SIST-TS CLC/TS 61850-80-1:2010
(Main)Communication networks and systems for power utility automation - Part 80-1: Guideline to exchanging information from a CDC-based data model using IEC 60870-5-101 or IEC 60870-5-104
Communication networks and systems for power utility automation - Part 80-1: Guideline to exchanging information from a CDC-based data model using IEC 60870-5-101 or IEC 60870-5-104
This technical specification gives a guideline on how to exchange information from a CDCbased data model (for example IEC 61850) using IEC 60870-5-101 or IEC 60870-5-104 between substation(s) and control center(s). Mostly guidelines for functions needed in a substation gateway device are given. The goal of this technical specification is to describe standardized mapping of device-oriented data models (for example IEC 61850) with already defined attributes of CDC's and services (for example IEC 61850-7) onto the already defined ASDU's and services of IEC 60870-5-104 or IEC 60870-5-101. It is not the goal of this technical specification to add any extensions to published standards (for example IEC 61850 or IEC 60870-5-104 or IEC 60870-5-101). After an introduction giving a basic description of the mapping, the mapping of the information model with associated data classes, and the mapping of services are described. Clause 9 shows how the mapped data and services according to the IEC 60870-5-104 and IEC 60870-5-101 protocol are marked (selected) in the interoperability sheet. The scope of this technical specification is to achieve real-time exchange of process information required for operational purposes between a substation using a CDC-based data model (for example IEC 61850) and (a) control centre(s) using a communication link over a wide area network (WAN) compliant to the definitions of IEC 60870-5-101 or IEC 60870-5- 104. The amount of real-time information provided by the substation-gateway device can vary dependent on the operational needs. Actors could be regional and nationwide control centers that receive real-time information in order to monitor and control geographically widespread processes. The described mapping can be used for several fields of application of power utilities, such as substations, hydro and wind power plants, and decentralized energy resources DER. The mapping is based on the definitions of the standard series IEC 61850 Edition 1.0 and IEC 60870-5-104:2006/IEC 60870-5-101:2003. The scope of the mapped IEC 60870-5-104 and IEC 60870-5-101 subset is given in Clause 9. This technical specification focuses mainly on defining rules and functions of a gateway device as a part of the substation. However, the rules and functions are also valid when an IED may optionally be connected directly to a WAN compliant with IEC 60870-5-101 or IEC 60870-5-104 and therefore, the mapping has to be done inside the IED.
Kommunikationsnetze und -systeme für die Automatisierung in der elektrischen Energieversorgung - Teil 80-1: Leitfaden zum Informationsaustausch mit einer Datenbasis, die auf gemeinsamen Datenklassen beruht, mit Hilfe von IEC 60870-5-101 oder IEC 60870-5-104
Komunikacijska omrežja in sistemi za avtomatizacijo porabe električne energije - 80-1. del: Smernica za izmenjavo informacij po podatkovnem modelu na podlagi CDC z uporabo IEC 60870-5-101 ali IEC 60870-5-104
