Standard Specification for Precast Reinforced Concrete Box Sections for Culverts, Storm Drains, and Sewers

SCOPE
1.1 This specification covers single-cell precast reinforced concrete box sections intended to be used for the construction of culverts and for the conveyance of storm water industrial wastes and sewage.
1.2 This specification is the companion to SI Specification C 1433M; therefore, no SI equivalents are shown in this specification.
Note 1—This specification is primarily a manufacturing and purchasing specification. However, standard designs are included and the criteria used to develop these designs are given in Appendix X1. The successful performance of this product depends upon the proper selection of the box section, bedding, backfill, and care that the installation conforms to the construction specifications. The purchaser of the precast reinforced concrete box sections specified herein is cautioned that proper correlation of the loading conditions and the field requirements with the box section specified, and provision for inspection at the construction site, are required.

General Information

Status
Historical
Publication Date
09-May-2003
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM C1433-03 - Standard Specification for Precast Reinforced Concrete Box Sections for Culverts, Storm Drains, and Sewers
English language
16 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn. Contact ASTM
International (www.astm.org) for the latest information.
Designation: C 1433 – 03
Standard Specification for
Precast Reinforced Concrete Box Sections for Culverts,
1
Storm Drains, and Sewers
This standard is issued under the fixed designation C 1433; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
2
1. Scope Billet-Steel Bars for Concrete Reinforcement
C 31/C 31M Practice for Making and Curing ConcreteTest
1.1 This specification covers single-cell precast reinforced
3
Specimens in the Field
concrete box sections intended to be used for the construction
3
C 33 Specification for Concrete Aggregates
of culverts and for the conveyance of storm water industrial
C 39 Test Method for Compressive Strength of Cylindrical
wastes and sewage.
3
Concrete Specimens
1.2 This specification is the companion to SI Specification
4
C 150 Specification for Portland Cement
C 1433M; therefore, no SI equivalents are shown in this
C 309 Specification for Liquid Membrane-Forming Com-
specification.
3
pounds for Curing Concrete
NOTE 1—This specification is primarily a manufacturing and purchas-
C 497 Test Methods for Concrete Pipe, Manhole Sections,
ing specification. However, standard designs are included and the criteria
5
or Tile
used to develop these designs are given in Appendix X1. The successful
4
C 595 Specification for Blended Hydraulic Cements
performance of this product depends upon the proper selection of the box
C 618 Specification for Coal Fly Ash and Raw or Calcined
section, bedding, backfill, and care that the installation conforms to the
Natural Pozzolan for Use as a Mineral Admixture in
construction specifications. The purchaser of the precast reinforced
3
concrete box sections specified herein is cautioned that proper correlation
Concrete
of the loading conditions and the field requirements with the box section
C 822 Terminology Relating to Concrete Pipe and Related
specified, and provision for inspection at the construction site, are 5
Products
required.
C 1116 Specification for Fiber-Reinforced Concrete and
5
Shotcrete
2. Referenced Documents
6
2.2 AASHTO Standard:
2.1 ASTM Standards:
Specifications for Highway Bridges, 1997 Edition
A 82 Specification for Steel Wire, Plain, for Concrete Re-
2
inforcement
3. Terminology
A 185 Specification for Steel Welded Wire Reinforcement,
3.1 Definitions—For definitions of terms relating to con-
2
Plain, for Concrete
crete pipe, see Terminology C 822.
A 496 Specification for Steel Wire, Deformed, for Concrete
2
Reinforcement
4. Types
A 497 Specification for Steel Welded Wire Reinforcement,
4.1 Precast reinforced concrete box sections manufactured
2
Deformed, for Concrete
in accordance with this specification shall be one of two types
A 615/A 615M Specification for Deformed and Plain
identified in Tables 1 and 2, and shall be designated by type,
span, rise, and design earth cover.
1
This specification is under the jurisdiction of Committee C13 on Concrete Pipe
3
and is the direct responsibility of Subcommittee C13.07 on Acceptance Specifica- Annual Book of ASTM Standards, Vol 04.02.
4
tions and Precast Concrete Box Sections. Annual Book of ASTM Standards, Vol 04.01.
5
Current edition approved May 10, 2003. Published July 2003. Originally Annual Book of ASTM Standards, Vol 04.05.
6
approved in 1999. Last previous edition approved in 2002 as C 1433–02a. Available from American Association of State Highway and Transportation
2
Annual Book of ASTM Standards, Vol 01.04. Officials (AASHTO), 444 N. Capitol St., NW, Suite 249, Washington, DC 20001.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn. Contact ASTM
International (www.astm.org) for the latest information.
C1433–03
TABLE 1 Design Requirements for Precast Concrete Box
15 0.12 0.19 0.19 0.12 18
Sections Under Earth Dead and HS20 Live Load Conditions
20 0.14 0.24 0.25 0.12 18
25 0.18 0.30 0.30 0.12 18
NOTE 1—Design earth covers and reinforcement areas are based on the
30 0.21 0.36 0.36 0.12 18
weight of a column of earth over the width of the box section as defined
A
in Appendix X1. Topslab8in.,bottomslab6in.
NOTE 2—Concrete design strength 5000 psi.
4ftby4ftby5in.
NOTE 3—The design earth cover indicated is the height of fill above the
2
Design Circumferential Reinforcement Areas, in. /ft
top of the box section. Design requirements are based on the material and
Earth
soil properties, loading data, and typical section as included in Appendix
A A A A A A A A “M,” in.
s1 s2 s3 s4 s5 s6 s7 s8
...