F06.40 - Practices
Practices
General Information
SIGNIFICANCE AND USE
4.1 There is typically a higher concentration of soluble alkali salts in the surface region of a concrete slab due to the initial bleeding process of a freshly placed concrete slab. If after a resilient floor covering material is installed there is sufficient moisture within the slab to place these salts into solution a potentially damaging high pH solution can develop beneath the installed material.
4.2 Results obtained through the use of this guide indicate the comparative pH of reagent water placed on properly prepared concrete slab surfaces only at the time of the procedure and in the specific locations evaluated.
4.3 If pre-installation surface pH evaluation is required by the manufacturer of the resilient flooring, adhesive, patching/underlayment products or project specifications, their instructions and limitations should be consulted.
SCOPE
1.1 This guide discusses procedures that may be used for evaluating the comparative change in pH of reagent water placed on the surface of a properly prepared concrete slab surface.
1.2 This guide is intended to be used in conjunction with the flat surface electrode pH meter manufacturer’s calibration procedures, operation instructions, and interpretive data where available.
1.3 This guide is intended to be used in conjunction with the pH paper manufacturer’s instructions, product shelf life, and interpretive data where available.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use Some specific hazards statements are given in Section 9 on Hazards.
1.6 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Guide4 pagesEnglish language
- Guide4 pagesEnglish language
SIGNIFICANCE AND USE
4.1 Moisture permeating from concrete substrates can detrimentally affect the performance of resilient floor covering systems. All resilient flooring and adhesive manufacturers have a maximum acceptable level of moisture in which their products can perform satisfactorily. If pre-installation moisture tests indicate that the moisture level is unacceptable for the specified floor covering to be installed, one option is to apply a topical treatment to the concrete substrate surface to mitigate the moisture condition. Experience has shown that certain types of membrane-forming moisture mitigation systems have more desirable properties and successful performance than others. Requirements for membrane-forming moisture mitigation systems to be used, and other related details, are generally included as part of the project plans, or specification details, and may vary from the minimum recommendations set forth in this practice.
4.2 This practice is intended for use after it has been determined that a floor moisture condition exceeds the resilient floor covering or adhesive manufacturer’s requirements, or both, as tested according to Test Methods F1869, F2170, and F2420.
4.3 Membrane-forming moisture mitigation systems are not intended for use over gypsum-based substrates or other moisture sensitive substrates.
SCOPE
1.1 This practice covers the properties, application, and performance of a two-component resin based membrane-forming moisture mitigation system to high moisture concrete substrates prior to the installation of resilient flooring.
1.2 This practice includes recommendations for the preparation of the concrete surface to receive a two-component resin based membrane-forming moisture mitigation system.
1.3 This practice does not supersede written instructions of the two-component resin based membrane-forming moisture mitigation system manufacturer, the resilient flooring manufacturer, underlayment manufacturer, the adhesive manufacturer, or other components of the finish flooring system, or combinations thereof. Users of this practice shall review manufacturer’s technical data sheets and installation instructions for compatibility of system components.
1.4 The following membrane-forming or non membrane-forming moisture mitigation systems are not included in the scope of this practice:
1.4.1 Moisture mitigation systems that chemically react with any constituent of the concrete to form a gel or crystalline substance within the concrete.
1.4.2 Penetrating, water- or solvent-based compounds that do not form a continuous membrane on the concrete surface.
1.4.3 Water-based membrane-forming moisture mitigation systems are not included in the scope of this document.
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard4 pagesEnglish language
SIGNIFICANCE AND USE
4.1 Use this test method to obtain a quantitative value indicating the rate of moisture vapor emission from the surface of a concrete floor and whether or not that floor is acceptable to receive resilient floor covering. The moisture vapor emission rate only reflects the condition of the concrete floor at the time of the test. All concrete subfloors emit some amount of moisture in vapor form. Concrete moisture emission is a natural process driven by environmental conditions. All floor coverings are susceptible to failure from excessive moisture vapor emissions. The moisture vapor emitted from a concrete slab is measured in pounds. This measurement is the equivalent weight of water evaporating from 1000 ft2 of concrete surface in a 24-h period. The calcium chloride moisture test has been the industry standard for making this determination and is a practical, well-established and accepted test of dynamic moisture. It will produce quantified results directly applicable to flooring manufacturer's specifications. The results obtained reflect the condition of the concrete floor surface at the time of testing and may not indicate future conditions.
SCOPE
1.1 This test method covers the quantitative determination of the rate of moisture vapor emitted from below-grade, on-grade, and above-grade (suspended) bare concrete floors.
1.2 This test shall not be used to evaluate the rate of moisture vapor emitted by gypsum concrete or floors containing lightweight aggregate.
1.3 This test shall not be used to evaluate moisture vapor emissions over coatings on concrete or through reactive penetrants or over patching or leveling compounds.
1.4 This quantity of moisture shall be expressed as the rate of moisture vapor emission, measured in pounds of moisture over a 1000 ft2 area during a 24-h period.
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard4 pagesEnglish language
- Standard4 pagesEnglish language
SIGNIFICANCE AND USE
4.1 Seams in some resilient flooring are heat sealed to prevent openings from forming between cut edges and to prevent penetrations of dirt, liquids, etc., into the seams. Decorative appearances may also be achieved using contrasting heat weld thread (rod).
SCOPE
1.1 This practice covers the instructions and precautions to be observed to ensure satisfactory performance of seams in resilient flooring sealed by the heat weld method.
1.2 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. See precaution information in 6.1.
1.3 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard2 pagesEnglish language
- Standard2 pagesEnglish language
SIGNIFICANCE AND USE
5.1 Moisture in concrete floor slabs affects the performance of flooring systems such as resilient, wood, and textile floor coverings and coatings. Manufacturers of such systems generally require moisture testing be performed before installation of coverings on floor slabs and screeds. The measurement of sub-surface comparative moisture condition in the upper 1.0 in. (25.4 mm) stratum of a concrete slab with a non-destructive moisture meter is one such method.
5.2 Excessive moisture in floor slabs after installation can cause floor covering system failures such as delamination, bonding failure, deterioration of finish flooring and coatings, and microbial growth.
5.3 5.3 Comparative moisture content tests indicate the moisture in the slab, which is usually referenced to the percentage of dry weight. That is:
Results indicate conditions at the time of the test.
5.4 Methods of meter calibration and factors affecting equilibration are described in Section 8.
SCOPE
1.1 This guide focuses on obtaining the comparative moisture condition within the upper 1.0 in. (25.4 mm) stratum in concrete, gypsum, anhydrite floor slabs and screeds for field tests. Due to the wide variation of material mixtures and additives used in floor slabs and screeds, this methodology may not be appropriate for all applications. See 1.2 through 1.8 and Section 11. Where appropriate or when specified, use further testing as outlined in Test Methods F1869 or F2170 before installing a resilient floor covering.
1.2 This guide is intended for use to determine if there are moisture-related conditions existing on, or in, the floor slabs that could adversely impact the successful application and performance of resilient flooring products.
1.3 This guide may be used to aid in the diagnosis of failures of installed resilient flooring.
1.4 This guide is intended to be used in conjunction with meter manufacturer’s operation instructions and interpretive data where available.
1.5 Where possible or when results need to be quantified, use this guide to determine where additional testing such as Test Methods F1869 or F2170 as specified to characterize the floor slab and the test area environment for moisture, humidity and temperature conditions.
1.6 This guide may not be suitable for areas that have surface applied moisture migration systems, curing compounds or coatings that cannot be removed or cleaned off sufficiently to allow the moisture to move upwards through the slab. For a floor slab of 6 in. (150 mm) plus thickness, low porosity slabs, slabs with no vapor retarder installed, and slabs where the above surface environmental conditions can have a greater than normal influence on the moisture reduction gradient of the floor slab or screed, consider Test Method F2170 (below surface in situ rh method) as a more suitable test method under these circumstances.
1.7 This guide is not intended to provide quantitative results as a basis for acceptance of a floor for installation of moisture sensitive flooring finishes systems. Test Methods F1869 or F2170 provide quantitative information for determining if moisture levels are within specific limits. Results from this guide do not provide vital information when evaluating thick slabs, slabs without effective vapor retarders directly under the slab, lightweight aggregate concrete floors, and slabs with curing compound or sealers on the surface.
1.8 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.9 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use...
- Guide6 pagesEnglish language
- Guide6 pagesEnglish language
SIGNIFICANCE AND USE
4.1 Seams in some sheet resilient flooring are sealed to prevent openings from forming between cut edges and prevent penetrations of dirt, liquids, etc., into the seams.
SCOPE
1.1 This practice covers the instructions and precautions to be observed to ensure satisfactory performance of seams in sheet resilient flooring sealed with liquid seam sealers.
1.2 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.3 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard2 pagesEnglish language
SIGNIFICANCE AND USE
5.1 The ability of a substrate surface to readily absorb water is a key indicator in determining how to correctly install many types of flooring adhesives, primers, self-leveling underlayments, and other products. Several flooring industry publications such as CRI’s Carpet Installation Standard, RFCI’s Recommended Installation Practice for Homogenous Sheet Flooring, Fully-Adhered, as well as most flooring, adhesive, primer, and underlayment manufacturers reference substrate surface porosity criteria in their application instructions since this directly impacts the spread rate of directly applied material, the open time, and other critical installation factors.
