Standard Test Method for Surface Flammability of Materials Using a Radiant Heat Energy Source

SIGNIFICANCE AND USE
5.1 This test method provides a laboratory test procedure for measuring and comparing the surface flammability of materials when exposed to a prescribed level of radiant heat energy. It is intended for use in measurements of the surface flammability of materials exposed to fire. The test is conducted using small specimens that are representative, to the extent possible, of the material or assembly being evaluated. (Example: in terms of their thickness, layering, and any potential substrate.)  
5.2 The rate at which flames will travel along surfaces depends upon the physical and thermal properties of the material, product or assembly under test, the specimen mounting method and orientation, the type and level of fire or heat exposure, the availability of air, and properties of the surrounding enclosure.4  
5.3 In this procedure, the specimens are subjected to one or more specific sets of laboratory fire test conditions. If different test conditions are substituted or the end-use conditions are changed, it is not always possible by or from this test to predict changes in the fire-test-response characteristics measured. Therefore, the results are valid only for the fire test exposure conditions described in this procedure.  
5.4 If the test results obtained by this test method are to be considered as part of an overall assessment of fire hazard in a building or structure, then the example criteria, concepts and procedures incorporated into Guide E1546 shall be taken into consideration.
SCOPE
1.1 This fire-test-response standard describes the measurement of surface flammability of materials. It is not intended for use as a basis of ratings for building code purposes (see Appendix X1).  
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.  
1.3 This standard measures and describes the response of materials, products, or assemblies to heat and flame under controlled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials, products, or assemblies under actual fire conditions.  
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.  
1.5 Fire testing of products and materials is inherently hazardous, and adequate safeguards for personnel and property shall be employed in conducting these tests. This test method may involve hazardous materials, operations, and equipment. Specific information about hazard is given in Section .
Note 1: There is no similar or equivalent ISO standard.

General Information

Status
Historical
Publication Date
14-Dec-2015
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Effective Date
15-Dec-2015

