Standard Test Method for Measuring the Field Performance of Commercial Kitchen Ventilation Systems

SIGNIFICANCE AND USE
5.1 Successful kitchen exhaust hood performance requires the complete capture and containment of the effluent plume along the hood’s entire perimeter. Any effluent leakage moving beyond 3 in. from the hood face will be deemed as having escaped from the hood, even if it may appear to be have been drawn back into the hood. If effluent spills from the hood, hot and greasy kitchens may be the result and the cause of the performance failure needs to be determined and corrected. Oftentimes, the exhaust flow rate needs to be increased to achieve proper hood performance for particular field conditions. As a result, the supply air to the kitchen will need to be increased to maintain the air balance. However, drafty room conditions due to incorrectly placed supply diffusers, cross drafts from windows and doors, return and supply at opposite ends of the kitchen, etc. could also severely degrade hood performance. Incorrectly designed supply systems may not be corrected by increasing the exhaust rate and could be corrected in a much more efficient and economical manner, such as by replacing a 4-way diffuser with a 3-way diffuser directed away from the hood. Likewise, if the plume is strongly captured, the hood may be over-exhausting and reducing the exhaust rate could be considered, along with a corresponding reduction of room supply air to maintain the building’s air balance.  
5.2 An appropriate airflow balance ensures adequate replacement air for the necessary exhaust conditions and allows the desired air pressure distribution to be maintained.  
5.3 Negative air pressure in the kitchen with respect to the adjacent indoor spaces ensures that the air flow is from these spaces into the kitchen so that odors and cooking effluent are contained within the kitchen. However, too great a pressure imbalance will severely degrade hood performance by creating a wind tunnel effect. Negative air pressure in the dining area with respect to the outside is usually an indication that the su...
SCOPE
1.1 This test method can be used to measure and validate successful design, installation and commissioning of commercial kitchen HVAC and makeup air systems for specific installations.  
1.2 This test method field evaluates commercial kitchen ventilation system airflows and pressures.  
1.3 This test method field evaluates visual hood capture and containment performance.  
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are for information only.  
1.5 The data generated is specific to the field conditions as installed.  
1.6 This test method may involve hazardous materials, gasses (for example, CO) operations, and equipment. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.  
1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

General Information

Status
Historical
Publication Date
31-Mar-2017
Current Stage
Ref Project

Buy Standard

Standard
ASTM F2975-12(2017) - Standard Test Method for Measuring the Field Performance of Commercial Kitchen Ventilation Systems
English language
13 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM F2975-12(2017) - Standard Test Method for Measuring the Field Performance of Commercial Kitchen Ventilation Systems
English language
13 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: F2975 − 12 (Reapproved 2017) An American National Standard
Standard Test Method for
Measuring the Field Performance of Commercial Kitchen
Ventilation Systems
This standard is issued under the fixed designation F2975; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope mance of Commercial Kitchen Exhaust Ventilation Sys-
tems
1.1 This test method can be used to measure and validate
2.2 Other Standards:
successful design, installation and commissioning of commer-
ANSI/ASHRAE Standard 111-2008 Measurement, Testing,
cial kitchen HVAC and makeup air systems for specific
Adjusting and Balancing of Building HVAC Systems
installations.
ANSI/ASHRAE Standard 154 Ventilation for Commercial
1.2 This test method field evaluates commercial kitchen
Cooking Operations
ventilation system airflows and pressures.
Testing, Adjusting and Balancing, Chapter 37 2007 HVAC
1.3 This test method field evaluates visual hood capture and
Applications Handbook
containment performance.
Kitchen Ventilation, Chapter 31 2007 HVAC Applications
Handbook
1.4 The values stated in inch-pound units are to be regarded
as standard. The values given in parentheses are for informa-
3. Terminology
tion only.
3.1 Definitions:
1.5 The data generated is specific to the field conditions as
3.1.1 airflow rate—volumetric flow rate of air in units of
installed.
