ASTM C412-99
(Specification)Standard Specification for Concrete Drain Tile
Standard Specification for Concrete Drain Tile
SCOPE
1.1 This specification covers concrete drain tile with internal diameters from 4 to 36 in. that are intended to be used for surface and subsurface drainage.
1.2 A complete metric companion to Specification C412 has been developed--C412M; therefore, no metric equivalents are presented in this specification. Note 1-This specification is a manufacturing and purchase specification only and does not include requirements for bedding, backfill, or the relationship between field load condition and the strength classification of drain tile. However, experience has shown that the successful performance of the product depends upon the proper selection of the class of drain tile, type of bedding and backfill, and care that the installation conforms to the construction specifications. The owner is cautioned that he must correlate the field requirements with the class of drain tile specified and provide for or require inspection at the construction site.
General Information
Relations
Standards Content (Sample)
NOTICE: This standard has either been superceded and replaced by a new version or discontinued.
Contact ASTM International (www.astm.org) for the latest information.
Designation: C 412 – 99
Standard Specification for
1
Concrete Drain Tile
This standard is issued under the fixed designation C 412; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the Department of Defense.
1. Scope shall be of the following four classes:
4.1.1 Standard-Quality Concrete Drain Tile, intended for
1.1 This specification covers concrete drain tile with inter-
land drainage of ordinary soils where the tile are laid in
nal diameters from 4 to 36 in. that are intended to be used for
trenches of moderate depths and widths. Standard-Quality
surface and subsurface drainage.
concrete drain tile are not recommended for use where internal
1.2 A complete metric companion to Specification C 412
diameters in excess of 12 in. are required.
has been developed—C 412M; therefore, no metric equivalents
4.1.2 Extra-Quality Concrete Drain Tile, intended for land
are presented in this specification.
drainage of ordinary soils where the tile are laid in trenches of
NOTE 1—This specification is a manufacturing and purchase specifica-
considerable depths or widths, or both.
tion only and does not include requirements for bedding, backfill, or the
4.1.3 Heavy-Duty Extra-Quality Concrete Drain Tile, in-
relationship between field load condition and the strength classification of
tended for land drainage of ordinary soils where the tile are laid
drain tile. However, experience has shown that the successful performance
in trenches of large depths or widths, or both.
of the product depends upon the proper selection of the class of drain tile,
4.1.4 Special-Quality Concrete Drain Tile, intended for land
type of bedding and backfill, and care that the installation conforms to the
construction specifications. The owner is cautioned that he must correlate
drainage where special precautions are necessary for concrete
the field requirements with the class of drain tile specified and provide for
tile laid in soils that are markedly acid or contain unusual
or require inspection at the construction site.
quantities of sulfates (see Section 7), and where the tile are laid
in trenches of considerable depths or widths, or both.
2. Referenced Documents
4.1.4.1 Where the calculated loads are in excess of the
2.1 ASTM Standards:
crushing strengths prescribed in the physical requirements for
2
C 33 Specification for Concrete Aggregates
extra-quality and special-quality concrete drain tile, tile
3
C 150 Specification for Portland Cement
strengths must be specified in advance by the owner.
C 497 Test Methods for Testing Concrete Pipe, Manhole
4
Sections, or Tile
5. Basis of Acceptance
3
C 595 Specification for Blended Hydraulic Cements
5.1 The acceptability of drain tile shall be determined by (1)
C 618 Specification for Coal Fly Ash and Raw or Calcined
the results of the physical tests as specified in Section 8, and in
Natural Pozzolan for Use as a Mineral Admixture in
Test Methods C 497, (2) measurements and inspection to
2
Concrete
ascertain whether the tile conform to the requirements regard-
C 822 Terminology Relating to Concrete Pipe and Related
ing dimensions, shape, and freedom from visible defects, and
4
Products
(3) the manufacturer’s certification in writing that the tile have
been made in accordance with any special provisions, such as
3. Terminology
strength, absorption, permeability, type of cement, admixture,
3.1 Definitions—For definitions of terms relating to con-
curing conditions, etc.
crete pipe, see Terminology C 822.
5.2 The owner shall specify in writing the class or classes of
concrete tile to be supplied, whether Standard-Quality, Extra-
4. Classification
Quality, Heavy-Duty Extra-Quality, or Special-Quality. Unless
4.1 Drain tile manufactured according to this specification
Extra-Quality, Heavy-Duty Extra-Quality, or Special-Quality
concrete drain tile have been specified, Standard-Quality drain
1
This specification is under the jurisdiction of ASTM Committee C-13 on
tile shall be accepted.
Concrete Pipe and is the direct responsibility of Subcommittee C13.01 on
Reinforced Concrete Sewer, Drain, and Irrigation Pipe.
6. Materials
Current edition approved Aug. 10, 1999. Published September 1999. Originally
6.1 Concrete—The concrete shall consist of cementitious
published as C 412–58T. Last previous edition C 412–94.
2
Annual Book of ASTM Standards, Vol 04.02.
materials, mineral aggregates, and water.
3
Annual Book of ASTM Standards, Vol 04.01.
6.2 Cementitious Materials:
4
Annual Book of ASTM Standards, Vol 04.05.
Copyright © ASTM International, 100 Barr Harbor Drive, PO B
...