Ta tehnična specifikacija podaja smernico za izmenjavo informacij po podatkovnem modelu na podlagi CDC (na primer IEC 61850) z uporabo IEC 60870-5-101 ali IEC 60870-5-104 med eno ali več razdelilnimi postajami in enim ali več nadzornimi centri. Večinoma so podana navodila za funkcije, ki so potrebne za prehodno napravo razdelilne postaje. Cilj te tehnične specifikacije je opisati standardizirano preslikavanje podatkovnih modelov, usmerjenih na naprave (na primer IEC 61850) z že definiranimi atributi CDC in storitev (na primer IEC 61850-7) na že definirane ASDU in storitve iz IEC 60870-5-104 ali IEC 60870-5-101. Cilj te tehnične specifikacije ni dodati kakršnihkoli razširitev objavljenim standardom (na primer IEC 61850 ali IEC 60870-5-104 ali IEC 60870-5-101). Po uvodu, ki podaja osnovni opis preslikave, sta opisana preslikava informacijskega modela s povezanimi razredi podatkov in preslikava storitev. Klavzula 9 prikazuje, kako so preslikani podatki in storitve v skladu s protokolom IEC 60870-5-104 in IEC 60870-5-101 označeni (izbrani) v medobratovalni preglednici. Področje te tehnične specifikacije je doseči izmenjavo procesnih informacij, potrebnih za operativne namene v realnem času, med razdelilno postajo, ki uporablja podatkovni model osnovan na CDC (na primer IEC 61850) in enim ali več nadzornimi centri, ki uporabljajo komunikacijsko povezavo preko prostranega omrežja (WAN), v skladu z definicijami v IEC 60870-5-101 ali IEC 60870-5- 104. Količina informacij v realnem času, ki jo zagotavlja prehodna naprava razdelilne postaje, se lahko razlikuje glede na operativne potrebe. Akterji so lahko regionalni in nacionalni kontrolni centri, ki prejemajo informacije v realnem času za spremljanje in nadzor geografsko razširjenih procesov. Opisana preslikava se lahko uporablja za več področij uporabe energetske infrastrukture, kot so razdelilne postaje, hidroelektrarne in vetrne elektrarne ter decentralizirani energetski viri. Preslikava je osnovana na definicijah serije standardov IEC 61850 izdaja 1.0 in IEC 60870-5-104:2006/IEC 60870-5-101:2003. Obseg preslikane podmnožice IEC 60870-5-104 in IEC 60870-5-101 je podan v Klavzuli 9. Ta tehnična specifikacija se osredotoča predvsem na definiranje pravil in funkcij prehodne naprave kot dela razdelilne postaje. Vendar pa pravila in funkcije veljajo tudi, kadar je lahko IED po izbiri povezan neposredno z WAN v skladu z IEC 60870-5-101 ali IEC 60870-5-104 in mora zato preslikava biti izvršena znotraj IED.
General Information
Standards Content (Sample)
SLOVENSKI STANDARD
SIST-TS CLC/TS 61850-80-1:2010
01-april-2010
.RPXQLNDFLMVNDRPUHåMDLQVLVWHPL]DDYWRPDWL]DFLMRSRUDEHHOHNWULþQHHQHUJLMH
GHO6PHUQLFD]DL]PHQMDYRLQIRUPDFLMSRSRGDWNRYQHPPRGHOXQDSRGODJL
&'&]XSRUDER,(&DOL,(&
Communication networks and systems for power utility automation - Part 80-1: Guideline
to exchanging information from a CDC-based data model using IEC 60870-5-101 or IEC
60870-5-104
Kommunikationsnetze und -systeme für die Automatisierung in der elektrischen
Energieversorgung - Teil 80-1: Leitfaden zum Informationsaustausch mit einer
Datenbasis, die auf gemeinsamen Datenklassen beruht, mit Hilfe von IEC 60870-5-101
oder IEC 60870-5-104
Ta slovenski standard je istoveten z: CLC/TS 61850-80-1:2010
ICS:
29.240.30 Krmilna oprema za Control equipment for electric
elektroenergetske sisteme power systems
33.200 Daljinsko krmiljenje, daljinske Telecontrol. Telemetering
meritve (telemetrija)
SIST-TS CLC/TS 61850-80-1:2010 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST-TS CLC/TS 61850-80-1:2010SIST-TS CLC/TS 61850-80-1:2010
---------------------- Page: 2 ----------------------
SIST-TS CLC/TS 61850-80-1:2010SIST-TS CLC/TS 61850-80-1:2010
TECHNICAL SPECIFICATION
CLC/TS 61850-80-1
SPÉCIFICATION TECHNIQUE
February 2010
TECHNISCHE SPEZIFIKATION
ICS 33.200
English version
Communication networks and systems for power utility automation -
Part 80-1: Guideline to exchanging information from a CDC-based data
model using IEC 60870-5-101 or IEC 60870-5-104
(IEC/TS 61850-80-1:2008)
Kommunikationsnetze und -systeme für
die Automatisierung in der elektrischen
Energieversorgung -
Teil 80-1: Leitfaden
zum Informationsaustausch
mit einer Datenbasis,
die auf gemeinsamen Datenklassen
beruht, mit Hilfe von IEC 60870-5-101
oder IEC 60870-5-104
(IEC/TS 61850-80-1:2008)
This Technical Specification was approved by CENELEC on 2009-12-11.