3 3
ft /min (cfm) or m /s. When adjusted for standard air density
1.6 This test method may involve hazardous materials,
the flow rate is designated by scfm.
gasses (for example, CO) operations, and equipment. This
3.1.2 appliance—cooking device used in kitchen and pow-
standard does not purport to address all of the safety concerns,
ered by gas, and/or electricity and/or solid fuel.
if any, associated with its use. It is the responsibility of the user
3.1.3 barometric pressure—absolute pressure of the air
of this standard to establish appropriate safety and health
measured by a barometer or absolute pressure measuring
practices and determine the applicability of regulatory limita-
device.
tions prior to use.
1.7 This international standard was developed in accor-
3.1.4 captureandcontainment(C&C)—theabilityofahood
dance with internationally recognized principles on standard-
or other removal device to capture and contain all effluent
ization established in the Decision on Principles for the
generated by the appliances or processes during normal opera-
Development of International Standards, Guides and Recom-
tion.
mendations issued by the World Trade Organization Technical
3.1.4.1 Discussion—For the purpose of this test method
Barriers to Trade (TBT) Committee.
effluent may be simulated as defined in this test method.
3.1.4.2 Discussion—Successful C&C shall be demonstrated
2. Referenced Documents
along the entire perimeter of the hood or removal device.
3.1.4.3 Discussion—Successful C&C may include rising
2.1 ASTM Standards:
effluent that when below the leading edge of the hood may
F1704 Test Method for Capture and Containment Perfor-
extend out no more than 3 in. vertically beyond the leading
edge of the hood and is completely recovered before reaching
This test method is under the jurisdiction of ASTM Committee F26 on Food
the leading edge of the hood or removal device and once inside
Service Equipment and is the direct responsibility of Subcommittee F26.07 on
the hood is completely contained. F1704
Commercial Kitchen Ventilation.
Current edition approved April 1, 2017. Published May 2017. Originally
approved in 2012. Last previous edition approved in 2012 as F2975 – 12. DOI:
10.1520/F2975-12R17. Available fromAmerican National Standards Institute (ANSI), 25 W. 43rd St.,
For referenced ASTM standards, visit the ASTM website, www.astm.org, or 4th Floor, New York, NY 10036, http://www.ansi.org.
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Available from American Society of Heating, Refrigerating, and Air-
Standards volume information, refer to the standard’s Document Summary page on Conditioning Engineers, Inc. (ASHRAE), 1791 Tullie Circle, NE, Atlanta, GA
the ASTM website. 30329, http://www.ashrae.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
F2975 − 12 (2017)
3.1.4.4 Discussion—For backshelf or passover style hoods difference between the total pressure sensed by the central tube
effluentshallnotrisemorethan3in.abovetheexteriorleading and the static pressure sensed by the outer tube.
edge of the hood and shall not extend more than 3 in. beyond
3.1.15 replacement air—outdoor air that is used to replace
the open front or sides of the cooking surface and shall be
air removed from a building through an exhaust system.
completely contained once reaching the hood.
Replacement air may be derived from one or more of the
following: Kitchen Supply, Makeup Air and/or Transfer Air.
3.1.5 differential pressure gauge—instrument that measures
However, the ultimate source of all replacement air is outdoor
pressure difference between the two inlet ports. This can be a
air.
mechanical type such as a Bourdon gauge with an indicator on
a dial face or an electronic type with a digital readout.
3.1.15.1 kitchen supply—air entering a space that contains
hoods and originates from an air-handling device that serves
3.1.6 dry bulb temperature—sensible temperature of air as
both purposes of supplying replacement air as well as space
measured by a shielded thermometer or an electronic tempera-
conditioning. Supply air is generally filtered, fan-forced, and
ture measuring device.
either heated and/or cooled and/or humidified and/ or dehu-
3.1.7 effluent—emissions from cooking, dishwasher or other
midified as necessary to maintain specified space temperature
ventilated processes such as convective hot air, steam, vapor,
and/or humidity conditions.
products of combustion, smoke and/or particulate matter.
