ASTM F2519-05(2011)
(Test Method)Standard Test Method for Grease Particle Capture Efficiency of Commercial Kitchen Filters and Extractors
Standard Test Method for Grease Particle Capture Efficiency of Commercial Kitchen Filters and Extractors
SIGNIFICANCE AND USE
The pressure drop results can be added to the pressure drops of other components in an exhaust system to determine the total exhaust fan pressure requirement.
The particulate capture efficiency can be used with known particulate size emission data for a cooking appliance-food product combination to determine the total mass of grease particles captured by the filter, the total mass of grease particles that pass through the filter, and the particle size distribution of the grease particles that pass through the filter. Fig. 1 shows an example particle capture efficiency curve.
FIG. 1 Particle Capture Efficiency Example Curve
SCOPE
1.1 This test method can be used to determine the grease particle capture efficiency of components and systems used in commercial kitchens to capture grease effluent prior to entering the exhaust duct. The results can be used to select a filter system best suited to a particular application.
1.2 This test method is applicable to filter components and systems. The performance information is obtained for new or clean filters and does not include the performance of used or loaded filters.
1.3 The filter can be evaluated with respect to the following (where applicable):
1.3.1 Pressure drop as a function of airflow through the filter (10.3), and
1.3.2 Particulate capture efficiency by particle size (10.4).
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are for information only.
1.5 This test method may involve hazardous materials, operations, and equipment. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
General Information
Relations
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: F2519 − 05(Reapproved 2011) An American National Standard
Standard Test Method for
Grease Particle Capture Efficiency of Commercial Kitchen
Filters and Extractors
This standard is issued under the fixed designation F2519; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 2.2 ISO Standard:
ISO Standard 3966, Measurement of Fluid Flow in Closed
1.1 This test method can be used to determine the grease
Conduits—VelocityArea Method Using Pitot StaticTubes
particle capture efficiency of components and systems used in
commercial kitchens to capture grease effluent prior to entering
3. Terminology
the exhaust duct. The results can be used to select a filter
3.1 Definitions:
system best suited to a particular application.
3.1.1 airflow rate, n—volumetric flow rate of air that passes
1.2 This test method is applicable to filter components and
through a filter or a bank of filters.
systems. The performance information is obtained for new or
3.1.2 capture effıciency, n—proportion of aerosol particles
clean filters and does not include the performance of used or
removed by a filter as a function of particle size, usually
loaded filters.
expressed as a percentage.
1.3 The filter can be evaluated with respect to the following
3.1.3 cartridge filter, n—removable extractor, a removable,
(where applicable):
integral component of listed exhaust hoods, which is typically
1.3.1 Pressuredropasafunctionofairflowthroughthefilter
constructed of stainless steel and containing a series of
(10.3), and
horizontal baffles designed to remove grease and drain it into a
container.
1.3.2 Particulate capture efficiency by particle size (10.4).
3.1.4 fixed extractor, n—water-wash hood or linear slot
1.4 The values stated in inch-pound units are to be regarded
hood, a fixed, integral component of listed exhaust hoods,
as standard. The values given in parentheses are for informa-
which is typically constructed of stainless steel and containing
tion only.
aseriesofhorizontalbafflesthatrunthefulllengthofthehood.
1.5 This test method may involve hazardous materials,
3.1.5 grease filter, n—device installed into a hood to capture
operations, and equipment. This standard does not purport to
grease effluent before it enters the exhaust duct. Several
address all of the safety concerns, if any, associated with its
identical devices may be installed in parallel in a hood. The
use. It is the responsibility of the user of this standard to
device may consist of more than one component or section.
establish appropriate safety and health practices and deter-
3.1.6 pressure drop, n—change in static pressure between
mine the applicability of regulatory limitations prior to use.
the front surface of the grease filter and its rear surface under
the rated airflow rate conditions.
2. Referenced Documents
3.1.7 reference hood, n—Type I exhaust hood used for the
2.1 ASHRAE Standard:
“no extractors” condition when measuring the efficiency and
ANSI/ASHRAE Standard 52.2-1999, Method of Testing
pressure drop of fixed extractor hoods. This is typically the
General Ventilation Air-Cleaning Devices for Removal
same hood that is used for testing removable grease filters and
Efficiency by Particle Size
removable cartridge filters.
3.2 Symbols:
This test method is under the jurisdiction of ASTM Committee F26 on Food
Service Equipment and is the direct responsibility of Subcommittee F26.07 on
E = capture efficiency
Commercial Kitchen Ventilation.
n = number of sample sets
Current edition approved Oct. 1, 2011. Published January 2012. Originally
approved in 2005. Last previous edition approved in 2005 as F2519 – 05. DOI:
10.1520/F2519-05R11.