5.2 Installing flooring products over low or non-absorptive (sometimes referred to as “non-porous”) substrates such as densely machine-troweled concrete, mature and well-hydrated concrete, existing resilient flooring, polymer terrazzo and others may require adjustments to the surface preparation method or product selection to ensure a successful installation.
5.3 Use this practice to obtain a qualitative assessment of substrate water absorption (porosity) and whether or not that substrate should be regarded as porous/absorptive or non-porous/non-absorptive as these terms relate to the installation of resilient floor coverings, adhesives, self-leveling underlayments, primers, and other products. This practice will produce results directly applicable to determining appropriate surface preparation requirements in accordance with manufacturer’s specifications, but it is in no way meant to replace published manufacturer’s literature regarding the determination of substrate water absorption (porosity) and the impact such has, if any, on substrate preparation requirements and on the installation of their respective materials.
5.4 Substrates that evidence immediate absorption, are chalky or dusty, or have varying degrees of absorption may require priming or other additional surface preparation prior to subseq...
SCOPE
1.1 This practice covers the determination of whether or not a substrate surface, in lieu of written instruction from a product manufacturer, is considered porous or non-porous prior to the installation of resilient flooring materials.
1.2 Although carpet tiles, carpet, wood flooring, coatings, films, paints, self-leveling and trowel-grade underlayments, primers, and other associated products are not specifically intended to be included in the category of resilient floor coverings, the procedures included in this practice may be useful for assessing the substrate water absorption for substrates to receive such materials.
1.3 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. Some specific hazards statements are given in Section 6 on Hazards.
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard4 pagesEnglish language
- Standard4 pagesEnglish language
ABSTRACT
This practice covers the procedure for determining the acceptability of concrete floors for the installation of resilient flooring. It also includes suggestions for ensuring that the constructed concrete floor is acceptable for such installations but does not cover tests for adequacy of the concrete floor to perform structural requirements. A permanent, effective moisture vapor retarder, of the specified thickness and permeance, is required under all on- or below-grade concrete floors. Concrete floors for resilient floorings should be permanently dry, clean, smooth, structurally sound, and free of substances that may prevent adhesive bonding. Surface cracks, grooves, depression, control joints or other non-moving joints, and other irregularities should be filled or smoothed with latex patching or a recommended underlayment compound. The surface of the floor should be cleaned by scraping, brushing, vacuuming, or any other method. All concrete slabs should be tested for moisture regardless of age or grade level while all concrete floors should be tested for pH before installing resilient flooring.
SCOPE
1.1 This practice covers the determination of the acceptability of a concrete floor for the installation of resilient flooring.
1.2 This practice includes suggestions for the construction of a concrete floor to ensure its acceptability for installation of resilient flooring.
1.3 This practice does not cover the adequacy of the concrete floor to perform its structural requirements.
1.4 This practice covers the necessary preparation of concrete floors prior to the installation of resilient flooring.
1.5 This practice does not supersede in any manner the resilient flooring or adhesive manufacturer's written instructions. Consult the individual manufacturer for specific recommendations.
1.6 Although carpet tiles, carpet, wood flooring, coatings, films, and paints are not specifically intended to be included in the category of resilient floor coverings, the procedures included in this practice may be useful for preparing concrete floors to receive such finishes.
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. See 4.1.1, 7.1.1, and 7.1.2 for specific warning statements.
1.8 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard10 pagesEnglish language
- Standard10 pagesEnglish language
SIGNIFICANCE AND USE
4.1 This practice provides minimum recommendations for the installation of thick poured gypsum concrete floor underlayments suitable to receive resilient floor coverings. This practice establishes the proper preparation, installation and quality control for thick poured gypsum concrete floor underlayments.
4.2 Actual requirements for thick poured gypsum concrete underlayments are generally included as part of project plans or specifications and may vary from the recommendations set forth in this practice. Project plans or specifications, or both, shall supersede the recommendations set forth in this practice.
SCOPE
1.1 This practice covers the installation and preparation of the thick poured gypsum concrete underlayments over wood structural panel subfloors in commercial structures or over concrete floors in commercial structures and the preparation of the thick poured gypsum concrete underlayment surface prior to the installation of resilient flooring in commercial buildings.
1.2 This practice covers the factors that are required to be controlled while installing thick poured gypsum concrete underlayment as a base for resilient flooring.
1.3 This practice does not cover the structural adequacy of the wood structural panel subfloor or concrete subfloor. The structural integrity of assemblies is governed by local building codes.
1.4 This practice does not supersede in any manner the thick poured gypsum concrete underlayment manufacturers, adhesive manufacturer’s or resilient flooring manufacturer’s written instructions. Consult the individual manufacturer for specific recommendations.
1.5 Thick poured gypsum concrete underlayments are not suitable for use on concrete slabs on ground due to potential moisture problems arising from moisture intrusion, unless an adequate vapor retarder or vapor barrier is present directly beneath the concrete subfloor.
1.6 The values stated in inch-pound units are to be regarded as standard. The values stated in parentheses are approximate mathematical conversions to SI units, which are provided for information only.
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.8 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard3 pagesEnglish language
SIGNIFICANCE AND USE
4.1 This practice provides minimum recommendations for preparing and smoothing panel underlayments, thick poured gypsum concrete underlayments, thick poured lightweight cellular concrete underlayments and concrete subfloors with patching compounds. Actual requirements for materials to be used, mixtures, and other details are generally included as part of the project plans or specification details and may vary from the minimum recommendations set forth in this practice.
SCOPE
1.1 This practice includes recommendations for preparing and smoothing panel underlayments, gypsum concrete and concrete subfloors with patching compounds upon which resilient flooring may be installed.
1.2 This practice does not cover the adequacy of the subfloor assembly to perform its structural requirements, which is governed by local building codes.
1.3 This practice does not supersede in any manner the resilient flooring, underlayment or adhesive manufacturer’s written instructions. Consult the individual resilient flooring, underlayment or adhesive manufacturer for specific recommendations.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.6 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard4 pagesEnglish language
SIGNIFICANCE AND USE
4.1 The effect of dynamic rolling load over resilient floor covering system is important since the resistance reflects the ability of a resilient floor covering system to properly perform under specific use or condition.
4.2 Excessive rolling load over an installed resilient floor covering may cause floor covering system failures such as bond failure, delamination, and finish or coating deteriorations.
4.3 The effect of dynamic rolling load shall be measured by qualitative evaluation comparing the tested assembly with a standard assembly.
SCOPE
1.1 This practice covers the determination of the effect of dynamic rolling load over a resilient floor covering.
1.2 This practice is intended to be used by resilient, adhesive and underlayment manufacturers to measure the impact of a dynamic rolling load over a specific product or a combination of products.
1.3 This practice may be used to evaluate the performance of joints (sealed or welded) in the resilient floor covering.
1.4 This practice may be used to aid in the diagnosis of a specific assembly performance and provide comparative evaluation.
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard4 pagesEnglish language
- Standard4 pagesEnglish language
SIGNIFICANCE AND USE
4.1 This practice provides minimum recommendations for the installation and preparation of wood-based, fiber-reinforced gypsum and fiber-cement panel underlayments suitable to receive resilient floor coverings. Actual requirements for materials to be used, mixtures, and other details are generally included as part of project plans or specification detail and may vary from the minimum recommendations set forth in this practice.
SCOPE
1.1 This practice includes recommendations for the installation of panel type underlayments including wood based, fiber reinforced gypsum and fiber-cement panel underlayment/subfloor assemblies upon which resilient flooring may be installed.
1.2 The structural integrity of subfloor assemblies is governed by local building codes.
1.3 This practice does not supersede in any manner the resilient flooring, underlayment or adhesive manufacturer's written instructions. Consult the individual resilient flooring, underlayment or adhesive manufacturer for specific recommendations. Manufacturer's instructions supercede the recommendations included in this practice.
1.4 See Supplementary Requirements for “Select Warnings” that have been provided.
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard5 pagesEnglish language
- Standard5 pagesEnglish language
SIGNIFICANCE AND USE
4.1 This practice provides minimum recommendations for the installation of self-leveling underlayments suitable to receive resilient floor coverings. This practice establishes the proper preparation of the subfloor, and installation methods and quality control requirements for self-leveling underlayments. This practice addresses any necessary preparation of the self-leveling underlayment’s surface prior to the installation of floor coverings.
4.2 Actual requirements for self-leveling underlayments are generally included as part of project plans or specifications and may vary from the recommendations set forth in this practice. Provisions in the project documents at variance with this practice shall take precedence.
SCOPE
1.1 This practice covers the installation of self-leveling underlayments, which may include a priming system, over solid wood, wood structural panel subfloors, over concrete, and over certain solidly bonded existing flooring systems such as epoxy floors, ceramic and natural stone tiles, terrazzo, metal subfloors and foils such as steel, copper and lead, solidly bonded patching and other leveling materials as well as properly prepared non water-soluble adhesive residues as recommended by the underlayment manufacturer. This practice also covers the preparation of the self-leveling underlayment’s surface prior to the installation of resilient flooring.
1.2 This practice points out the factors that are required to be controlled while installing a self-leveling underlayment to be used as a substrate for resilient flooring.