3.1.15.2 makeup air (dedicated replacement air)—outdoor
3.1.8 exhaust fan—also called power roof ventilator or
air supplied directly to a compensating hood or to supply air
centrifugal blower. A fan used to exhaust cooking effluent
deviceslocatedintheimmediatevicinityofthehoodtoreplace
including, grease, smoke, steam, heat, and/or vapor collected
air being exhausted through the hood. Makeup air is generally
by a hood. The majority of these fans have a centrifugal fan
filtered and fan-forced, and it may be heated and/or cooled
wheel.
depending on the requirements of the application. Makeup air
3.1.9 exhaust hood—a device designed to capture and con- may be delivered through outlets integral to the exhaust hood
tain cooking effluent including, grease, smoke, steam, hot air,
or through outlets in the same room that are typically in the
and vapor. immediate vicinity of the hood.
3.1.10 flow hood—an instrument that measures air flow rate 3.1.15.3 transfer air—outdoor that has been conditioned to
maintain comfort of and ventilate a space adjacent to the space
using a pyramid shaped hood that is used to contain the air to
be measured and is connected to a velocity pressure measuring in which the hood is located. Movement of this air may be
caused by pressure differential between spaces, that are sepa-
devicepositionedattheoutletendofthehood.Acompensating
baffle may be installed so that measurements with the baffle rated by adequately sized openings, or by fans and or grills
connected by ductwork above ceilings and or through walls,
open and closed can be used to estimate the air flow rate
through the device being measured when the pressure drop andshallbeusedtosupplementthecomfortconditioningofthe
imposed by the flow hood is eliminated. space in which the hood is located and to replace air exhausted
through the hood.
3.1.11 hood overhang—the horizontal distance the lower
3.1.16 rotating vane anemometer (RVA)—an instrument that
edge of the hood extends beyond the outer horizontal edge of
measuresairvelocityusinganelectronicpickuptomeasurethe
the cooking surface or outer perimeter of the appliance body.
rotating speed of the vane or propeller. The body of the
3.1.11.1 hood setback—the horizontal distance between the
anemometer is positioned perpendicular to the expected direc-
lower front edge of the hood and the front of the edge of the
tion of the air velocity.
cooking surface or outer perimeter of the cooking appliance.
3.1.17 smoke emitter—device that produces smoke particles
Setback is used for hood styles such as backshelf and/or
from a chemical reaction. The rate of smoke production is
passover that do not fully cover the entire cooking surface or
sufficient to be followed with the naked eye.
appliance.
3.1.18 standard air—air with a density of 0.075 lb/ft .
3.1.12 hot-film anemometer—an instrument for measuring
3.1.19 velocity grid—a velocity measuring device that con-
air velocity at a single point.The instrument measures velocity
past a heated sensor and requires calibration to correlate heat sists of an array of holes on both sides of a matrix. The holes
serveaspressuretapsontheupstreamanddownstreamsidesof
loss to air velocity.
the device. When connected to a differential pressure monitor
3.1.13 humidity measuring device—an instrument for mea-
and calibrated, it will provide the average air velocity across
suring the amount of moisture in the air. The instrument shall
the matrix.
provide the moisture level as either a) relative humidity, b) wet
bulb temperature or c) and/or dew point temperature.
