:1995, Compatibilité électromagnétique (CEM) − Partie 2: Environnement −
Section 5: Classification des environnements électromagnétiques – Publication fondamentale
en CEM
CEI 61000-6-1, Compatibilité électromagnétique (CEM) – Partie 6-1: Normes génériques –
Immunité pour les environnements résidentiels, commerciaux et de l’industrie légère
CEI 61000-6-2, Compatibilité électromagnétique (CEM) – Partie 6-2: Normes génériques –
Immunité pour les environnements industriels
____________
Une troisième édition est à l’étude.
60364-4-44 © CEI:2007 – 63 –
CEI 61000-6-3, Compatibilité électromagnétique (CEM) – Partie 6-3: Normes génériques –
Normes sur l’émission pour les environnements résidentiels, commerciaux et de l’industrie
légère
CEI 61000-6-4, Compatibilité électromagnétique (CEM) – Partie 6-4: Normes génériques –
Normes sur l’émission pour les environnements industriels
CEI 61558-2-1, Sécurité des transformateurs,alimentations, bobines d’inductance et produits
analogues – Partie 2-1: Règles particulières et essais pour transformateurs d’isolement à
enroulements séparés et alimentations incorporant des transformateurs d’isolement à
enroulements séparés pour applications d’ordre général
CEI 61558-2-4, Sécurité des transformateurs, blocs d’alimentation et analogues – Partie 2-4:
Règles particulières pour les transformateurs de séparation des circuits pour usage général
CEI 61558-2-6, Sécurité des transformateurs, blocs d’alimentation et analogues – Partie 2-6:
Règles particulières pour les transformateurs de sécurité pour usage général
CEI 61558-2-15, Sécurité des transformateurs, blocs d’alimentation et analogues – Partie 2-15:
Règles particulières pour les transformateurs de séparation de circuits pour locaux à usages
médicaux
CEI 61643 (toutes les parties), Parafoudres basse tension
CEI 61936-1, Installations électriques en courant alternatif de puissance supérieure à 1 kV -
Partie 1: Règles communes
CEI 62305-1, Protection contre la foudre – Partie 1: Principes généraux
CEI 62305-3, Protection contre la foudre – Partie 3: Dommages physiques sur les structures
et risques humains
CEI 62305-4, Protection contre la foudre – Partie 4: Réseaux de puissance et de
communication dans les structures
441 (Disponible)
442 Protection des installations électriques à basse tension contre les
surtensions temporaires dues à des défauts à la terre dans le réseau
haute tension et dues à des défauts dans le réseau basse tension
442.1 Généralités
Les exigences de cet article sont nécessaires pour assurer la sécurité des installations basse
tension contre:
– un défaut entre la haute tension et la terre dans le poste de transformation alimentant
l’installation basse tension;
– la perte du point neutre en basse tension;
– un court-circuit entre phase et neutre;
– un court-circuit entre terre et phase d’un système IT basse tension.
Les exigences pour la mise à la terre du poste sont données dans la CEI 61936-1.
442.1.1 Généralités
L’Article 442 donne des règles pour le concepteur et l’installateur du poste de transformation
et couvre les cas de défauts entre une phase haute tension et la terre d’un poste de
– 64 – 60364-4-44 © CEI:2007
transformation HT/BT. Il est nécessaire d’avoir les informations suivantes sur le réseau à
haute tension:
– le type de schéma de mise à la terre;
– la valeur maximale du courant de défaut;
– la résistance de la prise de terre.
Les paragraphes suivants considèrent quatre cas comme proposé en 442.1, qui
généralement, génèrent les surtensions temporaires les plus défavorables telles que définies
dans la CEI 60050-604 :
– défaut entre le réseau haute tension et la terre (voir 442.2);
– rupture du neutre dans le réseau à basse tension (voir 442.3);
– mise à la terre accidentelle dans un schéma IT BT (voir 442.4);
– court-circuit dans l’installation à basse tension (voir 442.5).
442.1.2 Symboles
Dans l’Article 442, les symboles suivants sont utilisés (voir la Figure 44.A1):
I partie du courant de défaut à la terre dans l'installation à haute tension qui s'écoule
E
par la prise de terre des masses du poste de transformation.