1.3 This practice does not cover the structural adequacy of the subfloor. The structural integrity of assemblies is governed by local building codes and may be superseded by the resilient flooring manufacturer's and the self-leveling underlayment manufacturer’s requirements.
1.4 This practice does not supersede the self-leveling underlayment manufacturer’s, adhesive manufacturer’s or resilient flooring manufacturer’s written instructions. Consult the individual manufacturer for specific recommendations.
1.5 Some self-leveling underlayments are not suitable for use on concrete slabs on or below grade due to potential moisture problems arising from moisture intrusion. However, most of the self-leveling underlayments may be suitable for use on and below grade if an adequate and effective vapor retarder or vapor barrier is present directly beneath the concrete slab or an effective moisture remediation system has been installed beneath the surface of the self-leveling underlayment. Consult the manufacturer of the self-leveling underlayment and flooring system for specific recommendations.
1.6 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.7 This practice does purport to address the necessity for or the safe or correct removal of asbestos containing materials. Breathing of asbestos dust is hazardous. Asbestos and asbestos products present demonstrated health risks for users and for those with whom they come into contact. In addition to other precautions, when working with asbestos-cement products, minimize the dust that results. For information on the safe use of chrysoltile asbestos, refer to “Safe Use of Chrysotile Asbestos: A Manual on Preventive and Control Measures.”2
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standar...
- Standard5 pagesEnglish language
- Standard5 pagesEnglish language
SIGNIFICANCE AND USE
5.1 Excessive moisture in floor slabs after floor covering has been installed can cause floor covering system failures such as debonding, peaking and deterioration of finish flooring and coatings and microbial growth.
5.2 Manufacturers of such systems generally require moisture testing to be performed before installation on concrete. Internal relative humidity testing is one such method.
5.3 Moisture test results indicate the moisture condition of the slab only at the time of the test and in the specific locations tested.
SCOPE
1.1 This test method covers the quantitative determination of percent relative humidity in concrete slabs for field or laboratory tests.
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
Specific warnings are given in Section 7, 10.3.2, and 10.4.4.
1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard7 pagesEnglish language
- Standard7 pagesEnglish language
SIGNIFICANCE AND USE
5.1 Any individual performing a mat bond evaluation should either be a qualified installer or a trained and experienced evaluator of resilient flooring and adhesive bond strength.
5.2 This practice should not be considered mandatory, except when required or specified by the end user, general contractor and architect, flooring contractor, adhesive manufacturer(s), underlayment manufacturer(s) or flooring manufacturer(s).
5.2.1 Typically, this practice is only recommended or required if products from a different manufacturer(s) are being used in combinations not experienced before or if the substrate preparation or application method is in question.
5.3 The number of mat bond evaluation(s) should be selected that is appropriate for the project and be representative of each type of substrate, including trenches, grade, type of flooring, and ambient conditions. The number may also be determined by the responsible party or specified by the end user, general contractor and architect, flooring contractor, adhesive manufacturer(s), underlayment manufacturer(s) or flooring manufacturer(s).
5.4 All mat bond evaluation(s) conducted shall have the results recorded within report, including photographs (see A1.11).
5.5 There are many factors that may influence the outcome of mat bond evaluation(s). Therefore, it is required to follow each manufacturer(s) installation/application instructions for every product used including open, curing, drying time, and the length of time required prior to evaluation(s)s.
5.6 Each step of the process must be conducted only at a time when the subfloor and ambient conditions comply with the requirements defined by all of the relevant manufacturer(s) written installation instructions or Practices F710, F1482, F2419, F2471, F2678, F2873, F3010, or combinations thereof.
SCOPE
1.1 This practice is designed to provide a short-term qualitative evaluation of the effectiveness and compatibility of the composite layers for flexible and fully adhered resilient flooring installation(s). Aspects of the resilient flooring assembly to be evaluated may include concrete surface profile (CSP), surface preparation, a topical moisture mitigation system, underlayment product(s), primer(s), application and the installation of the resilient flooring material itself. Aspects such as surface profile, surface cleanliness, surface porosity, the application method(s), and the open, curing, and drying times of each layer of the flooring system can be assessed using this practice prior to the actual full-scale installation taking place.
1.1.1 This practice is not intended for use with liquid applied, loose laid or perimeter fixed, or rigid resilient flooring products.
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. See Section 6 for specific Hazards statements.
1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard7 pagesEnglish language
SIGNIFICANCE AND USE
4.1 This practice provides minimum recommendations for the installation of thick poured lightweight cellular concrete floor underlayments suitable to receive resilient floor coverings. This practice establishes the proper preparation, installation and quality control for thick poured lightweight cellular concrete floor underlayments.
4.2 Actual requirements for thick poured lightweight cellular concrete underlayments are generally included as part of project plans or specifications and may vary from the recommendations set forth in this practice. Project plans or specifications, or both, shall supersede the recommendations set forth in this practice.
SCOPE
1.1 This practice covers the installation and preparation of the thick poured lightweight cellular concrete underlayments over wood structural panel subfloors in commercial structures or over concrete floors in commercial structures and the preparation of the thick poured lightweight cellular concrete underlayment surface prior to the installation of resilient flooring in commercial buildings.
1.2 This practice points out the factors that are required to be controlled while installing thick poured lightweight cellular concrete underlayment as a base for resilient flooring.
1.3 This practice does not cover the structural adequacy of the wood structural panel subfloor or concrete subfloor. The structural integrity of assemblies is governed by local building codes.
1.4 This practice does not supercede the thick poured lightweight cellular concrete underlayment manufacturers', adhesive manufacturers' or resilient flooring manufacturers' written instructions. Consult the individual manufacturer for specific recommendations.
1.5 Thick poured lightweight cellular concrete underlayments are not suitable for use on concrete slabs on ground due to potential moisture problems arising from moisture intrusion, unless an adequate vapor retarder or vapor barrier is present directly beneath the concrete subfloor.
1.6 The values stated in inch-pound units are to be regarded as standard. The values stated in parentheses are mathematical conversions to SI Units, which are provided for information only.
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.8 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard4 pagesEnglish language
- Standard4 pagesEnglish language
SIGNIFICANCE AND USE
4.1 There is typically a higher concentration of soluble alkali salts in the surface region of a concrete slab due to the initial bleeding process of a freshly placed concrete slab. If after a resilient floor covering material is installed there is sufficient moisture within the slab to place these salts into solution a potentially damaging high pH solution can develop beneath the installed material.
4.2 Results obtained through the use of this guide indicate the comparative pH of reagent water placed on properly prepared concrete slab surfaces only at the time of the procedure and in the specific locations evaluated.
4.3 If pre-installation surface pH evaluation is required by the manufacturer of the resilient flooring, adhesive, patching/underlayment products or project specifications, their instructions and limitations should be consulted.
SCOPE
1.1 This guide covers procedures that may be used for evaluating the comparative change in pH of reagent water placed on the surface of a properly prepared concrete slab surface.
1.2 This guide is intended to be used in conjunction with the flat surface electrode pH meter manufacturer’s calibration procedures, operation instructions, and interpretive data where available.
1.3 This guide is intended to be used in conjunction with the pH paper manufacturer’s instructions, product shelf life, and interpretive data where available.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use Some specific hazards statements are given in Section 9 on Hazards.
1.6 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Guide4 pagesEnglish language
- Guide4 pagesEnglish language
SIGNIFICANCE AND USE
4.1 There is typically a higher concentration of soluble alkali salts in the surface region of a concrete slab due to the initial bleeding process of a freshly placed concrete slab. If after a resilient floor covering material is installed there is sufficient moisture within the slab to place these salts into solution a potentially damaging high pH solution can develop beneath the installed material.
4.2 Results obtained through the use of this guide indicate the comparative pH of reagent water placed on properly prepared concrete slab surfaces only at the time of the procedure and in the specific locations evaluated.
4.3 If pre-installation surface pH evaluation is required by the manufacturer of the resilient flooring, adhesive, patching/underlayment products or project specifications, their instructions and limitations should be consulted.
SCOPE
1.1 This guide discusses procedures that may be used for evaluating the comparative change in pH of reagent water placed on the surface of a properly prepared concrete slab surface.
1.2 This guide is intended to be used in conjunction with the flat surface electrode pH meter manufacturer’s calibration procedures, operation instructions, and interpretive data where available.
1.3 This guide is intended to be used in conjunction with the pH paper manufacturer’s instructions, product shelf life, and interpretive data where available.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use Some specific hazards statements are given in Section 9 on Hazards.
1.6 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Guide4 pagesEnglish language
- Guide4 pagesEnglish language
- Guide4 pagesEnglish language
SIGNIFICANCE AND USE
4.1 There is typically a higher concentration of soluble alkali salts in the surface region of a concrete slab due to the initial bleeding process of a freshly placed concrete slab. If after a resilient floor covering material is installed there is sufficient moisture within the slab to place these salts into solution a potentially damaging high pH solution can develop beneath the installed material.
4.2 Results obtained through the use of this guide indicate the comparative pH of reagent water placed on properly prepared concrete slab surfaces only at the time of the procedure and in the specific locations evaluated.
4.3 If pre-installation surface pH evaluation is required by the manufacturer of the resilient flooring, adhesive, patching/underlayment products or project specifications, their instructions and limitations should be consulted.