4. Summary of Test Method
3.1.14 pitot tube—a double walled probe with a 90 degree
4.1 All systems that supply comfort conditioning, replace-
bend near the measuring end. The measuring end of the probe
ment air and/or supply air, makeup air, exhaust systems and
is oriented toward the oncoming air flow. The center opening,
cooking appliances in the kitchen shall be installed and
facing the oncoming airstream senses total pressure. Small
operational.
holes located around the circumference of the outer tube sense
static pressure. When connected to a differential pressure 4.2 The general ventilation system or systems for any
instrument the velocity pressure of the air is y measured as the portion or portions of the building that are adjacent to the
F2975 − 12 (2017)
kitchen and/or supply transfer air to the kitchen shall be the air pressure in the kitchen is more than 0.200 in. water less
installed and operation during the test procedure and shall than the air pressure in adjacent spaces, the makeup air flow
maintain the design air pressure in adjacent spaces and shall rate or supply air flow rate to the kitchen must be increased
supply the necessary transfer air. until the pressure differential is reduced to between 0.050 and
0.200 in. water.
4.3 The airflow rates for HVAC, Replacement Air and
kitchen exhaust shall be those specified.
5. Significance and Use
4.4 All ventilation systems associated with the kitchen and
5.1 Successful kitchen exhaust hood performance requires
spaces adjacent to the kitchen shall be turned on and operated
the complete capture and containment of the effluent plume
as under full load cooking conditions.
along the hood’s entire perimeter.Any effluent leakage moving
4.5 The flow rate of air exhausted through the kitchen hood
beyond 3 in. from the hood face will be deemed as having
shall be measured and computed using the apparatus and
escaped from the hood, even if it may appear to be have been
methods defined in this test method. Results shall be adjusted
drawn back into the hood. If effluent spills from the hood, hot
and reported in standard cubic feet per minute (scfm).
and greasy kitchens may be the result and the cause of the
4.6 Whenthecomputedairflowrateisnotwithin5%ofthe
performance failure needs to be determined and corrected.
specified value from 4.3, adjustments, such as changing fan
Oftentimes, the exhaust flow rate needs to be increased to
speedshallbemadeuntilthemeasuredcomputedairflowrates
achieve proper hood performance for particular field condi-
are within5%of specified values.
tions. As a result, the supply air to the kitchen will need to be
increased to maintain the air balance. However, drafty room
4.7 The total flow rate of air supplied to the kitchen shall be
conditions due to incorrectly placed supply diffusers, cross
determined by measuring the flow rate through each supply
drafts from windows and doors, return and supply at opposite
diffuser and makeup air unit and reporting the corresponding
ends of the kitchen, etc. could also severely degrade hood
air flow rates as standard cubic feet per minute (scfm). The
performance. Incorrectly designed supply systems may not be
total amount of air supplied to the kitchen shall be the sum of
corrected by increasing the exhaust rate and could be corrected
the measurements from the individual units.
in a much more efficient and economical manner, such as by
4.8 When the measured air flow rate through any of the
replacing a 4-way diffuser with a 3-way diffuser directed away
supply or makeup air units is less than 95 % of the specified
from the hood. Likewise, if the plume is strongly captured, the
value from 4.3, adjustments shall be made such as increasing
hood may be over-exhausting and reducing the exhaust rate
fanspeedand/oradjustingdamperpositionsuntilthecomputed
could be considered, along with a corresponding reduction of
and specified air flow rates are within 5 % for each supply and
room supply air to maintain the building’s air balance.
makeup air unit.
5.2 An appropriate airflow balance ensures adequate re-
4.9 With the supply air, makeup air, and exhaust air flow
placement air for the necessary exhaust conditions and allows
rates set to within5%of their design values, the ability of all
the desired air pressure distribution to be maintained.
exhaust hoods to capture and contain cooking effluent shall be
evaluated. All cooking appliances shall be turned on to idle 5.3 Negative air pressure in the kitchen with respect to the
conditions and allowed to warm up for one hour. Smoke adjacent indoor spaces ensures that the air flow is from these
emitters shall be used to ensure that the smoke enters all the spaces into the kitchen so that odors and cooking effluent are
hoods without spillage around the entire perimeter of each contained within the kitchen. However, too great a pressure
exhaust hood. imbalance will severely degrade hood performance by creating
a wind tunnel effect. Negative air pressure in the dining area
4.10 If
...