Available from American Society of Heating, Refrigerating, and Air-
Conditioning Engineers, Inc. (ASHRAE), 1791 Tullie Circle, NE, Atlanta, GA Available from International Organization for Standardization (ISO), 1 rue de
30329. Varembé, Case postale 56, CH-1211, Geneva 20, Switzerland.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
F2519 − 05 (2011)
equivalent 250 cfm per linear foot (width) of filter (based on
P = penetration
external filter dimensions).
t = t distribution variable
4.3.1 Performancemayalsobeevaluatedatotherairflowsin
T = sampling time
W = counts of each size range (or channel) with test accordance with manufacturer recommendations (see Appen-
device(s) installed dix X1).
WO = counts of each size range (or channel) without test
4.4 Balanced makeup air shall be provided at 75 6 5°F and
device(s)
50 6 20 % RH.
δ = standard deviation of a sample
4.5 Particulate capture efficiency for removable grease filter
or removable cartridges is determined by comparing particle
concentration versus size in the exhaust duct with and without
3.3 Subscripts:
the filters installed.
4.5.1 Particulate capture efficiency for hoods with fixed
b = background
extractorsisdeterminedbycomparingparticleconcentrationas
c = correlation
a function of particle size in the exhaust duct with the fixed
e = estimated
i = sample number extractor hood and the reference hood without the filters
lcl = lower confidence limit installed.
n = number of sample sets
4.5.2 The test aerosol is oleic acid that covers a size range
o = observed
from 0.3 to 10 µm in diameter or as specified by the
t = testing a filter
manufacturer. Efficiency shall be reported as zero from 0.3 µm
ucl = upper confidence limit
to the lower limit of the test conditions. Particulate concentra-
w = with test device(s) installed
tion measurements (as a function of particle size) are taken in
wo = without test device(s) installed
the exhaust duct using an isokinetic sampling probe and an
optical particle counter. The particulate capture efficiency is
4. Summary of Test Method
determined by taking the difference between the particle
4.1 There are three predominant classes of filters in kitchen
concentration with and without the filters installed at each
ventilation grease extraction systems: removable baffle filters,
particle size range set on the particle counter.
removable cartridge filters, and fixed extractors.
4.2 Removable baffle and cartridge filters to be tested are
5. Significance and Use
installed into the test system.
5.1 The pressure drop results can be added to the pressure
4.2.1 Identical filters to be tested are installed into a
drops of other components in an exhaust system to determine
standard 4-ft canopy hood connected to a nominal 12-in. round
the total exhaust fan pressure requirement.
duct exhaust system. The filters should fit tightly together and
1 5.2 The particulate capture efficiency can be used with
into the opening and any bypasses larger than ⁄8-in. wide on
known particulate size emission data for a cooking appliance-
the ends are sealed.
food product combination to determine the total mass of grease
4.2.2 For fixed-extractor systems, a reference hood shall be
particlescapturedbythefilter,thetotalmassofgreaseparticles
used for testing conditions that call for no filters to be installed
that pass through the filter, and the particle size distribution of
in the hood. Testing requires switching between the reference
the grease particles that pass through the filter. Fig. 1 shows an
hood and the fixed extractor hood.
example particle capture efficiency curve.
4.2.3 A filter system to be used in a non-standard canopy
hood is installed at the height of actual application above the
6. Apparatus
floor and connected to a nominal 12-in. round duct exhaust
6.1 Mandatory and Discretionary Requirements—Critical
system.
4.2.4 Thestaticpressuredropacrossthefiltersisrecordedat dimensions and arrangements of the test apparatus are shown
the test airflow. in Figs. 2-5. Vertical ductwork may also be used with the same
4.2.4.1 For removable baffle or cartridge filters, the net filter critical dimensions (duct diameter, length, and so forth). All
pressure drop is determined by subtracting the pressure drop of dimensions shown are mandatory unless otherwise indicated.
the hood when the filters are removed from the pressure drop Units shown are in inches unless otherwise indicated. The
measured when the filters are installed. The total exhaust design of equipment not specified, including but not limited to
volumetric flow rate must be equal in both pressure drop exhaust fan, makeup air system, and external structural
measurements. supports, is discretionary, but the equipment must have ad-
4.2.4.2 For fixed-extractor hood systems, the pressure drop equate capacity to meet the requirements of this test method.
is determined by subtracting the pressure drop of the reference
6.2 Test Facility:
hood when the filters are removed from the pressure drop
6.2.1 Exhaust Hood:
measured on the fixed-extractor hood. The total exhaust
6.2.1.1 The test installation should have a canopy exhaust
volumetric flow rate must be equal in both pressure drop
hoodwhichmeetstheserequirements:4ft(1.2m)inwidthand
measurements.
depth, minimum 2 ft (0.61 m) in height, wall mounted with the
4.3 The total airflow rate through the exhaust system is set lower edge of the hood 6 ⁄2 ft (2.0 m) from the floor and with
so that the volumetric flow rate through the filter under test is a 12 in. (0.305 m) diameter round duct collar mounted on top
F2519 − 05 (2011)
FIG. 1 Particle Capture Efficiency Example Curve
FIG. 2 Schematic Diagram of Test Apparatus—Front Elevation View of Horizontal Test Setup
in the center of the hood with the rear surface of the opening 1.0 in. from the back side of the hood. If the hood is installed
F2519 − 05 (2011)
FIG. 3 Schematic Diagram of Test Apparatus—Front Elevation of
Vertical Test Setup
F2519 − 05 (2011)
6. If the hood with fixed extractors cannot be built to match
6.2.1.1,thenthereferencehoodshallbebuilttomatchthehood
with fixed extractors.
