ASTM F1482-04
(Guide)Standard Practice for Installation and Preparation of Panel Type Underlayments to Receive Resilient Flooring
Standard Practice for Installation and Preparation of Panel Type Underlayments to Receive Resilient Flooring
SIGNIFICANCE AND USE
This practice provides minimum recommendations for the installation and preparation of wood-based, fiber-reinforced gypsum and fiber-cement panel underlayments suitable to receive resilient floor coverings. Actual requirements for materials to be used, mixtures, and other details are generally included as part of project plans or specification detail and may vary from the minimum recommendations set forth in this practice.
SCOPE
1.1 This practice includes recommendations for wood based, fiber reinforced gypsum and fiber-cement panel underlayment/subfloor assemblies upon which resilient flooring may be installed.
1.2 This practice does not cover the adequacy of the subfloor assembly to perform its structural requirements, which is governed by local building codes.
1.3 This practice does not supersede in any manner the resilient flooring, underlayment or adhesive manufacturer's written instructions. Consult the individual resilient flooring, underlayment or adhesive manufacturer for specific recommendations.
1.4 See Supplementary Requirements for "Select Warnings" that have been provided.
1.5 The values stated in inch/pound units are to be regarded as standard; the metric units in parentheses are for reference only.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
General Information
Relations
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:F1482–04
Standard Practice for
Installation and Preparation of Panel Type Underlayments to
1
Receive Resilient Flooring
This standard is issued under the fixed designation F 1482; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
3
1. Scope ANSI/A208.1-1998 Particleboard
3
ANSI/AHAA135.4-1995 Basic Hardboard
1.1 This practice includes recommendations for the instal-
2.3 NIST Standards:
lation of panel type underlayments including wood based, fiber
Voluntary Product Standard PS1-95 for Construction and
reinforced gypsum and fiber-cement panel underlayment/
3,4
Industrial Plywood
subfloor assemblies upon which resilient flooring may be
Voluntary Product Standard PS2-92 for Wood-Based
installed.
3,4
Structural-Use Panels
1.2 The structural integrity of subfloor assemblies is gov-
2.4 Other Documents:
erned by local building codes.
5
APA Engineered Wood Construction Guide, Form E30
1.3 This practice does not supersede in any manner the
APAInstallation and Preparation of Plywood Underlayment
resilient flooring, underlayment or adhesive manufacturer’s
5
for Resilient Flooring, Form L335
written instructions. Consult the individual resilient flooring,
Resilient Floor Covering Institute (RFCI) Recommended
underlayment or adhesive manufacturer for specific recom-
Work Practices for Removal of Resilient Floor Coverings
mendations. Manufacturer’s instructions supercede the recom-
6
(January 1998)
mendations included in this practice.
Lead-Based Paint: Interim Guidelines for Hazard Identifi-
1.4 SeeSupplementaryRequirementsfor“SelectWarnings”
cation andAbatement in Public and Indian housing (1991
that have been provided.
7
revised)
1.5 The values stated in inch/pound units are to be regarded
as standard. The metric units in parentheses are for reference
3. Terminology
only.
3.1 Definitions used in this standard shall be in accordance
1.6 This standard does not purport to address all of the
with Terminology F 141.
safety concerns, if any, associated with its use. It is the
3.2 Definitions of Terms Specific to This Standard:
responsibility of the user of this standard to establish appro-
3.2.1 fully adhered flooring—resilient flooring which has
priate safety and health practices and determine the applica-
adhesive under the entire product, bonding it to the underlay-
bility of regulatory limitations prior to use.
ment surface.
2. Referenced Documents 3.2.2 non fully adhered flooring—resilient flooring that may
2
be loose laid, in which no adhesive is utilized, or partially
2.1 ASTM Standards:
bonded to the surface of the underlayment, typically at seams
C 1278/C 1278M Specification for Fiber-Reinforced Gyp-
or the surrounding perimeter, or both, of the product.
sum Panel
C 1288 Specification for Discrete Non-Asbestos Fiber-
4. Significance and Use
Cement Interior Substrate Sheets
4.1 This practice provides minimum recommendations for
F 141 Terminology Relating to Resilient Floor Coverings
theinstallationandpreparationofwood-based,fiber-reinforced
2.2 ANSI Standards:
3
Available fromAmerican National Standards Institute (ANSI), 25 W. 43rd St.,
1
ThisguideisunderthejurisdictionofASTMCommitteeF06onResilientFloor 4th Floor, New York, NY 10036, www.ansi.org.
4
Coverings and is the direct responsibility of Subcommittee F06.40 on Special Available from National Institute of Standards and Technology (NIST), 100
Properties. Bureau Dr., Stop 3460, Gaithersburg, MD 20899-3460, www.nist.gov.
5
Current edition approved March 1, 2004. Published April 2004. Originally Available from APA—The Engineered Wood Association, 7011 S. 19th St.,
approved in 1994. Last previous edition approved in 2003 as F 1482 – 03. Tacoma, WA 98466–5399, www.apawood.org.
2 6
For referenced ASTM standards, visit the ASTM website, www.astm.org, or Resilient Floor Covering Institute, 401 E. Jefferson Suite 102 Rockville, MD
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM 20850, www.rfci.com.
7
Standards volume information, refer to the standard’s Document Summary page on U.S. Department of Housing & Urban Development, Washington, DC,
the ASTM website. www.hud.gov.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1
---------------------- Page: 1 ----------------------
F1482–04
gypsum and fiber-cement panel underlayments suitable to literature offers specific recommendations or prohibitions as to
receive resilient floor coverings. Actual requirements for ma- types of underlayments for use under their flooring products.
terials to be used, mixtures, and other details are g
...