This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: F2975 − 12 F2975 − 12 (Reapproved 2017) An American National Standard
Standard Test Method for
Measuring the Field Performance of Commercial Kitchen
Ventilation Systems
This standard is issued under the fixed designation F2975; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This test method can be used to measure and validate successful design, installation and commissioning of commercial
kitchen HVAC and makeup air systems for specific installations.
1.2 This test method field evaluates commercial kitchen ventilation system airflows and pressures.
1.3 This test method field evaluates visual hood capture and containment performance.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are for information
only.
1.5 The data generated is specific to the field conditions as installed.
1.6 This test method may involve hazardous materials, gasses (for example, CO) operations, and equipment. This standard does
not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard
to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
1.7 This international standard was developed in accordance with internationally recognized principles on standardization
established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued
by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
2. Referenced Documents
2.1 ASTM Standards:
F1704 Test Method for Capture and Containment Performance of Commercial Kitchen Exhaust Ventilation Systems
2.2 Other Standards:
ANSI/ASHRAE Standard 111-2008 Measurement, Testing, Adjusting and Balancing of Building HVAC Systems
ANSI/ASHRAE Standard 154 Ventilation for Commercial Cooking Operations
Testing, Adjusting and Balancing, Chapter 37 2007 HVAC Applications Handbook
Kitchen Ventilation, Chapter 31 2007 HVAC Applications Handbook
3. Terminology
3.1 Definitions:
3 3
3.1.1 airflow rate—volumetric flow rate of air in units of ft /min (cfm) or m /s. When adjusted for standard air density the flow
rate is designated by scfm.
3.1.2 appliance—cooking device used in kitchen and powered by gas, and/or electricity and/or solid fuel.
3.1.3 barometric pressure—absolute pressure of the air measured by a barometer or absolute pressure measuring device.
3.1.4 capture and containment (C&C)—the ability of a hood or other removal device to capture and contain all effluent
generated by the appliances or processes during normal operation.
This test method is under the jurisdiction of ASTM Committee F26 on Food Service Equipment and is the direct responsibility of Subcommittee F26.07 on Commercial
Kitchen Ventilation.
Current edition approved Oct. 1, 2012April 1, 2017. Published December 2012May 2017. Originally approved in 2012. Last previous edition approved in 2012 as
F2975 – 12. DOI: 10.1520/F2975-1210.1520/F2975-12R17.
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Available from American National Standards Institute (ANSI), 25 W. 43rd St., 4th Floor, New York, NY 10036, http://www.ansi.org.
Available from American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. (ASHRAE), 1791 Tullie Circle, NE, Atlanta, GA 30329,
http://www.ashrae.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
F2975 − 12 (2017)
3.1.4.1 Discussion—
For the purpose of this test method effluent may be simulated as defined in this test method.
3.1.4.2 Discussion—
Successful C&C shall be demonstrated along the entire perimeter of the hood or removal device.
3.1.4.3 Discussion—
Successful C&C may include rising effluent that when below the leading edge of the hood may extend out no more than 3 in.
vertically beyond the leading edge of the hood and is completely recovered before reaching the leading edge of the hood or removal
device and once inside the hood is completely contained. F1704
3.1.4.4 Discussion—
For backshelf or passover style hoods effluent shall not rise more than 3 in. above the exterior leading edge of the hood and shall
not extend more than 3 in. beyond the open front or sides of the cooking surface and shall be completely contained once reaching
the hood.
3.1.5 differential pressure gauge—instrument that measures pressure difference between the two inlet ports. This can be a
mechanical type such as a Bourdon gauge with an indicator on a dial face or an electronic type with a digital readout.
3.1.6 dry bulb temperature—sensible temperature of air as measured by a shielded thermometer or an electronic temperature
measuring device.