SCOPE
1.1 This guide discusses procedures that may be used for evaluating the comparative change in pH of reagent water placed on the surface of a properly prepared concrete slab surface.
1.2 This guide is intended to be used in conjunction with the flat surface electrode pH meter manufacturer’s calibration procedures, operation instructions, and interpretive data where available.
1.3 This guide is intended to be used in conjunction with the pH paper manufacturer’s instructions, product shelf life, and interpretive data where available.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use Some specific hazards statements are given in Section 9 on Hazards.
1.6 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Guide4 pagesEnglish language
SIGNIFICANCE AND USE
5.1 Moisture in concrete floor slabs affects the performance of flooring systems such as resilient, wood, and textile floor coverings and coatings. Manufacturers of such systems generally require moisture testing be performed before installation of coverings on floor slabs and screeds. The measurement of sub-surface comparative moisture condition in the upper 1.0 in. (25.4 mm) stratum of a concrete slab with a non-destructive moisture meter is one such method.
5.2 Excessive moisture in floor slabs after installation can cause floor covering system failures such as delamination, bonding failure, deterioration of finish flooring and coatings, and microbial growth.
5.3 5.3 Comparative moisture content tests indicate the moisture in the slab, which is usually referenced to the percentage of dry weight. That is:
Results indicate conditions at the time of the test.
5.4 Methods of meter calibration and factors affecting equilibration are described in Section 8.
SCOPE
1.1 This guide focuses on obtaining the comparative moisture condition within the upper 1.0 in. (25.4 mm) stratum in concrete, gypsum, anhydrite floor slabs and screeds for field tests. Due to the wide variation of material mixtures and additives used in floor slabs and screeds, this methodology may not be appropriate for all applications. See 1.2 through 1.8 and Section 11. Where appropriate or when specified, use further testing as outlined in Test Methods F1869 or F2170 before installing a resilient floor covering.
1.2 This guide is intended for use to determine if there are moisture-related conditions existing on, or in, the floor slabs that could adversely impact the successful application and performance of resilient flooring products.
1.3 This guide may be used to aid in the diagnosis of failures of installed resilient flooring.
1.4 This guide is intended to be used in conjunction with meter manufacturer’s operation instructions and interpretive data where available.
1.5 Where possible or when results need to be quantified, use this guide to determine where additional testing such as Test Methods F1869 or F2170 as specified to characterize the floor slab and the test area environment for moisture, humidity and temperature conditions.
1.6 This guide may not be suitable for areas that have surface applied moisture migration systems, curing compounds or coatings that cannot be removed or cleaned off sufficiently to allow the moisture to move upwards through the slab. For a floor slab of 6 in. (150 mm) plus thickness, low porosity slabs, slabs with no vapor retarder installed, and slabs where the above surface environmental conditions can have a greater than normal influence on the moisture reduction gradient of the floor slab or screed, consider Test Method F2170 (below surface in situ rh method) as a more suitable test method under these circumstances.
1.7 This guide is not intended to provide quantitative results as a basis for acceptance of a floor for installation of moisture sensitive flooring finishes systems. Test Methods F1869 or F2170 provide quantitative information for determining if moisture levels are within specific limits. Results from this guide do not provide vital information when evaluating thick slabs, slabs without effective vapor retarders directly under the slab, lightweight aggregate concrete floors, and slabs with curing compound or sealers on the surface.
1.8 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.9 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use...
- Guide6 pagesEnglish language
- Guide6 pagesEnglish language
SIGNIFICANCE AND USE
4.1 Use this test method to obtain a quantitative value indicating the rate of moisture vapor emission from the surface of a concrete floor and whether or not that floor is acceptable to receive resilient floor covering. The moisture vapor emission rate only reflects the condition of the concrete floor at the time of the test. All concrete subfloors emit some amount of moisture in vapor form. Concrete moisture emission is a natural process driven by environmental conditions. All floor coverings are susceptible to failure from excessive moisture vapor emissions. The moisture vapor emitted from a concrete slab is measured in pounds. This measurement is the equivalent weight of water evaporating from 1000 ft2 of concrete surface in a 24-h period. The calcium chloride moisture test has been the industry standard for making this determination and is a practical, well-established and accepted test of dynamic moisture. It will produce quantified results directly applicable to flooring manufacturer's specifications. The results obtained reflect the condition of the concrete floor surface at the time of testing and may not indicate future conditions.
SCOPE
1.1 This test method covers the quantitative determination of the rate of moisture vapor emitted from below-grade, on-grade, and above-grade (suspended) bare concrete floors.
1.2 This test shall not be used to evaluate the rate of moisture vapor emitted by gypsum concrete or floors containing lightweight aggregate.
1.3 This test shall not be used to evaluate moisture vapor emissions over coatings on concrete or through reactive penetrants or over patching or leveling compounds.
1.4 This quantity of moisture shall be expressed as the rate of moisture vapor emission, measured in pounds of moisture over a 1000 ft2 area during a 24-h period.
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard4 pagesEnglish language
- Standard4 pagesEnglish language
ABSTRACT
This practice covers the procedure for determining the acceptability of concrete floors for the installation of resilient flooring. It also includes suggestions for ensuring that the constructed concrete floor is acceptable for such installations but does not cover tests for adequacy of the concrete floor to perform structural requirements. A permanent, effective moisture vapor retarder, of the specified thickness and permeance, is required under all on- or below-grade concrete floors. Concrete floors for resilient floorings should be permanently dry, clean, smooth, structurally sound, and free of substances that may prevent adhesive bonding. Surface cracks, grooves, depression, control joints or other non-moving joints, and other irregularities should be filled or smoothed with latex patching or a recommended underlayment compound. The surface of the floor should be cleaned by scraping, brushing, vacuuming, or any other method. All concrete slabs should be tested for moisture regardless of age or grade level while all concrete floors should be tested for pH before installing resilient flooring.
SCOPE
1.1 This practice covers the determination of the acceptability of a concrete floor for the installation of resilient flooring.
1.2 This practice includes suggestions for the construction of a concrete floor to ensure its acceptability for installation of resilient flooring.
1.3 This practice does not cover the adequacy of the concrete floor to perform its structural requirements.
1.4 This practice covers the necessary preparation of concrete floors prior to the installation of resilient flooring.
1.5 This practice does not supersede in any manner the resilient flooring or adhesive manufacturer's written instructions. Consult the individual manufacturer for specific recommendations.
1.6 Although carpet tiles, carpet, wood flooring, coatings, films, and paints ae not specifically intended to be included in the category of resilient floor coverings, the procedures included in this practice may be useful for preparing concrete floors to receive such finishes.
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. See 4.1.1, 7.1.1, and 7.1.2 for specific warning statements.
1.8 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard8 pagesEnglish language
- Standard8 pagesEnglish language
SIGNIFICANCE AND USE
4.1 This practice provides minimum recommendations for the installation of self-leveling underlayments suitable to receive resilient floor coverings. This practice establishes the proper preparation of the subfloor, and installation methods and quality control requirements for self-leveling underlayments. This practice addresses any necessary preparation of the self-leveling underlayment’s surface prior to the installation of floor coverings.
4.2 Actual requirements for self-leveling underlayments are generally included as part of project plans or specifications and may vary from the recommendations set forth in this practice. Provisions in the project documents at variance with this practice shall take precedence.
SCOPE
1.1 This practice covers the installation of self-leveling underlayments, which may include a priming system, over solid wood, wood structural panel subfloors, over concrete, and over certain solidly bonded existing flooring systems such as epoxy floors, ceramic and natural stone tiles, terrazzo, metal subfloors and foils such as steel, copper and lead, solidly bonded patching and other leveling materials as well as properly prepared non water-soluble adhesive residues as recommended by the underlayment manufacturer. This practice also covers the preparation of the self-leveling underlayment’s surface prior to the installation of resilient flooring.
1.2 This practice points out the factors that are required to be controlled while installing a self-leveling underlayment to be used as a substrate for resilient flooring.
1.3 This practice does not cover the structural adequacy of the subfloor. The structural integrity of assemblies is governed by local building codes and may be superseded by the resilient flooring manufacturer's and the self-leveling underlayment manufacturer’s requirements.
1.4 This practice does not supersede the self-leveling underlayment manufacturer’s, adhesive manufacturer’s or resilient flooring manufacturer’s written instructions. Consult the individual manufacturer for specific recommendations.
1.5 Some self-leveling underlayments are not suitable for use on concrete slabs on or below grade due to potential moisture problems arising from moisture intrusion. However, most of the self-leveling underlayments may be suitable for use on and below grade if an adequate and effective vapor retarder or vapor barrier is present directly beneath the concrete slab or an effective moisture remediation system has been installed beneath the surface of the self-leveling underlayment. Consult the manufacturer of the self-leveling underlayment and flooring system for specific recommendations.
1.6 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.7 This practice does purport to address the necessity for or the safe or correct removal of asbestos containing materials. Breathing of asbestos dust is hazardous. Asbestos and asbestos products present demonstrated health risks for users and for those with whom they come into contact. In addition to other precautions, when working with asbestos-cement products, minimize the dust that results. For information on the safe use of chrysoltile asbestos, refer to “Safe Use of Chrysotile Asbestos: A Manual on Preventive and Control Measures.”2
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standar...