R résistance de la prise de terre du poste de transformation.
E
R résistance de la prise de terre des masses des matériels du réseau à basse tension
A
R résistance de la prise de terre du neutre du réseau à basse tension dans lequel les
B
mises à la terre du transformateur et celle du neutre sont électriquement
indépendantes
U pour les schémas TN et TT: tension nominal alternative efficace entre phase et terre
o
en schéma IT: tension nominale alternative entre phase et neutre ou conducteur de
point milieu, selon configuration
U tension de défaut à fréquence industrielle dans l'installation à basse tension entre les
f
masses et la terre lors du défaut
U contrainte à fréquence industrielle de tension entre les conducteurs actifs et les
masses des matériels électriques à basse tension situées dans le poste de
transformation lors du défaut
U contrainte à fréquence industrielle de tension entre les conducteurs actifs et les
masses des matériels électriques à basse tension de l’installation électrique à basse
tension lors du défaut
NOTE 1 La contrainte à fréquence industrielle (U et U ) est la tension apparaissant à travers l’isolation des
1 2
matériels à basse tension et à travers les parafoudres connectés à l’installation basse tension.
Les symboles complémentaires suivants sont utilisés en schéma IT dans lequel les masses
des matériels électriques à basse tension sont connectées à une prise de terre
électriquement indépendante de celle du poste de transformation.
I courant de défaut s’écoulant dans la prise de terre des masses des matériels de
h
l’installation à basse tension lors du défaut si un défaut est présent en haute tension
et avec un premier défaut en basse tension (voir Tableau 44.A1).
60364-4-44 © CEI:2007 – 65 –
I le courant de défaut conforme à 411.6.2 s’écoulant dans la prise de terre des masses
d
des matériels de l’installation à basse tension avec un premier défaut en basse
tension (voir Tableau 44.A1).
Z l’impédance (par exemple, impédance interne « IMD », impédance du neutre artificiel)
entre le réseau à basse tension et la prise de terre
NOTE 2 Une prise de terre peut être considérée comme électriquement indépendante d’une autre, si une
élévation du potentiel due à une autre prise n’entraîne pas d’élévation dangereuse de potentiel dans cette prise de
terre. Voir CEI 61936-1.
442.2 Surtensions dans un réseau BT en cas de défaut HT
En cas de défaut à la terre dans la partie HT du poste, les types de surtensions suivantes
peuvent affecter l’installation BT:
• tension de défaut à fréquence industrielle (U );
f
• contraintes de tension industrielles (U et U ).
1 2
Le Tableau 44.A1 donne les méthodes appropriées de calcul des diverses surtensions.
NOTE 1 Le Tableau 44.A1 traite uniquement des schémas IT ayant un point neutre. Pour les schémas IT n'ayant
pas de point neutre, il convient d’ajuster la formule en conséquence.
Poste de U Installation BT
U
transformation
HT BT
L1
L2
L3
ou N ou PEN
Z
I R R R U
E E B A f
IEC 1379/07
Figure 44.A1 – Schéma représentatif des diverses liaisons à la terre dans le poste de
transformation et dans l’installation BT et des surtensions afférentes en cas de défaut
Si les prises de terre HT et BT sont proches l’une de l’autre, deux méthodes sont
actuellement utilisées:
– interconnexion de toutes les prises de terre HT (R ) et BT (R );
E B
– séparation des prises de terre HT (R ) et BT (R ).
E B
– 66 – 60364-4-44 © CEI:2007
La méthode générale utilisée est l’interconnexion. Les prises de terre HT et BT doivent être
interconnectées si le réseau BT est complètement confiné dans la zone de la prise de terre
HT( voir la CEI 61936-1).
NOTE 2 Les détails des divers schémas de liaisons à la terre (TN, TT et IT) sont indiqués dans la CEI 60364-1.