3.1.7 effluent—emissions from cooking, dishwasher or other ventilated processes such as convective hot air, steam, vapor,
products of combustion, smoke and/or particulate matter.
3.1.8 exhaust fan—also called power roof ventilator or centrifugal blower. A fan used to exhaust cooking effluent including,
grease, smoke, steam, heat, and/or vapor collected by a hood. The majority of these fans have a centrifugal fan wheel.
3.1.9 exhaust hood—a device designed to capture and contain cooking effluent including, grease, smoke, steam, hot air, and
vapor.
3.1.10 flow hood—an instrument that measures air flow rate using a pyramid shaped hood that is used to contain the air to be
measured and is connected to a velocity pressure measuring device positioned at the outlet end of the hood. A compensating baffle
may be installed so that measurements with the baffle open and closed can be used to estimate the air flow rate through the device
being measured when the pressure drop imposed by the flow hood is eliminated.
3.1.11 hood overhang—the horizontal distance the lower edge of the hood extends beyond the outer horizontal edge of the
cooking surface or outer perimeter of the appliance body.
3.1.11.1 hood setback—the horizontal distance between the lower front edge of the hood and the front of the edge of the cooking
surface or outer perimeter of the cooking appliance. Setback is used for hood styles such as backshelf and/or passover that do not
fully cover the entire cooking surface or appliance.
3.1.12 hot-film anemometer—an instrument for measuring air velocity at a single point. The instrument measures velocity past
a heated sensor and requires calibration to correlate heat loss to air velocity.
3.1.13 humidity measuring device—an instrument for measuring the amount of moisture in the air. The instrument shall provide
the moisture level as either a) relative humidity, b) wet bulb temperature or c) and/or dew point temperature.
3.1.14 pitot tube—a double walled probe with a 90 degree bend near the measuring end. The measuring end of the probe is
oriented toward the oncoming air flow. The center opening, facing the oncoming airstream senses total pressure. Small holes
located around the circumference of the outer tube sense static pressure. When connected to a differential pressure instrument the
velocity pressure of the air is y measured as the difference between the total pressure sensed by the central tube and the static
pressure sensed by the outer tube.
3.1.15 replacement air—outdoor air that is used to replace air removed from a building through an exhaust system. Replacement
air may be derived from one or more of the following: Kitchen Supply, Makeup Air and/or Transfer Air. However, the ultimate
source of all replacement air is outdoor air.
3.1.15.1 kitchen supply—air entering a space that contains hoods and originates from an air-handling device that serves both
purposes of supplying replacement air as well as space conditioning. Supply air is generally filtered, fan-forced, and either heated
and/or cooled and/or humidified and/ or dehumidified as necessary to maintain specified space temperature and/or humidity
conditions.
F2975 − 12 (2017)
3.1.15.2 makeup air (dedicated replacement air)—outdoor air supplied directly to a compensating hood or to supply air devices
located in the immediate vicinity of the hood to replace air being exhausted through the hood. Makeup air is generally filtered and
fan-forced, and it may be heated and/or cooled depending on the requirements of the application. Makeup air may be delivered
through outlets integral to the exhaust hood or through outlets in the same room that are typically in the immediate vicinity of the
hood.
3.1.15.3 transfer air—outdoor that has been conditioned to maintain comfort of and ventilate a space adjacent to the space in
which the hood is located. Movement of this air may be caused by pressure differential between spaces, that are separated by
adequately sized openings, or by fans and or grills connected by ductwork above ceilings and or through walls, and shall be used
to supplement the comfort conditioning of the space in which the hood is located and to replace air exhausted through the hood.
3.1.16 rotating vane anemometer (RVA)—an instrument that measures air velocity using an electronic pickup to measure the
rotating speed of the vane or propeller. The body of the anemometer is positioned perpendicular to the expected direction of the
air velocity.
3.1.17 smoke emitter—device that produces smoke particles from a chemical reaction. The rate of smoke production is sufficient
to be followed with the naked eye.