CENELEC members are required to announce the existence of this TS in the same way as for an EN and to
make the TS available promptly at national level in an appropriate form. It is permissible to keep conflicting
national standards in force.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus,
the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy,
Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia,
Spain, Sweden, Switzerland and the United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Central Secretariat: Avenue Marnix 17, B - 1000 Brussels
© 2010 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. CLC/TS 61850-80-1:2010 E
---------------------- Page: 3 ----------------------
SIST-TS CLC/TS 61850-80-1:2010SIST-TS CLC/TS 61850-80-1:2010
CLC/TS 61850-80-1:2010 - 2 -
Foreword
This Technical Specification consists of the text of the International Technical Specification
IEC 61850-80-1:2008 prepared by IEC TC 57, Power systems management and associated
information exchange.
It was circulated for voting in accordance with the Internal Regulations, Part 2, Subclause 11.3.3.3 and
was accepted as a CENELEC Technical Specification on 2009-12-11.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN and CENELEC shall not be held responsible for identifying any or all such patent
rights.
The following date was fixed:
– latest date by which the existence of the CLC/TS
has to be announced at national level (doa) 2010-06-11
Annex ZA has been added by CENELEC.
__________
---------------------- Page: 4 ----------------------
SIST-TS CLC/TS 61850-80-1:2010SIST-TS CLC/TS 61850-80-1:2010
- 3 - CLC/TS 61850-80-1:2010
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
NOTE Where an international publication has been modified by common modifications, indicated by (mod), the relevant
EN/HD applies.
Publication Year Title EN/HD Year
IEC 60870-5-3 - Telecontrol equipment and systems EN 60870-5-3 -
Part 5-3: Transmission protocols -
General structure of application data
IEC 60870-5-4 1993 Telecontrol equipment and systems EN 60870-5-4 1993
Part 5-4: Transmission protocols –
Definition and coding of application
information elements
IEC 60870-5-5 1995 Telecontrol equipment and systems EN 60870-5-5 1995
Part 5-5: Transmission protocols -
Basic application functions
IEC 60870-5-101 2003 Telecontrol equipment and systems EN 60870-5-101 2003
Part 5-101: Transmission protocols -
Companion standard for basic telecontrol
tasks
IEC 60870-5-104 2006 Telecontrol equipment and systems EN 60870-5-104 2006
Part 5-101: Transmission protocols -
Network access for IEC 60870-5-101
using standard transport profiles
IEC 61400-25-2 - Wind turbines EN 61400-25-2 -
Part 25-2: Communications for monitoring
and control of wind power plants -
Information models
IEC 61850 Series Communication networks and systems in EN 61850 Series
substations
IEC 61850-6 - Communication networks and systems in EN 61850-6 -
substations
Part 6: Configuration description
language for communication in electrical
substations related to IEDs
---------------------- Page: 5 ----------------------
SIST-TS CLC/TS 61850-80-1:2010SIST-TS CLC/TS 61850-80-1:2010
CLC/TS 61850-80-1:2010 - 4 -
Publication Year Title EN/HD Year
IEC 61850-7-2 2003 Communication networks and systems in EN 61850-7-2 2003
substations
Part 7-2: Basic communication structure
for substation and feeder equipment -
Abstract communication service interface
(ACSI)
IEC 61850-7-3 - Communication networks and systems in EN 61850-7-3 -
substations
Part 7-3: Basic communication structure
for substation and feeder equipment -
Common data classes