Tableau 44.A1 – Contraintes de tension et tensions de défaut industrielles
dans le réseau BT
Schémas
Types de prise de
de U U U
1 2 f
terre
ditribution
R et R connectées U *) 0 *)
E B R × I + U
o
E E o
TT
R et R séparées
E B R × I + U U*) 0 *)
E E o o
R et R connectées U *) U *) R × I **)
E B
o o E E
TN
R et R séparées R × I + U U*) 0 *)
E B
E E o o
U *) R × I + U 0 *)
o E E o
R et Z connectées
E
R et R separées
E A
R × I
U × 3 R × I + U × 3
A h
o E E o
U *) U *)
R × I
R et Z connectées o o
E E E
R et R
E A
IT
interconnectées
R × I
U × 3 U × 3
E E
o o
R × I + U U*) 0 *)
E E o o
RE et Z séparées
R et R séparées
E A
R × I
R × I + U × 3 U × 3
A d
E E o o
*) Sans considération particulière.
**) Voir le second paragraphe du 442.2.1.
Au sujet des défauts à la terre dans une installation
NOTE 3 Les exigences pour U et U sont issues des critères de conception de l’isolation des matériels BT vis-à-
1 2
vis des surtensions industrielles temporaires (voir aussi le Tableau 44.A2).
NOTE 4 Dans un réseau où le neutre est connecté à la prise de terre du poste de transformation, de telles
surtensions industrielles temporaires sont susceptibles d’apparaître à travers l’isolation qui n’est pas dans une
enveloppe mise à la terre lorsque le matériel est à l’extérieur d’un bâtiment.
NOTE 5 En schémas TT et TN, le qualificatif « connecté » ou « séparé » se réfère à la liaison électrique entre RE
et R . En schéma IT, il se réfère à la liaison électrique entre R et Z et à celle entre R et R .
B
E E A
442.2.1 Valeur et durée de la tension de défaut à fréquence industrielle
La valeur et la durée de la tension de défaut U (calculées selon le Tableau 44.A1)
f
apparaissant dans l’installation BT entre les masses et la terre, ne doit pas dépasser les
valeurs données pour U de la courbe de la Figure 44.A2 lors du défaut.
f
Normalement, le conducteur PEN du réseau BT est connecté à la terre en plusieurs points.
Dans ce cas, la valeur globale de la résistance de terre est réduite. Dû à ces multiples
connexions à la terre du PEN, U peut être calculé par la formule suivante:
f
U = 0,5 R × I
f F F
60364-4-44 © CEI:2007 – 67 –
Durée de la tension de défaut
1 200
1 100
1 000
10 100 1 000 10 000
Durée du défaut t (ms)
IEC 1380/07
Figure 44.A2 – Tension de défaut acceptable due à un défaut en HT
NOTE La courbe de la Figure 44.A2 est celle de la CEI 61936-1. En se fondant sur des données de probabilité et
statistiques, cette courbe représente un niveau faible de risque dans le cas le plus défavorable lorsque le neutre
BT n’est mis à la terre qu’au niveau du poste de transformation. Des directives concernant d’autres situations sont
fournies dans la CEI 61936-1.
442.2.2 Valeur et durée des contraintes à fréquence industrielle
La valeur et la durée des contraintes à fréquence industrielle (U et U ) calculées selon le
1 2
Tableau 44.A1, apparaissant dans les matériels de l’installation BT dues à un défaut HT ne
doit pas dépasser les valeurs données dans le Tableau 44.A2.
Tension de défaut U (V)
f
– 68 – 60364-4-44 © CEI:2007
Tableau 44.A2 – Contraintes à fréquence industrielle admissibles
Contraintes de tension admissibles sur les matériels d'une
Durée du défaut HT
installation à basse tension
t
U
>5 s + 250 V
U
o
≤5 s U + 1 200 V
o
Dans les systèmes sans conducteur neutre, U doit être la tension entre phase.
o
NOTE 1 La première ligne du tableau est relative aux systèmes d'alimentation haute tension ayant des temps
de coupure longs, par exemple les systèmes à neutre isolé ou mis à la terre. La seconde ligne est relative aux
systèmes d'alimentation HT ayant des temps de coupure courts, par exemple les systèmes mis à la terre
directement. Les deux lignes ensemble sont des critères de conception à prendre en considération quant à
l'isolement des matériels à basse tension pour les surtensions temporaires, voir la CEI 60664-1.
