Standard Specification for Filter Units, Air Conditioning: Viscous-Impingement and Dry Types, Replaceable (Withdrawn 2012)

ABSTRACT
This specification covers throw-away, flat panel-type filter units for use in air conditioning, heating, and ventilating systems. This specification also includes panel-type filters with pleated media. The filters are furnished in two types as follows: type I - throw-away frames and media, and type II - permanent frames with replaceable media. The filters are furnished in three grades as follows: grade A - standard dust-holding capacity, grade B - high dust-holding capacity, and grade C - high resistance. The adhesive oil, filter initial resistance, filter average arrestance, and filter dust holding capacity conform to the requirements specified.
SCOPE
1.1 This specification covers throw-away, flat panel-type filter units for use in air conditioning, heating, and ventilating systems. This specification also includes panel-type filters with pleated media.
1.2 The values stated in inch-pound units are to be regarded as the standard.
WITHDRAWN RATIONALE
This specification covered throw-away, flat panel-type filter units for use in air conditioning, heating, and ventilating systems. This specification also included panel-type filters with pleated media.
Formerly under the jurisdiction of Committee D22 on Air Quality, this specification was withdrawn in April 2012 due to its limited use by industry.

General Information

Status
Withdrawn
Publication Date
31-Mar-2007
Withdrawal Date
31-Mar-2012
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM F1040-87(2007) - Standard Specification for Filter Units, Air Conditioning: Viscous-Impingement and Dry Types, Replaceable (Withdrawn 2012)
English language
3 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: F1040 – 87 (Reapproved 2007)
Standard Specification for
Filter Units, Air Conditioning: Viscous-Impingement and Dry
1
Types, Replaceable
This standard is issued under the fixed designation F1040; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the Department of Defense.
1. Scope 4. Classification
1.1 This specification covers throw-away, flat panel-type 4.1 The filters are furnished in two types as follows:
filter units for use in air conditioning, heating, and ventilating 4.1.1 Type 1—Throw-away frames and media, and
systems.Thisspecificationalsoincludespanel-typefilterswith 4.1.2 Type 2—Permanent frames with replaceable media.
pleated media. 4.2 The filters are furnished in three grades as follows:
1.2 The values stated in inch-pound units are to be regarded 4.2.1 Grade A—Standard dust-holding capacity,
as the standard. 4.2.2 Grade B—High dust-holding capacity, and
4.2.3 Grade C—High arrestance.
2. Referenced Documents
2
5. Ordering Information
2.1 ASTM Standards:
D3951 Practice for Commercial Packaging 5.1 Contracts or orders for the units under this specification
2.2 ASHRAE Standard: shall include the following information:
52 Method of Testing Air-Cleaning Devices Used in Gen- 5.1.1 Quantity,
3
eral Ventilation for Removing Particulate Matter 5.1.2 MaterialformediaframeforType2filter,(seesection
2.3 Federal Standard: 6.4.4),
Fed. Std. No. 123 Military Standard for Marking for Ship- 5.1.3 Size, (See 7.1),
4
ment and Storage 5.1.4 Certification of the filter units by the producer or
2.4 Military Standard: supplier, if required, (see Section 10).
4
MIL-STD-129 Marking for Shipment and Storage
6. Materials and Manufacture
2.5 UL Standard:
5
6.1 Filters shall be the manufacturer’s standard commercial
UL900 Test Performance of Air Filter Units
product with any added features needed to comply with the
3. Descriptions of Term Specific to This Standard
specified requirements.
3.1 net face area—the net upstream area of the medium
7. Physical Properties
exposed to air flow measured in the plane or planes of the
7.1 The filter units shall be the flat panel type, with or
media, excluding sealing flanges, framing supports, etc.
without pleated media. They shall be designed and fabricated
for disposal when, because of accumulated dust loading, the
1
This specification is under the jurisdiction of ASTM Committee D22 on Air
dust-load limit is reached. In Type 2 filters, the media frames
Quality and is the direct responsibility of Subcommittee D22.05 on Indoor Air.
shallbepermanentandthemediapadonlyshallbedisposable.
Current edition approved April 1, 2007. Published June 2007. Originally
approved in 1987. Last previous edition approved in 2001 as F1040-87(2001).
The filter media shall be dry or adhesive-coated in accordance
DOI: 10.1520/F1040-87R07.
with the manufacturer’s recommendations.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
7.2 Filter Construction—Filters shall be constructed with
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
1
90° corners. Frame edges shall be parallel to within ⁄16 in.
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website.
Mediapadreinforcementintheformofgrilles,retaininggrids,
3
Available from American Society of Heating, Refrigerating, and Air-
fabricnetting,ortheequivalentshallbeinstalledonbothfaces
Conditioning Engineers, Inc. (ASHRAE), 1791 Tullie Circle, NE, Atlanta, GA
of the filter in accordance with the manufacturer’s recommen-
30329, http://www.ashrae.org.
4
Available from Standardization Documents Order Desk, DODSSP, Bldg. 4, dations. The media shall be attached to the frame of Type 1
Section D, 700 Robbins Ave., Philadelphia, PA 19111-5098, http://
filters, and supported in the frame of Type 2 filters, in such a
www.dodssp.daps.mil.
5 manner that the media pad will not slump or otherwise be
Available from Underwriters Laboratories (UL), 333 Pfingsten Rd., North-
brook, IL 60062-2096, http://www.ul.com.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
F1040 – 87 (2007)
permanently displaced under the conditions of maximum air at350fpm(1.78m/s)facevelocity.TheresultsofTable1shall
velocity (350 ft/min (1.78 m/s)) and filter resistance specified be obtained at the maximum final pressure drop specified in
herein. 7.2.2.
7.2.1 Filter Media—Filter media shall be suitable for the 8.3.4 Dissimilar Metals—Joints between di
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.