- Standard5 pagesEnglish language
- Standard5 pagesEnglish language
SIGNIFICANCE AND USE
5.1 Excessive moisture in floor slabs after floor covering has been installed can cause floor covering system failures such as debonding, peaking and deterioration of finish flooring and coatings and microbial growth.
5.2 Manufacturers of such systems generally require moisture testing to be performed before installation on concrete. Internal relative humidity testing is one such method.
5.3 Moisture test results indicate the moisture condition of the slab only at the time of the test and in the specific locations tested.
SCOPE
1.1 This test method covers the quantitative determination of percent relative humidity in concrete slabs for field or laboratory tests.
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
Specific warnings are given in Section 7, 10.3.2, and 10.4.4.
1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard7 pagesEnglish language
- Standard7 pagesEnglish language
ABSTRACT
This practice covers the procedure for determining the acceptability of concrete floors for the installation of resilient flooring. It also includes suggestions for ensuring that the constructed concrete floor is acceptable for such installations but does not cover tests for adequacy of the concrete floor to perform structural requirements. A permanent, effective moisture vapor retarder, of the specified thickness and permeance, is required under all on- or below-grade concrete floors. Concrete floors for resilient floorings should be permanently dry, clean, smooth, structurally sound, and free of substances that may prevent adhesive bonding. Surface cracks, grooves, depression, control joints or other non-moving joints, and other irregularities should be filled or smoothed with latex patching or a recommended underlayment compound. The surface of the floor should be cleaned by scraping, brushing, vacuuming, or any other method. All concrete slabs should be tested for moisture regardless of age or grade level while all concrete floors should be tested for pH before installing resilient flooring.
SCOPE
1.1 This practice covers the determination of the acceptability of a concrete floor for the installation of resilient flooring.
1.2 This practice includes suggestions for the construction of a concrete floor to ensure its acceptability for installation of resilient flooring.
1.3 This practice does not cover the adequacy of the concrete floor to perform its structural requirements.
1.4 This practice covers the necessary preparation of concrete floors prior to the installation of resilient flooring.
1.5 This practice does not supersede in any manner the resilient flooring or adhesive manufacturer's written instructions. Consult the individual manufacturer for specific recommendations.
1.6 Although carpet tiles, carpet, wood flooring, coatings, films, and paints ae not specifically intended to be included in the category of resilient floor coverings, the procedures included in this practice may be useful for preparing concrete floors to receive such finishes.
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. See 4.1.1, 7.1.1, and 7.1.2 for specific warning statements.
1.8 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard8 pagesEnglish language
- Standard8 pagesEnglish language
ABSTRACT
This practice covers the procedure for determining the acceptability of concrete floors for the installation of resilient flooring. It also includes suggestions for ensuring that the constructed concrete floor is acceptable for such installations but does not cover tests for adequacy of the concrete floor to perform structural requirements. A permanent, effective moisture vapor retarder, of the specified thickness and permeance, is required under all on- or below-grade concrete floors. Concrete floors for resilient floorings should be permanently dry, clean, smooth, structurally sound, and free of substances that may prevent adhesive bonding. Surface cracks, grooves, depression, control joints or other non-moving joints, and other irregularities should be filled or smoothed with latex patching or a recommended underlayment compound. The surface of the floor should be cleaned by scraping, brushing, vacuuming, or any other method. All concrete slabs should be tested for moisture regardless of age or grade level while all concrete floors should be tested for pH before installing resilient flooring.
SCOPE
1.1 This practice covers the determination of the acceptability of a concrete floor for the installation of resilient flooring.
1.2 This practice includes suggestions for the construction of a concrete floor to ensure its acceptability for installation of resilient flooring.
1.3 This practice does not cover the adequacy of the concrete floor to perform its structural requirements.
1.4 This practice covers the necessary preparation of concrete floors prior to the installation of resilient flooring.
1.5 This practice does not supersede in any manner the resilient flooring or adhesive manufacturer's written instructions. Consult the individual manufacturer for specific recommendations.
1.6 Although carpet tiles, carpet, wood flooring, coatings, films, and paints ae not specifically intended to be included in the category of resilient floor coverings, the procedures included in this practice may be useful for preparing concrete floors to receive such finishes.
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. See 4.1.1, 7.1.1, and 7.1.2 for specific warning statements.
1.8 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard8 pagesEnglish language
- Standard8 pagesEnglish language
SIGNIFICANCE AND USE
4.1 This practice provides minimum recommendations for the installation of self-leveling underlayments suitable to receive resilient floor coverings. This practice establishes the proper preparation of the subfloor, and installation methods and quality control requirements for self-leveling underlayments. This practice addresses necessary preparation of the self-leveling underlayment’s surface prior to the installation of floor coverings.
4.2 Actual requirements for self-leveling underlayments are generally included as part of project plans or specifications and may vary from the recommendations set forth in this practice. Provisions in the project documents at variance with this practice shall take precedence.
SCOPE
1.1 This practice covers the installation of self-leveling underlayments, which may include a priming system, over solid wood, wood structural panel subfloors, over concrete, and over certain solidly bonded existing flooring systems such as epoxy floors, ceramic and natural stone tiles, terrazzo, metal subfloors and foils such as steel, copper and lead, solidly bonded patching and other leveling materials as well as properly prepared non water-soluble adhesive residues as recommended by the underlayment manufacturer. This practice also covers the preparation of the self-leveling underlayment’s surface prior to the installation of resilient flooring.
1.2 This practice points out the factors that are required to be controlled while installing a self-leveling underlayment to be used as a substrate for resilient flooring.
1.3 This practice does not cover the structural adequacy of the subfloor. The structural integrity of assemblies is governed by local building codes and may be superseded by the resilient flooring manufacturer's and the self-leveling underlayment manufacturer’s requirements.
1.4 This practice does not supersede the self-leveling underlayment manufacturer’s, adhesive manufacturer’s or resilient flooring manufacturer’s written instructions. Consult the individual manufacturer for specific recommendations.
1.5 Some self-leveling underlayments are not suitable for use on concrete slabs on or below grade due to potential moisture problems arising from moisture intrusion. However, most of the self-leveling underlayments may be suitable for use on and below grade if an adequate and effective vapor retarder or vapor barrier is present directly beneath the concrete slab or an effective moisture remediation system has been installed beneath the surface of the self-leveling underlayment. Consult the manufacturer of the self-leveling underlayment and flooring system for specific recommendations.
1.6 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.7 This practice does purport to address the necessity for or the safe or correct removal of asbestos containing materials. Breathing of asbestos dust is hazardous. Asbestos and asbestos products present demonstrated health risks for users and for those with whom they come into contact. In addition to other precautions, when working with asbestos-cement products, minimize the dust that results. For information on the safe use of chrysoltile asbestos, refer to “Safe Use of Chrysotile Asbestos: A Manual on Preventive and Control Measures.”2
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, ...
- Standard5 pagesEnglish language
- Standard5 pagesEnglish language
SIGNIFICANCE AND USE
4.1 Moisture permeating from concrete substrates can detrimentally affect the performance of resilient floor covering systems. All resilient flooring and adhesive manufacturers have a maximum acceptable level of moisture in which their products can perform satisfactorily. If pre-installation moisture tests indicate that the moisture level is unacceptable for the specified floor covering to be installed, one option is to apply a topical treatment to the concrete substrate surface to mitigate the moisture condition. Experience has shown that certain types of membrane-forming moisture mitigation systems have more desirable properties and successful performance than others. Requirements for membrane-forming moisture mitigation systems to be used, and other related details, are generally included as part of the project plans, or specification details, and may vary from the minimum recommendations set forth in this practice.
4.2 This practice is intended for use after it has been determined that a floor moisture condition exceeds the resilient floor covering or adhesive manufacturer’s requirements, or both, as tested according to Test Methods F1869, F2170, and F2420.
4.3 Membrane-forming moisture mitigation systems are not intended for use over gypsum-based substrates or other moisture sensitive substrates.
SCOPE
1.1 This practice covers the properties, application, and performance of a two-component resin based membrane-forming moisture mitigation system to high moisture concrete substrates prior to the installation of resilient flooring.
1.2 This practice includes recommendations for the preparation of the concrete surface to receive a two-component resin based membrane-forming moisture mitigation system.
1.3 This practice does not supersede written instructions of the two-component resin based membrane-forming moisture mitigation system manufacturer, the resilient flooring manufacturer, underlayment manufacturer, the adhesive manufacturer, or other components of the finish flooring system, or combinations thereof. Users of this practice shall review manufacturer’s technical data sheets and installation instructions for compatibility of system components.
1.4 The following membrane-forming or non membrane-forming moisture mitigation systems are not included in the scope of this practice:
1.4.1 Moisture mitigation systems that chemically react with any constituent of the concrete to form a gel or crystalline substance within the concrete.
1.4.2 Penetrating, water- or solvent-based compounds that do not form a continuous membrane on the concrete surface.
1.4.3 Water-based membrane-forming moisture mitigation systems are not included in the scope of this document.
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard4 pagesEnglish language
- Standard4 pagesEnglish language
- Standard4 pagesEnglish language
SIGNIFICANCE AND USE
4.1 Seams in some sheet resilient flooring are sealed to prevent openings from forming between cut edges and prevent penetrations of dirt, liquids, etc., into the seams.