IEC 61850-8-1 - Communication networks and systems in EN 61850-8-1 -
substations
Part 8-1: Specific Communication Service
Mapping (SCSM) - Mappings to MMS
(ISO 9506-1 and ISO 9506-2) and to
ISO/IEC 8802-3
57/963/INF - IEC 61850 – Technical issues - -
(www.tissue.iec61850.com)
IEEE 754 2008 Binary floating-point arithmetic - -
RFC 2200 June Internet official protocol standards – - -
1997 Request for comments 2200
---------------------- Page: 6 ----------------------
SIST-TS CLC/TS 61850-80-1:2010SIST-TS CLC/TS 61850-80-1:2010
IEC/TS 61850-80-1
Edition 1.0 2008-12
TECHNICAL
SPECIFICATION
Communication networks and systems for power utility automation –
Part 80-1: Guideline to exchanging information from a CDC-based data model
using IEC 60870-5-101 or IEC 60870-5-104
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
PRICE CODE
XF
ICS 33.200 ISBN 2-8318-1020-8
® Registered trademark of the International Electrotechnical Commission
---------------------- Page: 7 ----------------------
SIST-TS CLC/TS 61850-80-1:2010SIST-TS CLC/TS 61850-80-1:2010
– 2 – TS 61850-80-1 © IEC:2008(E)
CONTENTS
FOREWORD.6
1 Scope and object.8
2 Normative references .8
3 Abbreviated terms .9
4 The mapping architecture .10
5 Conceptual architectures and associated use cases .11
5.1 Conceptual architecture of a gateway device.11
5.2 Conceptual architecture of an IED directly connected to a WAN (optional) .15
6 Mapping of a device-oriented information model to IEC 60870-5-104 or
IEC 60870-5-101 .16
6.1 General .16
6.2 Mapping of a device-oriented information model reference .16
6.3 Logical device class mapping .17
6.4 Logical node class mapping .17
7 Mapping of the common data classes (CDC) .17
7.1 List of CDC, type Identifications and corresponding mappings for IEC 61850 .17
7.2 CDC single point status (SPS).20
7.3 CDC double point status (DPS) .20
7.4 CDC integer status (INS).21
7.5 CDC protection activated information (ACT) .23
7.6 CDC directional protection activation information (ACD) .25
7.7 CDC Security violation counting (SEC) .27
7.8 CDC binary counter reading (BCR).28
7.9 CDC measured value (MV) .29
7.10 CDC complex measured value (CMV).30
7.11 CDC Phase to ground related measured values of a three-phase system
(WYE) .32
7.12 CDC phase to phase measured values of a three phase system (DEL).32
7.13 CDC sequence (SEQ) .33
7.14 CDC harmonic value (HMV).34
7.15 CDC harmonic value for WYE (HWYE) .35
7.16 CDC harmonic value for DEL (HDEL) .35
7.17 CDC controllable single point (SPC) .36
7.18 CDC controllable double point (DPC) .38
7.19 CDC controllable integer status (INC).40
7.20 CDC binary controlled step position information (BSC) .42
7.21 CDC integer-controlled step position information (ISC).44
7.22 CDC controllable analogue set point information (APC) .46
7.23 CDC Single point setting (SPG).47
7.24 CDC integer status setting (ING) .48
7.25 CDC analogue settings (ASG) .48
8 Mapping of services.48
8.1 List of service models and corresponding mappings .48
8.2 Server class mapping .50
8.3 Association class mapping .50
8.4 Logical node class mapping .51
8.5 Data class mapping.52
---------------------- Page: 8 ----------------------
SIST-TS CLC/TS 61850-80-1:2010SIST-TS CLC/TS 61850-80-1:2010
TS 61850-80-1 © IEC:2008(E) – 3 –
8.6 Setting group class mapping .53
8.7 Report control block class mapping .54
8.8 Control class mapping .54
9 Protocol stack selections for IEC 60870-5-101 and IEC 60870-5-104 .76
9.1 General .76
9.2 Structure of application data.76
9.3 IEC 60870-5 interoperability .77
Annex A (informative) Use of SCL (substation configuration language) to include