3.1.18 standard air—air with a density of 0.075 lb/ft .
3.1.19 velocity grid—a velocity measuring device that consists of an array of holes on both sides of a matrix. The holes serve
as pressure taps on the upstream and downstream sides of the device. When connected to a differential pressure monitor and
calibrated, it will provide the average air velocity across the matrix.
4. Summary of Test Method
4.1 All systems that supply comfort conditioning, replacement air and/or supply air, makeup air, exhaust systems and cooking
appliances in the kitchen shall be installed and operational.
4.2 The general ventilation system or systems for any portion or portions of the building that are adjacent to the kitchen and/or
supply transfer air to the kitchen shall be installed and operation during the test procedure and shall maintain the design air pressure
in adjacent spaces and shall supply the necessary transfer air.
4.3 The airflow rates for HVAC, Replacement Air and kitchen exhaust shall be those specified.
4.4 All ventilation systems associated with the kitchen and spaces adjacent to the kitchen shall be turned on and operated as
under full load cooking conditions.
4.5 The flow rate of air exhausted through the kitchen hood shall be measured and computed using the apparatus and methods
defined in this test method. Results shall be adjusted and reported in standard cubic feet per minute (scfm).
4.6 When the computed air flow rate is not within 5% 5 % of the specified value from 4.3, adjustments, such as changing fan
speed shall be made until the measured computed air flow rates are within 5% 5 % of specified values.
4.7 The total flow rate of air supplied to the kitchen shall be determined by measuring the flow rate through each supply diffuser
and makeup air unit and reporting the corresponding air flow rates as standard cubic feet per minute (scfm). The total amount of
air supplied to the kitchen shall be the sum of the measurements from the individual units.
4.8 When the measured air flow rate through any of the supply or makeup air units is less than 95% 95 % of the specified value
from 4.3, adjustments shall be made such as increasing fan speed and/or adjusting damper positions until the computed and
specified air flow rates are within 5% 5 % for each supply and makeup air unit.
4.9 With the supply air, makeup air, and exhaust air flow rates set to within 5% 5 % of their design values, the ability of all
exhaust hoods to capture and contain cooking effluent shall be evaluated. All cooking appliances shall be turned on to idle
conditions and allowed to warm up for one hour. Smoke emitters shall be used to ensure that the smoke enters all the hoods without
spillage around the entire perimeter of each exhaust hood.
4.10 If spillage occurs, the exhaust air flow rate in the hood must be increased, or the replacement air redirected, and the test
repeated until no spillage is observed. The increase in exhaust flow rate is usually accomplished by increasing the fan speed.
4.11 The differential static pressure shall be measured between the kitchen and adjacent areas in the same building such as the
dining area and dry storage areas, and the kitchen and outdoors.
4.12 When the kitchen static pressure is within 0.02–0.05 6 0.005 of the static pressure of the dining area or any adjacent
occupied area in the building, at least one kitchen exhaust system shall be adjusted to exhaust a larger amount of air until the
pressure in the kitchen is a minimum of 0.005 in. water less than the surrounding areas.
4.13 When the total exhaust air flow rate from the kitchen has been increased more than 10% 10 % above the design value to
provide adequate capture and containment of the effluent, and the air pressure in the kitchen is more than 0.200 in. water less than
the air pressure in adjacent spaces, the makeup air flow rate or supply air flow rate to the kitchen must be increased until the
pressure differential is reduced to between 0.050 and 0.200 in. water.
F2975 − 12 (2017)
5. Significance and Use
5.1 Successful kitchen exhaust hood performance requires the complete capture and containment of the effluent plume along
the hood’s entire perimeter. Any effluent leakage moving beyond 3 in. from the hood face will be deemed as having escaped from
the hood, even if it may appear to be have been drawn back into the hood. If effluent spills from the hood, hot and greasy kitchens
may be the result and the cause of the performance failure needs to be determined and
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.