SCOPE
1.1 This practice covers the instructions and precautions to be observed to ensure satisfactory performance of seams in sheet resilient flooring sealed with liquid seam sealers.
1.2 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.3 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard2 pagesEnglish language
- Standard2 pagesEnglish language
SIGNIFICANCE AND USE
5.1 Excessive moisture in floor slabs after floor covering has been installed can cause floor covering system failures such as debonding, peaking and deterioration of finish flooring and coatings and microbial growth.
5.2 Manufacturers of such systems generally require moisture testing to be performed before installation on concrete. Internal relative humidity testing is one such method.
5.3 Moisture test results indicate the moisture condition of the slab only at the time of the test and in the specific locations tested.
SCOPE
1.1 This test method covers the quantitative determination of percent relative humidity in concrete slabs for field or laboratory tests.
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
Specific warnings are given in Section 7, 10.3.2, and 10.4.4.
1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard7 pagesEnglish language
- Standard7 pagesEnglish language
SIGNIFICANCE AND USE
4.1 Seams in some resilient flooring are heat sealed to prevent openings from forming between cut edges and to prevent penetrations of dirt, liquids, etc., into the seams. Decorative appearances may also be achieved using contrasting heat weld thread (rod).
SCOPE
1.1 This practice covers the instructions and precautions to be observed to ensure satisfactory performance of seams in resilient flooring sealed by the heat weld method.
1.2 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. See precaution information in 6.1.
1.3 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard2 pagesEnglish language
- Standard2 pagesEnglish language
SIGNIFICANCE AND USE
4.1 This practice provides minimum recommendations for the installation of thick poured gypsum concrete floor underlayments suitable to receive resilient floor coverings. This practice establishes the proper preparation, installation and quality control for thick poured gypsum concrete floor underlayments.
4.2 Actual requirements for thick poured gypsum concrete underlayments are generally included as part of project plans or specifications and may vary from the recommendations set forth in this practice. Project plans or specifications, or both, shall supersede the recommendations set forth in this practice.
SCOPE
1.1 This practice covers the installation and preparation of the thick poured gypsum concrete underlayments over wood structural panel subfloors in commercial structures or over concrete floors in commercial structures and the preparation of the thick poured gypsum concrete underlayment surface prior to the installation of resilient flooring in commercial buildings.
1.2 This practice covers the factors that are required to be controlled while installing thick poured gypsum concrete underlayment as a base for resilient flooring.
1.3 This practice does not cover the structural adequacy of the wood structural panel subfloor or concrete subfloor. The structural integrity of assemblies is governed by local building codes.
1.4 This practice does not supersede in any manner the thick poured gypsum concrete underlayment manufacturers, adhesive manufacturer’s or resilient flooring manufacturer’s written instructions. Consult the individual manufacturer for specific recommendations.
1.5 Thick poured gypsum concrete underlayments are not suitable for use on concrete slabs on ground due to potential moisture problems arising from moisture intrusion, unless an adequate vapor retarder or vapor barrier is present directly beneath the concrete subfloor.
1.6 The values stated in inch-pound units are to be regarded as standard. The values stated in parentheses are approximate mathematical conversions to SI units, which are provided for information only.
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.8 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard3 pagesEnglish language
- Standard3 pagesEnglish language
ABSTRACT
This practice covers the procedure for determining the acceptability of concrete floors for the installation of resilient flooring. It also includes suggestions for ensuring that the constructed concrete floor is acceptable for such installations but does not cover tests for adequacy of the concrete floor to perform structural requirements. A permanent, effective moisture vapor retarder, of the specified thickness and permeance, is required under all on- or below-grade concrete floors. Concrete floors for resilient floorings should be permanently dry, clean, smooth, structurally sound, and free of substances that may prevent adhesive bonding. Surface cracks, grooves, depression, control joints or other non-moving joints, and other irregularities should be filled or smoothed with latex patching or a recommended underlayment compound. The surface of the floor should be cleaned by scraping, brushing, vacuuming, or any other method. All concrete slabs should be tested for moisture regardless of age or grade level while all concrete floors should be tested for pH before installing resilient flooring.
SCOPE
1.1 This practice covers the determination of the acceptability of a concrete floor for the installation of resilient flooring.
1.2 This practice includes suggestions for the construction of a concrete floor to ensure its acceptability for installation of resilient flooring.
1.3 This practice does not cover the adequacy of the concrete floor to perform its structural requirements.
1.4 This practice covers the necessary preparation of concrete floors prior to the installation of resilient flooring.
1.5 This practice does not supersede in any manner the resilient flooring or adhesive manufacturer's written instructions. Consult the individual manufacturer for specific recommendations.
1.6 Although carpet tiles, carpet, wood flooring, coatings, films, and paints ae not specifically intended to be included in the category of resilient floor coverings, the procedures included in this practice may be useful for preparing concrete floors to receive such finishes.
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. See 7.1, 7.1.1, and 7.1.2 for specific warning statements.
1.8 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard8 pagesEnglish language
- Standard8 pagesEnglish language
SIGNIFICANCE AND USE
5.1 Excessive moisture in floor slabs after floor covering has been installed can cause floor covering system failures such as debonding, peaking and deterioration of finish flooring and coatings and microbial growth.
5.2 Manufacturers of such systems generally require moisture testing to be performed before installation on concrete. Internal relative humidity testing is one such method.
5.3 Moisture test results indicate the moisture condition of the slab only at the time of the test and in the specific locations tested.
SCOPE
1.1 This test method covers the quantitative determination of percent relative humidity in concrete slabs for field or laboratory tests.
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
Specific warnings are given in Section 7, 10.3.2, and 10.4.4.
1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Standard6 pagesEnglish language
- Standard6 pagesEnglish language
SIGNIFICANCE AND USE
4.1 Use this test method to obtain a quantitative value indicating the rate of moisture vapor emission from the surface of a concrete floor and whether or not that floor is acceptable to receive resilient floor covering. The moisture vapor emission rate only reflects the condition of the concrete floor at the time of the test. All concrete subfloors emit some amount of moisture in vapor form. Concrete moisture emission is a natural process driven by environmental conditions. All floor coverings are susceptible to failure from excessive moisture vapor emissions. The moisture vapor emitted from a concrete slab is measured in pounds. This measurement is the equivalent weight of water evaporating from 1000 ft2 of concrete surface in a 24–h period. The calcium chloride moisture test has been the industry standard for making this determination and is a practical, well-established and accepted test of dynamic moisture. It will produce quantified results directly applicable to flooring manufacturer's specifications. The results obtained reflect the condition of the concrete floor surface at the time of testing and may not indicate future conditions.
SCOPE
1.1 This test method covers the quantitative determination of the rate of moisture vapor emitted from below-grade, on-grade, and above-grade (suspended) bare concrete floors.
1.2 This test shall not be used to evaluate the rate of moisture vapor emitted by gypsum concrete or floors containing lightweight aggregate.
1.3 This test shall not be used to evaluate moisture vapor emissions over coatings on concrete or through reactive penetrants or over patching or leveling compounds.
1.4 This quantity of moisture shall be expressed as the rate of moisture vapor emission, measured in pounds of moisture over a 1000 ft2 area during a 24-h period.
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices, and determine the applicability of regulatory limitations prior to use.
- Standard4 pagesEnglish language
- Standard4 pagesEnglish language
SIGNIFICANCE AND USE
5.1 The ability of a substrate surface to readily absorb water is a key indicator in determining how to correctly install many types of flooring adhesives, primers, self-leveling underlayments, and other products. Several flooring industry publications such as CRI’s Carpet Installation Standard, RFCI’s Recommended Installation Practice for Homogenous Sheet Flooring, Fully-Adhered, as well as most flooring, adhesive, primer, and underlayment manufacturers reference substrate surface porosity criteria in their application instructions since this directly impacts the spread rate of directly applied material, the open time, and other critical installation factors.
5.2 Installing flooring products over low or non-absorptive (sometimes referred to as “non-porous”) substrates such as densely machine-troweled concrete, mature and well-hydrated concrete, existing resilient flooring, polymer terrazzo and others may require adjustments to the surface preparation method or product selection to ensure a successful installation.
5.3 Use this practice to obtain a qualitative assessment of substrate water absorption (porosity) and whether or not that substrate should be regarded as porous/absorptive or non-porous/non-absorptive as these terms relate to the installation of resilient floor coverings, adhesives, self-leveling underlayments, primers, and other products. This practice will produce results directly applicable to determining appropriate surface preparation requirements in accordance with manufacturer’s specifications, but it is in no way meant to replace published manufacturer’s literature regarding the determination of substrate water absorption (porosity) and the impact such has, if any, on substrate preparation requirements and on the installation of their respective materials.
5.4 Substrates that evidence immediate absorption, are chalky or dusty, or have varying degrees of absorption may require priming or other additional surface preparation prior to subseq...
SCOPE
1.1 This practice covers the determination of whether or not a substrate surface, in lieu of written instruction from a product manufacturer, is considered porous or non-porous prior to the installation of resilient flooring materials.