6.2.1.4 To facilitate switching hoods, the lab may build
rolling stands for each reference hood and the current hood
being tested. These stands may be rolled in and out of the test
rig. Care should be taken to insure that both hoods are installed
in the same location at the same height (6 ⁄2 ft) each time.
6.2.1.5 The test apparatus shown in Figs. 2-5 is designed for
test filters with a nominal height of 20 in. It is permitted to test
a bank of several filters in parallel if the width of an individual
filtration device is less than 50 % of the width of the hood.
Spacers may be added symmetrically on both ends of the filter
under test if the filter does not span the entire width of the
FIG. 4 Schematic Diagram of Test Apparatus—Plan View
hood.
6.2.2 Round Exhaust Duct, 12 in. (0.305 m) in diameter,
connected to the duct collar on the top of the exhaust hood and
leading to an exhaust fan.All duct connections shall be sealed.
The duct may be horizontal or vertical. If horizontal, it must
have a 90-degree elbow configured as shown in Fig. 7. The
elbow must have a centerline duct radius of 14-in.
NOTE 1—The r/D ratio is 1.167 for this configuration.
6.2.2.1 The distance from the duct collar for a vertical
exhaust duct or from the end of the 90 degree elbow for a
horizontal exhaust duct to the sampling location shall be 84 in.
If a different sampling location is used, or a different exhaust
configuration is used, an aerosol uniformity test shall be
conducted.
6.2.2.2 The minimum distance from the sampling location
to the nearest duct fitting or fan inlet shall be 24 in.
6.2.3 Exhaust Fan, capable of moving 1000 ft /min (472
L/s) through the filters under test and the additional exhaust
system components at the test static pressure condition. The
fan shall have a variable frequency drive or other means to
control the airflow rate. The exhaust shall be discharged
outdoors.
6.2.4 MakeupAir System, a means for providing makeup air
at 75 6 5°F and 50 6 20 % relative humidity to match exhaust
rate without disturbing the airflow pattern near the exhaust
hood.
6.2.5 Heat Source, a uniform electric heat source with a
solid metal surface, a minimum 2 ft. deep by 3 ft. wide,
maintained at an average surface temperature of 375 6 5°F.
FIG. 5 Schematic Diagram of Test Apparatus—Side Elevation
NOTE 2—A commercial electric griddle with a rated input between 7
View and 10 kW and been shown to work well as a heat source.
6.2.5.1 The cooking surface of the heat source shall be 32
in. (0.81 m) above the floor. The heat source shall be centered
under the hood from side to side and from front to back. Any
at a different height, a distance of 46 in. must be maintained
air gap between the rear of the heat source and the back wall
between the appliance surface and bottom of the hood. The
shall be sealed with a horizontal sheet of stainless steel
hood shall contain means for securing grease filters under test
positioned at the same height as the rear of the heat source.
in a position typical in application.
6.3 Instrumentation:
6.2.1.2 Hoods with fixed extractors should be built to match
the description given in 6.2.1.1 as closely as possible without 6.3.1 Flow Metering Station, installed in the exhaust duct
affecting the hood’s extraction efficiency. for measuring the airflow rate through the filters under test.
6.2.1.3 The typical reference hood will be a canopy exhaust Options include a grid of local velocity measurements using
hood matching the one described in 6.2.1.1 and shown in Fig. the log-Tchebycheff method, a flow nozzle, or an orifice plate.
F2519 − 05 (2011)
FIG. 6 Schematic Diagram of Reference Hood
made with and without the test filters installed to set the fan
speed for proper airflow rate at each test condition.
6.3.2 Barometer, for measuring absolute pressure of the air
entering the exhaust hood. The barometer shall have a resolu-
tion of 0.2 in. Hg (670 Pa).
6.3.3 Differential Pressure Gage,formeasuringthepressure
drop across the filters under test. The pressure gage shall have
a range from 0 to 5 in. water (0 to 2.5 kPa), and have an
accuracy of 1 % at full scale.
6.3.4 Temperature Sensors, industry standard Type T or K
thermocouples, one mounted at the inlet to the particle sam-
pling probe in the exhaust duct to measure the temperature of
the exhaust, the other located 6 ⁄2 ft from the floor and 6 ft in
front of the center of the exhaust hood with radiation shielding
FIG. 7 Schematic Diagram of 90-Degree Elbow to Connect the
Duct Collar on the Canopy Hood
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.