Buy Standard

Standard
ASTM E162-15b - Standard Test Method for Surface Flammability of Materials Using a Radiant Heat Energy Source
English language
12 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM E162-15b - Standard Test Method for Surface Flammability of Materials Using a Radiant Heat Energy Source
English language
12 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: E162 − 15b An American National Standard
Standard Test Method for
Surface Flammability of Materials Using a Radiant Heat
1
Energy Source
This standard is issued under the fixed designation E162; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the U.S. Department of Defense.
1. Scope Cement Interior Substrate Sheets
D3675Test Method for Surface Flammability of Flexible
1.1 This fire-test-response standard describes the measure-
Cellular Materials Using a Radiant Heat Energy Source
mentofsurfaceflammabilityofmaterials.Itisnotintendedfor
E84Test Method for Surface Burning Characteristics of
use as a basis of ratings for building code purposes (see
Building Materials
Appendix X1).
E176Terminology of Fire Standards
1.2 The values stated in inch-pound units are to be regarded
E1546Guide for Development of Fire-Hazard-Assessment
as standard. The values given in parentheses are mathematical
Standards
conversions to SI units that are provided for information only
3
2.2 ISO Standards
and are not considered standard.
ISO13943Fire Safety—Vocabulary
1.3 This standard measures and describes the response of
3. Terminology
materials, products, or assemblies to heat and flame under
controlled conditions, but does not by itself incorporate all
3.1 Definitions—For definitions of terms used in this test
factors required for fire hazard or fire risk assessment of the
method, refer to the terminology contained in Terminology
materials, products, or assemblies under actual fire conditions.
E176 and ISO13943. In case of conflict, the definitions given
in Terminology E176 shall prevail.
1.4 This standard does not purport to address all of the
safety concerns, if any, associated with its use. It is the
3.2 Definitions of Terms Specific to This Standard:
responsibility of the user of this standard to establish appro-
3.2.1 flashing, n—flame fronts of 3 seconds or less in
priate safety and health practices and determine the applica-
duration.
bility of regulatory limitations prior to use.
3.2.1.1 Discussion—All flame fronts, however temporary,
1.5 Fire testing of products and materials is inherently
are to be taken into account.
hazardous,andadequatesafeguardsforpersonnelandproperty
3.2.2 radiant panel index, I,n—the radiant panel index is
s
shall be employed in conducting these tests. This test method
the product of the flame spread factor, F , and the heat
s
may involve hazardous materials, operations, and equipment.
evolution factor, Q.
Specific information about hazard is given in Section .
NOTE 1—There is no similar or equivalent ISO standard. 4. Summary of Test Method
4.1 This test method of measuring surface flammability of
2. Referenced Documents
materials employs a radiant heat source consisting of a 12 by
2
2.1 ASTM Standards:
18-in. (305 by 457-mm) panel, in front of which an inclined 6
C1186Specification for Flat Fiber-Cement Sheets
by 18-in. (152 by 457 mm) specimen of the material is placed.
C1288 Specification for Discrete Non-Asbestos Fiber-
The orientation of the specimen is such that ignition is forced
near its upper edge and the flame front progresses downward.
4.2 A factor derived from the rate of progress of the flame
1
This test method is under the jurisdiction of ASTM Committee E05 on Fire
Standards and is the direct responsibility of Subcommittee E05.22 on Surface front and another derived from the rate of heat liberated by the
Burning.
material under test are combined to provide a radiant panel
Current edition approved Dec. 15, 2015. Published January 2016. Originally
index.
approved in 1960. Last previous edition approved in 2015 as E162–15a. DOI:
10.1520/E0162-15B.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
3
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Available from International Organization for Standardization (ISO), 1, ch. de
Standards volume information, refer to the standard’s Document Summary page on la Voie-Creuse, Case postale 56, CH-1211, Geneva 20, Switzerland, http://
the ASTM website. www.iso.ch.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
E162 − 15b
5. Significance and Use 6.1.3 Framework for Support of the Specimen Holder—The
framework shall have two transverse rods of stainless steel,
5.1 Thistestmethodprovidesalaboratorytestprocedurefor
each 0.50 6 0.13 in. (12.7 6 3.3 mm) in diameter, with a stop
measuringandcomparingthesurfaceflammabilityofmaterials
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: E162 − 15a E162 − 15b An American National Standard
Standard Test Method for
Surface Flammability of Materials Using a Radiant Heat
1
Energy Source
This standard is issued under the fixed designation E162; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the U.S. Department of Defense.
1. Scope
1.1 This fire-test-response standard describes the measurement of surface flammability of materials. It is not intended for use
as a basis of ratings for building code purposes (see Appendix X1).
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
1.3 This standard measures and describes the response of materials, products, or assemblies to heat and flame under controlled
conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials, products,
or assemblies under actual fire conditions.
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
1.5 Fire testing of products and materials is inherently hazardous, and adequate safeguards for personnel and property shall be
employed in conducting these tests. This test method may involve hazardous materials, operations, and equipment. Specific
information about hazard is given in Section .
NOTE 1—There is no similar or equivalent ISO standard.
2. Referenced Documents
2
2.1 ASTM Standards:
C1186 Specification for Flat Fiber-Cement Sheets
C1288 Specification for Discrete Non-Asbestos Fiber-Cement Interior Substrate Sheets
D3675 Test Method for Surface Flammability of Flexible Cellular Materials Using a Radiant Heat Energy Source
E84 Test Method for Surface Burning Characteristics of Building Materials
E176 Terminology of Fire Standards
E1546 Guide for Development of Fire-Hazard-Assessment Standards
3
2.2 ISO Standards
ISO 13943 Fire Safety—Vocabulary
3. Terminology
3.1 Definitions—For definitions of terms used in this test method, refer to the terminology contained in Terminology E176 and
ISO 13943. In case of conflict, the definitions given in Terminology E176 shall prevail.
3.2 Definitions of Terms Specific to This Standard:
3.2.1 flashing, n—flame fronts of 3 seconds or less in duration.
1
This test method is under the jurisdiction of ASTM Committee E05 on Fire Standards and is the direct responsibility of Subcommittee E05.22 on Surface Burning.
Current edition approved July 1, 2015Dec. 15, 2015. Published September 2015January 2016. Originally approved in 1960. Last previous edition approved in 2015 as
E162 – 15.E162 – 15a. DOI: 10.1520/E0162-15A.10.1520/E0162-15B.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
3
Available from International Organization for Standardization (ISO), 1, ch. de la Voie-Creuse, Case postale 56, CH-1211, Geneva 20, Switzerland, http://www.iso.ch.
3.2.1.1 Discussion—
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
E162 − 15b
All flame fronts, however temporary, are to be taken into account.
3.2.2 radiant panel index, I , n—the radiant panel index is the product of the flame spread factor, F , and the heat evolution
s s
factor, Q.
4. Summary of Test Method
4.1 This test method of measuring surface flammability of materials employs a radiant heat source consisting of a 12 by 18-in.
(305 by 457-mm) panel, in front of which an inclined 6 by 18-in. (152 by 457 mm) specimen of the material is placed. The
orientation of the specimen is such that ignition is forced near its upper edge and the flame front progresses downward.
4.2 A factor derived from the rate of progress of the flame front and another derived from the rate of heat liberated by the
materia
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.