NOTE 2 Dans un réseau où le neutre est connecté à la prise de terre du poste de transformation, de telles
surtensions industrielles temporaires sont susceptibles d’apparaître à travers l’isolation qui n’est pas dans une
enveloppe mise à la terre lorsque le matériel est à l’extérieur d’un bâtiment.
442.2.3 Exigences pour le calcul des limites
Dans le cas où cela est requis dans le Tableau 44.A1, la limite de contrainte de tension à
fréquence industrielle ne doit pas être supérieure à celle du Tableau 44.A2.
Dans le cas où cela est requis dans le Tableau 44.A1, la limite de tension de défaut à
fréquence industrielle ne doit pas être supérieure à celle de la Figure 44.A2.
Les exigences du 442.2.1 et 442.2.2 correspondent aux exigences d’une installation recevant
une alimentation basse tension depuis un réseau de distribution public d’électricité.
Pour satisfaire aux exigences ci-dessus, une coordination entre le gestionnaire du réseau HT
et l’installateur du réseau BT est nécessaire. La conformité aux exigences ci-dessus est de la
responsabilité de l’installateur/propriétaire/gestionnaire du poste de transformation lequel doit
aussi satisfaire aux exigences de la CEI 61936-1. C’est pourquoi le calcul de U , U et U
1 2 f
n’est normalement pas nécessaire pour l’installateur du réseau BT.
Des dispositions possibles pour satisfaire aux exigences ci-dessus sont par exemple:
• la séparation des prises de terre HT et BT;
• le changement du schéma des liaisons à la terre en BT;
• la réduction de la valeur de la prise de terre R .
E
442.3 Contraintes de tension à fréquence industrielle en cas de rupture du
conducteur neutre en schémas TN et en schéma TT
L'attention doit se porter sur le fait qu'en cas de rupture du conducteur neutre d’un système
polyphasé, les isolations principale, double et renforcée ainsi que les matériels dimensionnés
pour la tension entre conducteurs de phase et le conducteur neutre peuvent être soumis
temporairement à la tension entre phases. La contrainte de tension peut atteindre U = √3 U .
o
442.4 Contraintes de tension à fréquence industrielle en cas de défaut à la terre en
schéma IT avec neutre distribué
L'attention doit se porter sur le fait qu'en cas de défaut à la terre d'un conducteur de phase en
schéma IT, les isolations ou les matériels dimensionnés pour la tension simple peuvent être
soumis temporairement à la tension composée. La contrainte de tension peut atteindre U = √3
U
o.
60364-4-44 © CEI:2007 – 69 –
442.5 Contraintes de tension à fréquence industrielle en cas de court-circuit entre
phase et neutre
L'attention doit se porter sur le fait qu'en cas de court-circuit entre phase et neutre dans
l’installation à basse tension, les contraintes de tension entre les autres conducteurs de
phase et le neutre peuvent atteindre la valeur de 1,45 x U pendant une durée non supérieure
à 5 s.
443 Protection contre les surtensions d’origine atmosphérique ou dues à
des manœuvres
443.1 Généralités
Le présent article de la CEI 60364-4-44 traite de la protection des installations électriques
contre les surtensions transitoires d'origine atmosphérique transmises par les réseaux de
distribution et contre les surtensions de manoeuvre.
Généralement, les surtensions de manœuvre sont plus faibles que les surtensions d'origine
atmosphérique et c’est pourquoi les exigences relatives à la protection contre les surtensions
d’origine atmosphérique sont suffisantes pour la protection contre les surtensions de
manœuvre.
NOTE 1 Des mesures statistiques ont montré qu’il existe un risque faible de niveau de surtensions de manœuvre
supérieur à la catégorie de surtensions II. Voir 443.2.
Les surtensions qui peuvent apparaître à l'origine d'une installation, le niveau kéraunique
présumé, l'emplacement et les caractéristiques des dispositifs de protection contre les
surtensions doivent être pris en considération, de sorte que les probabilités d'incidents dus à
des contraintes de surtension soient réduites à un niveau acceptable pour la sécurité des
personnes et des biens, ainsi que pour la continuité de service souhaitée.