IEC 60870-5-101 or IEC 60870-5-104 information.104
Figure 1 – Conceptual architecture of a gateway device .11
Figure 2 – Use case a) for a gateway device.12
Figure 3 – Use case b) for a gateway device.13
Figure 4 – Use case c) for a gateway device.14
Figure 5 – Conceptual architecture of an IED.15
Figure 6 – Mapping architecture (conceptual) .17
Figure 7 – Direct control with normal security with status update – positive case
applied to gateway device.55
Figure 8 – Direct control with normal security with status update – positive case
applied to IED .56
Figure 9 – Direct control with normal security in general – negative case a) applied to
gateway device .56
Figure 10 – Direct control with normal security in general – negative case a) applied to IED.57
Figure 11 – Direct control with normal security in general – negative case b) applied to
gateway device .57
Figure 12 – Direct control with normal security in general – negative case b) applied to IED.58
Figure 13 – Direct control with normal security with status update – negative case c)
applied to gateway device.58
Figure 14 – Direct control with normal security with status update – negative case c)
applied to IED .59
Figure 15 – Direct control with normal security without status update – positive case
applied to gateway device.59
Figure 16 – Direct control with normal security without status update – positive case
applied to IED .60
Figure 17 – Direct control with enhanced security – positive case applied to gateway
device.62
Figure 18 – Direct control with enhanced security – positive case applied to IED .63
Figure 19 – Direct control with enhanced security – negative case c) applied to
gateway device .64
Figure 20 – Direct control with enhanced security – negative case c) applied to IED.64
Figure 21 – Direct control with enhanced security – negative case d) applied to
gateway device .65
Figure 22 – Direct control with enhanced security – negative case d) applied to IED.65
Figure 23 – SBOw control – positive case applied to gateway device.67
Figure 24 – SBOw control – positive case applied to IED .67
Figure 25 – SBOw control – negative case a) applied to gateway device .68
Figure 26 – SBOw control – negative case a) applied to IED.68
---------------------- Page: 9 ----------------------
SIST-TS CLC/TS 61850-80-1:2010SIST-TS CLC/TS 61850-80-1:2010
– 4 – TS 61850-80-1 © IEC:2008(E)
Figure 27 – SBOw control – negative case b) applied to gateway device .69
Figure 28 – SBOw control – negative case b) applied to IED.69
Figure 29 – SBOw control – negative case c) applied to gateway device.70
Figure 30 – SBOw control – negative case c) applied to IED.70
Figure 31 – SBO with enhanced security – positive case applied to gateway device .71
Figure 32 – SBO with enhanced security – positive case applied to IED .72
Figure 33 – SBO with enhanced security – negative case a) applied to gateway device .72
Figure 34 – SBO with enhanced security – negative case a) applied to IED .73
Figure 35 – SBO with enhanced security – negative case b) applied to gateway device .73
Figure 36 – SBO with enhanced security – negative case b) applied to IED .74
Table 1 – Mapping structure CDC onto ASDU type .18
Table 2 – CDC: Single point status (SPS) .20
Table 3 – CDC: Single point status (SPS) mapping.20
Table 4 – CDC: Double point status (DPS).20
Table 5 – CDC: Double point status (DPS) mapping .21
Table 6 – CDC: Integer status (INS).21
Table 7 – CDC: Integer status (INS) mapping .22
Table 8 – CDC: Protection activated information (ACT).23
Table 9 – CDC: Protection activated information (ACT) mapping .24
Table 10 – CDC: Protection activated information (ACD) .25