1.2 Although carpet tiles, carpet, wood flooring, coatings, films, paints, self-leveling and trowel-grade underlayments, primers, and other associated products are not specifically intended to be included in the category of resilient floor coverings, the procedures included in this practice may be useful for assessing the substrate water absorption for substrates to receive such materials.
1.3 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. Some specific hazards statements are given in Section 6 on Hazards.
- Standard4 pagesEnglish language
SIGNIFICANCE AND USE
5.1 Excessive moisture in floor slabs after floor covering has been installed can cause floor covering system failures such as debonding, peaking and deterioration of finish flooring and coatings and microbial growth.
5.2 Manufacturers of such systems generally require moisture testing to be performed before installation on concrete. Internal relative humidity testing is one such method.
5.3 Moisture test results indicate the moisture condition of the slab only at the time of the test and in the specific locations tested.
SCOPE
1.1 This test method covers the quantitative determination of percent relative humidity in concrete slabs for field or laboratory tests.
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
Specific warnings are given in Section 7, 10.3.2, and 10.4.4.
- Standard6 pagesEnglish language
- Standard6 pagesEnglish language
SIGNIFICANCE AND USE
5.1 Moisture permeating from concrete floor slabs affects the performance of flooring systems such as resilient and textile floor coverings and coatings. Manufacturers of such systems generally require moisture testing to be performed before installation on concrete. Internal relative humidity testing is one such method.
5.2 Excessive moisture permeating from floor slabs after installation can cause floor covering system failures such as debonding and deterioration of finish flooring and coatings and microbial growth.
5.3 Moisture test results indicate the moisture condition of the slab only at the time of the test.
SCOPE
1.1 This test method covers the quantitative determination of percent relative humidity in concrete slabs for field or laboratory tests.
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
Specific warnings are given in Section 7, 10.3.2, and 10.4.4.
- Standard6 pagesEnglish language
- Standard6 pagesEnglish language
SIGNIFICANCE AND USE
5.1 Moisture permeating from concrete floor slabs affects the performance of flooring systems such as resilient and textile floor coverings and coatings. Manufacturers of such systems generally require moisture testing to be performed before installation on concrete. Internal relative humidity testing is one such method.
5.2 Excessive moisture permeating from floor slabs after installation can cause floor covering system failures such as debonding and deterioration of finish flooring and coatings and microbial growth.
5.3 Moisture test results indicate the moisture condition of the slab only at the time of the test.
SCOPE
1.1 This test method covers the quantitative determination of percent relative humidity in concrete slabs for field or laboratory tests.
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
Specific warnings are given in Section 7, 10.3.2, and 10.4.4.
- Standard6 pagesEnglish language
- Standard6 pagesEnglish language
SIGNIFICANCE AND USE
4.1 Use this test method to obtain a quantitative value indicating the rate of moisture vapor emission from the surface of a concrete floor and whether or not that floor is acceptable to receive resilient floor covering. The moisture vapor emission rate only reflects the condition of the concrete floor at the time of the test. All concrete subfloors emit some amount of moisture in vapor form. Concrete moisture emission is a natural process driven by environmental conditions. All floor coverings are susceptible to failure from excessive moisture vapor emissions. The moisture vapor emitted from a concrete slab is measured in pounds. This measurement is the equivalent weight of water evaporating from 1000 ft2 of concrete surface in a 24–h period. The calcium chloride moisture test has been the industry standard for making this determination and is a practical, well-established and accepted test of dynamic moisture. It will produce quantified results directly applicable to flooring manufacturer's specifications. The results obtained reflect the condition of the concrete floor surface at the time of testing and may not indicate future conditions.
SCOPE
1.1 This test method covers the quantitative determination of the rate of moisture vapor emitted from below-grade, on-grade, and above-grade (suspended) bare concrete floors.
1.2 This test shall not be used to evaluate the rate of moisture vapor emitted by gypsum concrete or floors containing lightweight aggregate.
1.3 This test shall not be used to evaluate moisture vapor emissions over coatings on concrete or through reactive penetrants or over patching or leveling compounds.
1.4 This quantity of moisture shall be expressed as the rate of moisture vapor emission, measured in pounds of moisture over a 1000 ft2 area during a 24-h period.
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices, and determine the applicability of regulatory limitations prior to use.
- Standard4 pagesEnglish language
- Standard4 pagesEnglish language
SIGNIFICANCE AND USE
4.1 This practice provides minimum recommendations for preparing and smoothing panel underlayments, thick poured gypsum concrete underlayments, thick poured lightweight cellular concrete underlayments and concrete subfloors with patching compounds. Actual requirements for materials to be used, mixtures, and other details are generally included as part of the project plans or specification details and may vary from the minimum recommendations set forth in this practice.
SCOPE
1.1 This practice includes recommendations for preparing and smoothing panel underlayments, gypsum concrete and concrete subfloors with patching compounds upon which resilient flooring may be installed.
1.2 This practice does not cover the adequacy of the subfloor assembly to perform its structural requirements, which is governed by local building codes.
1.3 This practice does not supersede in any manner the resilient flooring, underlayment or adhesive manufacturer’s written instructions. Consult the individual resilient flooring, underlayment or adhesive manufacturer for specific recommendations.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
- Standard4 pagesEnglish language
- Standard4 pagesEnglish language
SIGNIFICANCE AND USE
4.1 The effect of dynamic rolling load over resilient floor covering system is important since the resistance reflects the ability of a resilient floor covering system to properly perform under specific use or condition.
4.2 Excessive rolling load over an installed resilient floor covering may cause floor covering system failures such as bond failure, delamination, and finish or coating deteriorations.
4.3 The effect of dynamic rolling load shall be measured by qualitative evaluation comparing the tested assembly with a standard assembly.
SCOPE
1.1 This practice covers the determination of the effect of dynamic rolling load over a resilient floor covering.
1.2 This practice is intended to be used by resilient, adhesive and underlayment manufacturers to measure the impact of a dynamic rolling load over a specific product or a combination of products.
1.3 This practice may be used to evaluate the performance of joints (sealed or welded) in the resilient floor covering.
1.4 This practice may be used to aid in the diagnosis of a specific assembly performance and provide comparative evaluation.
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
- Standard3 pagesEnglish language
- Standard3 pagesEnglish language
SIGNIFICANCE AND USE
5.1 Moisture in concrete floor slabs affects the performance of flooring systems such as resilient, wood, and textile floor coverings and coatings. Manufacturers of such systems generally require moisture testing be performed before installation of coverings on floor slabs and screeds. The measurement of sub-surface comparative moisture condition in the upper 1.0 in. (25.4 mm) stratum of a concrete slab with a non-destructive moisture meter is one such method.
5.2 Excessive moisture in floor slabs after installation can cause floor covering system failures such as delamination, bonding failure, deterioration of finish flooring and coatings, and microbial growth.
5.3 5.3 Comparative moisture content tests indicate the moisture in the slab, which is usually referenced to the percentage of dry weight. That is:
Results indicate conditions at the time of the test.
5.4 Methods of meter calibration and factors affecting equilibration are described in Section 8.
SCOPE
1.1 This guide focuses on obtaining the comparative moisture condition within the upper 1.0 in. (25.4 mm) stratum in concrete, gypsum, anhydrite floor slabs and screeds for field tests. Due to the wide variation of material mixtures and additives used in floor slabs and screeds, this methodology may not be appropriate for all applications. See 1.2 through 1.8 and Section 11. Where appropriate or when specified use further testing as outlined in Test Methods F1869, F2170 or F2420 before installing a resilient floor covering.
1.2 This guide is intended for use to determine if there are moisture-related conditions existing on, or in, the floor slabs that could adversely impact the successful application and performance of resilient flooring products.
1.3 This guide may be used to aid in the diagnosis of failures of installed resilient flooring.
1.4 This guide is intended to be used in conjunction with meter manufacturer’s operation instructions and interpretive data where available.
1.5 Where possible, or when results need to be quantified use this standard guide to determine where additional testing such as Test Methods F1869, F2170, or F2420 as specified to characterize the floor slab and the test area environment for moisture, humidity and temperature conditions.
1.6 This guide may not be suitable for areas that have surface applied moisture migration systems, curing compounds or coatings that cannot be removed or cleaned off sufficiently to allow the moisture to move upwards through the slab. For a floor slab of 6 in. (150 mm) plus thickness, low porosity slabs, slabs with no vapor retarder installed, and slabs where the above surface environmental conditions can have a greater than normal influence on the moisture reduction gradient of the floor slab or screed, consider Test Method F2170 (below surface in situ rh method) as a more suitable test method under these circumstances.
1.7 This guide is not intended to provide quantitative results as a basis for acceptance of a floor for installation of moisture sensitive flooring finishes systems. Test Methods F1869, F2170, or F2420 provide quantitative information for determining if moisture levels are within specific limits. Results from this guide do not provide vital information when evaluating thick slabs, slabs without effective vapor retarders directly under the slab, lightweight aggregate concrete floors, and slabs with curing compound or sealers on the surface.
1.8 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.9 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitatio...
- Guide6 pagesEnglish language
- Guide6 pagesEnglish language
SIGNIFICANCE AND USE
4.1 This practice provides minimum recommendations for the installation and preparation of wood-based, fiber-reinforced gypsum and fiber-cement panel underlayments suitable to receive resilient floor coverings. Actual requirements for materials to be used, mixtures, and other details are generally included as part of project plans or specification detail and may vary from the minimum recommendations set forth in this practice.