Les valeurs de surtensions transitoires dépendent de la nature du réseau d'alimentation
(souterrain ou aérien) et de la présence éventuelle de dispositifs de protection contre les
surtensions en amont de l'origine de l'installation et du niveau de tension du réseau
d'alimentation.
Le présent article fournit des indications lorsque la protection contre les surtensions est
obtenue par la situation naturelle ou assurée par la situation contrôlée. Si la protection
conformément à cet article n'est pas prévue, la coordination de l'isolement n'est pas assurée
et le risque dû aux surtensions doit être estimé.
Le présent article ne s'applique pas en cas de surtensions dues à un coup de foudre direct ou
proche. Pour la protection contre les surtensions transitoires dues à un coup de foudre direct,
la CEI 62305-1, la CEI 62305-3, la CEI 62305-4 et la série CEI 61643 s'appliquent. Le présent
article ne s'applique pas aux surtensions sur les systèmes de transmissions de données.
NOTE 2 En ce qui concerne les surtensions transitoires d'origine atmosphérique, aucune distinction n'est faite
entre les installations mises à la terre et celles non mises à la terre.
NOTE 3 Les surtensions de manoeuvre créées en dehors de l'installation et transmises par le réseau
d'alimentation sont à l'étude.
NOTE 4 Le risque dû à des surtensions est traité dans la CEI 61662 et son amendement 1.
– 70 – 60364-4-44 © CEI:2007
443.2 Classification des tensions de tenue aux chocs (catégories de surtensions)
443.2.1 Objet de la classification des tensions de tenue aux chocs
(catégories de surtensions)
NOTE 1 Les catégories de surtensions sont définies pour les installations électriques comme l’objet de la
coordination de l’isolement et d’une classification des matériels vis-à-vis des tensions de tenue aux chocs, voir
Tableau 44B.
NOTE 2 La tension assignée de tenue aux chocs est une tension de choc fixée par le constructeur pour les
matériels ou à une partie de ceux-ci, caractérisant la tenue spécifiée de leur isolation contre les surtensions
(conformément à 3.9.2 de la CEI 60664-1).
Le concept de tension de tenue aux chocs (catégorie de surtension) est utilisé pour classer
les matériels alimentés directement par le réseau.
Les tensions de tenue aux chocs pour les matériels choisies en fonction de la tension
nominale sont données pour distinguer les divers degrés de disponibilité des matériels en
fonction de la continuité du service et du risque acceptable de défaillance. A l'aide du choix
des matériels dans la série de tensions de tenue aux chocs, une coordination appropriée de
l'isolement peut être obtenue dans l'ensemble de l'installation, réduisant ainsi le risque de
défaillance à un niveau acceptable.
NOTE 3 Les surtensions transitoires transmises par le réseau de distribution ne subissent pas d'atténuation
significative en aval dans la plupart des installations.
443.2.2 Relation entre tensions de tenue aux chocs des matériels et catégories de
surtensions
Les matériels de tension de tenue aux chocs correspondant à la catégorie de surtension IV
sont utilisés à l'origine ou au voisinage de l'origine de l'installation en amont du tableau de
distribution. Les équipements de catégorie IV se caractérisent par un très haut niveau de
tenue aux chocs et assurent le haut niveau de fiabilité tel que requis.
NOTE 1 Des exemples de tels matériels sont les compteurs électriques, les matériels principaux de protection
contre les surintensités et les dispositifs de télémesure.
Les matériels de tension de tenue aux chocs correspondant à la catégorie de surtension III
sont des matériels appartenant à l'installation fixe en aval de et y compris le tableau de
distribution assurant un haut niveau de fiabilité.
NOTE 2 Des exemples de tels matériels sont les armoires de distribution, les disjoncteurs, les canalisations (voir
la CEI 60050-826, définition 826-15-01), comprenant les câbles, les jeux de barres, les boîtes de jonction, les
interrupt
...












Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...