Table 11 – CDC: Directional protection activated information (ACD) mapping .26
Table 12 – CDC: Security violation counting (SEC) .27
Table 13 – CDC: Security violation counting (SEC) mapping.27
Table 14 – CDC: Binary counter reading (BCR) .28
Table 15 – CDC: Binary counter reading (BCR) mapping .28
Table 16 – CDC: Measured value (MV) .29
Table 17 – CDC: Measured value (MV) mapping.29
Table 18 – CDC: Complex measured value (CMV) .30
Table 19 – CDC: Complex measured value (CMV) mapping.31
Table 20 – CDC: Phase to ground related measured values of a three-phase system
(WYE).32
Table 21 – CDC: Phase to phase measured values of a three phase system (DEL) .33
Table 22 – CDC: Sequence (SEQ) .33
Table 23 – CDC: Harmonic value (HMV) .34
Table 24 – CDC: Harmonic value (HMV) mapping.34
Table 25 – CDC: Harmonic value for WYE (HWYE).35
Table 26 – CDC: Harmonic value for DEL (HDEL).35
Table 27 – CDC: Controllable single point (SPC) .36
Table 28 – CDC: Controllable single point (SPC) mapping .37
Table 29 – CDC: Controllable double point (DPC).38
Table 30 – CDC: Controllable double point (DPC) mapping.39
Table 31 – CDC: Controllable integer status (INC) .40
---------------------- Page: 10 ----------------------
SIST-TS CLC/TS 61850-80-1:2010SIST-TS CLC/TS 61850-80-1:2010
TS 61850-80-1 © IEC:2008(E) – 5 –
Table 32 – CDC: Controllable integer status (INC) mapping.41
Table 33 – CDC: Binary controlled step position information (BSC).42
Table 34 – CDC: Binary controlled step position information (BSC) mapping of data
attributes of the functional constraint ST .42
Table 35 – CDC: Binary controlled step position information (BSC) mapping of data
attributes of the functional constraint CO .43
Table 36 – CDC: Integer-controlled step position information (ISC).44
Table 37 – CDC: Integer-controlled step position information (ISC) mapping .45
Table 38 – CDC: Controllable analogue set point information (APC) .46
Table 39 – CDC: Controllable analogue set point information (APC) mapping of data
attributes of the functional constraint MX .46
Table 40 – CDC: Controllable analogue set point information (APC) mapping of data
attributes of the functional constraint SP.47
Table 41 – CDC: Single point setting (SPG).47
Table 42 – CDC: Integer status setting (ING) .48
Table 43 – CDC: Analogue settings (ASG).48
Table 44 – Services requiring client/server communication profile.49
Table 45 – Server services mapping .50
Table 46 – Association services mapping.50
Table 47 – Logical nodes services mapping .51
Table 48 – Data services mapping .52
Table 49 – Setting group services mapping.53
Table 50 – Report control block services mapping .54
Table 51 – Direct control with normal security services mapping.61
Table 52 – Direct control with enhanced security services mapping .66
Table 53 – SBO control with enhanced security services mapping .74
Table A.1 – Extension of the “P” element types to hold IEC 60870-5-101 information . 133
Table A.2 – Extension of the “P” element types to hold IEC 60870-5-104 information . 135
Table A.3 – Extension of the “P” element types using redundancy groups. 136
---------------------- Page: 11 ----------------------
SIST-TS CLC/TS 61850-80-1:2010SIST-TS CLC/TS 61850-80-1:2010
– 6 – TS 61850-80-1 © IEC:2008(E)
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
COMMUNICATION NETWORKS AND
SYSTEMS FOR POWER UTILITY AUTOMATION –
Part 80-1: Guideline to exchanging information from a CDC-
based data model using IEC 60870-5-101 or IEC 60870-5-104
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
The main task of IEC technic
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.