SCOPE
1.1 This practice includes recommendations for the installation of panel type underlayments including wood based, fiber reinforced gypsum and fiber-cement panel underlayment/subfloor assemblies upon which resilient flooring may be installed.
1.2 The structural integrity of subfloor assemblies is governed by local building codes.
1.3 This practice does not supersede in any manner the resilient flooring, underlayment or adhesive manufacturer's written instructions. Consult the individual resilient flooring, underlayment or adhesive manufacturer for specific recommendations. Manufacturer's instructions supercede the recommendations included in this practice.
1.4 See Supplementary Requirements for “Select Warnings” that have been provided.
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
- Standard5 pagesEnglish language
- Standard5 pagesEnglish language
SIGNIFICANCE AND USE
4.1 Moisture permeating from concrete substrates can detrimentally affect the performance of resilient floor covering systems. All resilient flooring and adhesive manufacturers have a maximum acceptable level of moisture in which their products can perform satisfactorily. If pre-installation moisture tests indicate that the moisture level is unacceptable for the specified floor covering to be installed, one option is to apply a topical treatment to the concrete substrate surface to mitigate the moisture condition. Experience has shown that certain types of membrane-forming moisture mitigation systems have more desirable properties and successful performance than others. Requirements for membrane-forming moisture mitigation systems to be used, and other related details, are generally included as part of the project plans, or specification details, and may vary from the minimum recommendations set forth in this practice.
4.2 This practice is intended for use after it has been determined that a floor moisture condition exceeds the resilient floor covering or adhesive manufacturer’s requirements, or both, as tested according to Test Methods F1869, F2170, and F2420.
4.3 Membrane-forming moisture mitigation systems are not intended for use over gypsum-based substrates or other moisture sensitive substrates.
SCOPE
1.1 This practice covers the properties, application, and performance of a two-component resin based membrane-forming moisture mitigation system to high moisture concrete substrates prior to the installation of resilient flooring.
1.2 This practice includes recommendations for the preparation of the concrete surface to receive a two-component resin based membrane-forming moisture mitigation system.
1.3 This practice does not supersede written instructions of the two-component resin based membrane-forming moisture mitigation system manufacturer, the resilient flooring manufacturer, underlayment manufacturer, the adhesive manufacturer, or other components of the finish flooring system, or combinations thereof. Users of this practice shall review manufacturer’s technical data sheets and installation instructions for compatibility of system components.
1.4 The following membrane-forming or non membrane-forming moisture mitigation systems are not included in the scope of this practice:
1.4.1 Moisture mitigation systems that chemically react with any constituent of the concrete to form a gel or crystalline substance within the concrete.
1.4.2 Penetrating, water- or solvent-based compounds that do not form a continuous membrane on the concrete surface.
1.4.3 Water-based membrane-forming moisture mitigation systems are not included in the scope of this document.
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
- Standard4 pagesEnglish language
SIGNIFICANCE AND USE
4.1 This practice provides minimum recommendations for the installation of self-leveling underlayments suitable to receive resilient floor coverings. This practice establishes the proper preparation of the subfloor, and installation methods and quality control requirements for self-leveling underlayments. This practice addresses the preparation of the self-leveling underlayment’s surface prior to the installation of floor coverings.
4.2 Actual requirements for self-leveling underlayments are generally included as part of project plans or specifications and may vary from the recommendations set forth in this practice. Provisions in the project documents at variance with this practice shall take precedence.
SCOPE
1.1 This practice covers the installation of self-leveling underlayments, which may include a priming system, over solid wood, wood structural panel subfloors, over concrete, and over certain solidly bonded existing flooring systems such as epoxy floors, ceramic and natural stone tiles, terrazzo, as well as properly prepared non water-soluble adhesive residues as recommended by the underlayment manufacturer. This practice also covers the preparation of the self-leveling underlayment’s surface prior to the installation of resilient flooring.
1.2 This practice points out the factors that are required to be controlled while installing a self-leveling underlayment to be used as a substrate for resilient flooring.
1.3 This practice does not cover the structural adequacy of the subfloor. The structural integrity of assemblies is governed by local building codes and may be superseded by the resilient flooring manufacturer's requirements.
1.4 This practice does not supersede the self-leveling underlayment manufacturer’s, adhesive manufacturer’s or resilient flooring manufacturer’s written instructions. Consult the individual manufacturer for specific recommendations.
1.5 Many self-leveling underlayments are not suitable for use on concrete slabs on grade or below due to potential moisture problems arising from moisture intrusion. This may occur unless an adequate vapor retarder or vapor barrier is present directly beneath the concrete slab or an effective moisture remediation system has been installed beneath the surface of the self-leveling underlayment. Consult the manufacturer of the self-leveling underlayment and flooring system for specific recommendations.
1.6 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.7 This practice does purport to address the necessity for or the safe or correct removal of asbestos containing materials. Breathing of asbestos dust is hazardous. Asbestos and asbestos products present demonstrated health risks for users and for those with whom they come into contact. In addition to other precautions, when working with asbestos-cement products, minimize the dust that results. For information on the safe use of chrysoltile asbestos, refer to “Safe Use of Chrysotile Asbestos: A Manual on Preventive and Control Measures.”2
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
- Standard5 pagesEnglish language
SIGNIFICANCE AND USE
4.1 This practice provides minimum recommendations for the installation of thick poured lightweight cellular concrete floor underlayments suitable to receive resilient floor coverings. This practice establishes the proper preparation, installation and quality control for thick poured lightweight cellular concrete floor underlayments.
4.2 Actual requirements for thick poured lightweight cellular concrete underlayments are generally included as part of project plans or specifications and may vary from the recommendations set forth in this practice. Project plans or specifications, or both, shall supersede the recommendations set forth in this practice.
SCOPE
1.1 This practice covers the installation and preparation of the thick poured lightweight cellular concrete underlayments over wood structural panel subfloors in commercial structures or over concrete floors in commercial structures and the preparation of the thick poured lightweight cellular concrete underlayment surface prior to the installation of resilient flooring in commercial buildings.
1.2 This practice points out the factors that are required to be controlled while installing thick poured lightweight cellular concrete underlayment as a base for resilient flooring.
1.3 This practice does not cover the structural adequacy of the wood structural panel subfloor or concrete subfloor. The structural integrity of assemblies is governed by local building codes.
1.4 This practice does not supercede the thick poured lightweight cellular concrete underlayment manufacturers', adhesive manufacturers' or resilient flooring manufacturers' written instructions. Consult the individual manufacturer for specific recommendations.
1.5 Thick poured lightweight cellular concrete underlayments are not suitable for use on concrete slabs on ground due to potential moisture problems arising from moisture intrusion, unless an adequate vapor retarder or vapor barrier is present directly beneath the concrete subfloor.
1.6 The values stated in inch-pound units are to be regarded as standard. The values stated in parentheses are mathematical conversions to SI Units, which are provided for information only.
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
- Standard4 pagesEnglish language
- Standard4 pagesEnglish language
SIGNIFICANCE AND USE
4.1 Seams in some resilient flooring are heat sealed to prevent openings from forming between cut edges and to prevent penetrations of dirt, liquids, etc., into the seams. Decorative appearances may also be achieved using contrasting heat weld thread (rod).
SCOPE
1.1 This practice covers the instructions and precautions to be observed to ensure satisfactory performance of seams in resilient flooring sealed by the heat weld method.
1.2 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. See precaution information in 6.1.
- Standard2 pagesEnglish language
- Standard2 pagesEnglish language
SIGNIFICANCE AND USE
Seams in some sheet resilient flooring are sealed to prevent openings from forming between cut edges and prevent penetrations of dirt, liquids, etc., into the seams.
SCOPE
1.1 This practice covers the instructions and precautions to be observed to ensure satisfactory performance of seams in sheet resilient flooring sealed with liquid seam sealers.
1.2 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
- Standard2 pagesEnglish language
SIGNIFICANCE AND USE
Moisture permeating from concrete floor slabs affects the performance of flooring systems such as resilient and textile floor coverings and coatings. Manufacturers of such systems generally require moisture testing to be performed before installation on concrete. Internal relative humidity testing is one such method.
Excessive moisture permeating from floor slabs after installation can cause floor covering system failures such as debonding and deterioration of finish flooring and coatings and microbial growth.
Moisture test results indicate the moisture condition of the slab only at the time of the test.
SCOPE
1.1 This test method covers the quantitative determination of percent relative humidity in concrete slabs for field or laboratory tests.
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
Specific warnings are given in Section 7, 10.3.2, and 10.4.4.
- Standard5 pagesEnglish language
- Standard5 pagesEnglish language
Frequently Asked Questions
F06.40 is a Technical Committee within ASTM International. It is named "Practices". This committee has published 88 standards.
F06.40 develops ASTM standards in the area of Information technology. Currently, there are 88 published standards from this technical committee.
ASTM is a standardization organization that develops and publishes standards to support industry, commerce, and regulatory requirements.
A Technical Committee (TC) in ASTM is a group of experts responsible for developing international standards in a specific technical area. TCs are composed of national member body delegates and work through consensus to create standards that meet global industry needs. Each TC may have subcommittees (SCs) and working groups (WGs) for specialized topics.